A-2YF(L)2Y – Water-Blocked Telecommunications Cable
PE-insulated copper telecommunications cable with star-quad construction, petrolatum gel filling, laminated aluminium screen and black polyethylene outer sheath. Designed for local communication networks, underground installations and low-frequency industrial communication systems.
Product Overview
A-2YF(L)2Y is a screened, polyethylene-insulated telecommunications cable designed for local communication networks and predominantly low-frequency installations.
The cable incorporates solid bare copper conductors with nominal diameters of 0.6 mm or 0.8 mm. Individual conductors are insulated with polyethylene and arranged in star quads.
The interstices of the cable core are continuously filled with petrolatum gel to provide longitudinal protection against water penetration.
A plastic-coated aluminium tape forms the electrostatic screen and contributes to transverse moisture protection. The outer sheath consists of black polyethylene.
The longitudinally and transversely water-blocked construction is suitable for underground installations, cable ducts, conduits and communication networks within industrial and operational facilities.
Key Technical Features
Cable Variants
0.6 mm Copper Conductor
2–100 pairs
Solid bare copper conductors with a nominal diameter of 0.6 mm.
Conductor loop resistance: 130.0 Ω/km.
Approximate outer diameter: 8.3–30.3 mm.
Eight reference configurations.
0.8 mm Copper Conductor
2–150 pairs
Solid bare copper conductors with a nominal diameter of 0.8 mm.
Conductor loop resistance: 73.2 Ω/km.
Approximate outer diameter: 8.8–42.2 mm.
Ten reference configurations.
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Water-Blocking Construction
Longitudinal Water Protection
The cable core interstices are continuously filled with petrolatum gel to restrict longitudinal water migration within the cable.
Transverse Water Protection
The plastic-coated aluminium tape and polyethylene outer sheath provide the transverse moisture-protection construction specified for this cable type.
Typical Applications
Installation Methods
A-2YF(L)2Y telecommunications cables are suitable for installation directly in the ground, in conduits and in cable ducts.
The specified minimum bending radius during bending is 15 times the overall cable diameter.
The permitted temperature range during bending is -20°C to +50°C. For fixed installations, the specified temperature range is -20°C to +70°C.
Installation conditions and mechanical protection requirements must be assessed for the individual project.
Applicable Standards
DIN VDE 0816 – Reference standard for core identification.
DIN EN 60228, Class 1 – Reference standard for solid conductor construction.
A-2YF(L)2Y – Cable Sizes & Technical Data
Complete reference range of water-blocked copper telecommunications cables with 0.6 mm and 0.8 mm solid copper conductors, including cable dimensions, copper content, cable weights, electrical characteristics and installation parameters.
Available Cable Sizes & Construction Data
| Cable Size | Number of Pairs | Conductor Diameter (mm) | Copper Content (kg/km) | Insulation Thickness* (mm) | Approx. Outer Diameter (mm) | Approx. Weight (kg/km) |
|---|---|---|---|---|---|---|
| A-2YF(L)2Y – 0.6 mm Solid Copper Conductors | ||||||
| 2x2x0.6 | 2 | 0.6 | 12.5 | 1.8 | 8.3 | 67 |
| 6x2x0.6 | 6 | 0.6 | 34.6 | 1.8 | 11.0 | 126 |
| 10x2x0.6 | 10 | 0.6 | 56.6 | 1.8 | 12.5 | 171 |
| 20x2x0.6 | 20 | 0.6 | 110.4 | 1.8 | 15.8 | 287 |
| 30x2x0.6 | 30 | 0.6 | 165.1 | 1.8 | 19.0 | 409 |
| 40x2x0.6 | 40 | 0.6 | 218.9 | 1.8 | 20.4 | 503 |
| 50x2x0.6 | 50 | 0.6 | 273.6 | 1.8 | 22.2 | 606 |
| 100x2x0.6 | 100 | 0.6 | 545.3 | 2.0 | 30.3 | 1155 |
| A-2YF(L)2Y – 0.8 mm Solid Copper Conductors | ||||||
| 2x2x0.8 | 2 | 0.8 | 21.1 | 1.8 | 8.8 | 83 |
| 4x2x0.8 | 4 | 0.8 | 39.4 | 1.8 | 11.2 | 134 |
| 6x2x0.8 | 6 | 0.8 | 59.5 | 1.8 | 12.0 | 165 |
| 10x2x0.8 | 10 | 0.8 | 98.9 | 1.8 | 14.0 | 232 |
| 20x2x0.8 | 20 | 0.8 | 194.9 | 1.8 | 19.1 | 445 |
| 30x2x0.8 | 30 | 0.8 | 291.8 | 1.8 | 22.0 | 588 |
| 40x2x0.8 | 40 | 0.8 | 387.8 | 2.0 | 24.0 | 748 |
| 50x2x0.8 | 50 | 0.8 | 484.8 | 2.0 | 26.0 | 910 |
| 100x2x0.8 | 100 | 0.8 | 967.7 | 2.2 | 36.0 | 1787 |
| 150x2x0.8 | 150 | 0.8 | 1451.5 | 2.2 | 42.2 | 2553 |
Cable sizes are expressed as number of pairs x two conductors x nominal conductor diameter in millimetres. Cable diameters and weights are approximate.
*The thickness values of 1.8–2.2 mm are reproduced under the insulation thickness heading used in the reference documentation. The specific cable layer to which these values apply must be confirmed before technical approval.
Conductor Characteristics
| Parameter | 0.6 mm Conductor | 0.8 mm Conductor |
|---|---|---|
| Materijal vodiča | Bare Copper | Bare Copper |
| Conductor Construction | Solid, Class 1 | Solid, Class 1 |
| Nominal Conductor Diameter | 0.6 mm | 0.8 mm |
| Calculated Geometric Cross-Section | 0.283 mm² | 0.503 mm² |
| Conductor Loop Resistance | 130.0 Ω/km | 73.2 Ω/km |
| Number of Pairs | 2–100 | 2–150 |
| Reference Configurations | 8 | 10 |
| Core Arrangement | Star Quads | Star Quads |
| Core Insulation | PE | PE |
Geometric conductor cross-sections are calculated from the nominal conductor diameters using the circular area formula. They are not independently declared nominal cross-sections.
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Peak Operating Voltage | 225 V |
| Test Voltage Core/Core at 50 Hz | 500 V AC |
| Test Voltage Core/Screen at 50 Hz | 2000 V AC |
| Loop Resistance – 0.6 mm | 130.0 Ω/km |
| Loop Resistance – 0.8 mm | 73.2 Ω/km |
| Minimum Insulation Resistance | 1500 MΩ/km |
| Maximum Operating Capacitance | 52 nF/km |
| Maximum Capacitance Unbalance per 100 m | 800 pF |
Temperature & Mechanical Characteristics
| Parameter | Reference Value |
|---|---|
| Temperature During Bending | -20°C to +50°C |
| Fixed Installation Temperature | -20°C to +70°C |
| Minimum Bending Radius During Bending | 15 x D |
| Longitudinal Water Blocking | Yes |
| Transverse Water Blocking | Yes |
| Underground Installation | Suitable |
| Conduit Installation | Suitable |
| Cable Duct Installation | Suitable |
Minimum Cable Bending Radius
| Cable Size | Approx. Outer Diameter (mm) | Calculated Minimum Bending Radius – 15 x D (mm) |
|---|---|---|
| 0.6 mm Conductor Diameter | ||
| 2x2x0.6 | 8.3 | 124.5 |
| 6x2x0.6 | 11.0 | 165 |
| 10x2x0.6 | 12.5 | 187.5 |
| 20x2x0.6 | 15.8 | 237 |
| 30x2x0.6 | 19.0 | 285 |
| 40x2x0.6 | 20.4 | 306 |
| 50x2x0.6 | 22.2 | 333 |
| 100x2x0.6 | 30.3 | 454.5 |
| 0.8 mm Conductor Diameter | ||
| 2x2x0.8 | 8.8 | 132 |
| 4x2x0.8 | 11.2 | 168 |
| 6x2x0.8 | 12.0 | 180 |
| 10x2x0.8 | 14.0 | 210 |
| 20x2x0.8 | 19.1 | 286.5 |
| 30x2x0.8 | 22.0 | 330 |
| 40x2x0.8 | 24.0 | 360 |
| 50x2x0.8 | 26.0 | 390 |
| 100x2x0.8 | 36.0 | 540 |
| 150x2x0.8 | 42.2 | 633 |
The minimum bending radii are calculated using the approximate outer diameters and the specified bending factor of 15 x D. Actual installation limits must be confirmed using the supplied cable dimensions.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Solid Bare Copper, Ø 0.6 or 0.8 mm |
| 2 | Core Insulation | Polyethylene (PE) |
| 3 | Core Filling and Wrapping | Continuous Petrolatum Gel Filling and Plastic Foil |
| 4 | Electrostatic Screen | Plastic-Coated Aluminium Tape |
| 5 | Outer Sheath | Black Polyethylene (PE) |
Applicable Standards
| Standard | Reference Application |
|---|---|
| DIN VDE 0816 | Core Identification |
| DIN EN 60228, Class 1 | Solid Conductor Construction |