H07BQ-F / X07BQ-F 450/750 V
Flexible PUR Rubber Cable | Class 5 Copper | EPR Insulation | Oil, Abrasion & Impact Resistant
Product Description
H07BQ-F and X07BQ-F are flexible power and connection cables designed for electrical equipment operating in demanding industrial and construction environments under medium mechanical stress.
The cable construction combines fine-stranded Class 5 bare copper conductors, ethylene propylene rubber (EPR) insulation and a durable polyurethane (PUR) outer sheath.
The PUR outer sheath provides high resistance to oil, abrasion and mechanical impact, making these cables suitable for connecting electrical tools and portable industrial equipment.
The cables are intended for dry and wet environments, cold environments and temporary outdoor use within the specified operating conditions.
Key Features
- Flexible Class 5 copper conductors.
- Durable polyurethane (PUR) outer sheath.
- EPR rubber insulation, type EI6.
- High resistance to oil and abrasion.
- High resistance to mechanical impact.
- Suitable for dry and wet environments.
- Suitable for temporary outdoor use.
- Suitable for medium mechanical stress.
- Available with and without filler.
Primjene
- Electrical tools on construction sites.
- Portable electrical equipment.
- Industrial machinery and equipment.
- Manufacturing and production facilities.
- Industrial maintenance operations.
- Electrical equipment in cold environments.
- Temporary outdoor electrical connections.
- Industrial environments requiring resistance to oil, abrasion and mechanical impact.
Cable Versions
| Designation | Construction |
|---|---|
| H07BQ-F | With filler |
| H07BQ-F | Without filler |
| X07BQ-F | With filler |
| X07BQ-F | Without filler |
Cable Construction
| Component | Description |
|---|---|
| Conductor | Bare copper |
| Conductor Class | Class 5, fine-stranded according to DIN EN IEC 60228 (VDE 0295) |
| Core Insulation | Ethylene propylene rubber (EPR), EI6 |
| Filler | Depending on cable version |
| Outer Sheath | Polyurethane (PUR) |
| Sheath Colour | Orange; black for selected sizes |
| Core Identification | According to VDE 0293 / HD 308, depending on cable version |
| Protective Conductor | Depending on cable configuration |
Technical Characteristics
| Parameter | Value |
|---|---|
| Rated Voltage Uo/U | 450/750 V |
| Maximum Conductor Temperature | +90°C |
| Permitted Outer Cable Temperature – Fixed | -40°C to +50°C |
| Minimum Bending Radius – Fixed | 4 × outer cable diameter |
| Bending Radius – Moving | 12.5 × outer cable diameter |
| Mechanical Stress | Medium |
| Oil Resistance | IEC 60811-404 |
| Abrasion Resistance | High |
| Impact Resistance | High |
| Flame Retardancy | Not flame-retardant |
| Outdoor Installation | Temporary outdoor use |
| Installation Environment | Dry and wet environments |
Standardi
- DIN EN 50525-2-21 (VDE 0285-525-2-21).
- DIN EN IEC 60228 / VDE 0295 – Class 5 flexible copper conductors.
- DIN EN 60811-404 / VDE 0473-811-404 / IEC 60811-404 – Oil resistance.
- VDE 0293 / HD 308 – Core identification.
Available Cross-Sections
- H07BQ-F: 1 mm² to 16 mm².
- X07BQ-F: 1.5 mm² to 300 mm².
- Single-core and multicore configurations.
- Available configurations depend on the cable designation and construction.
Installation Conditions
When installed in pipes or similar enclosed systems, the reference technical documentation permits use at voltages up to 1000 V AC or 750 V DC against earth, subject to the applicable installation requirements.
H07BQ-F / X07BQ-F – Technical Data & Dimensions
450/750 V | Class 5 Copper | EPR EI6 Insulation | PUR Outer Sheath
H07BQ-F – With Filler
| Nominal Size mm² |
Sheath Colour | Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|---|
| 4G6 | Orange | 3.3 | 37 | 16.2 | 230 | 391 |
| 5G6 | Orange | 3.3 | 38 | 17.9 | 288 | 472 |
| 4G10 | Orange | 1.91 | 52 | 21.6 | 384 | 722 |
| 5G10 | Orange | 1.91 | 54 | 23.2 | 480 | 840 |
| 4G16 | Orange | 1.21 | 69 | 24.2 | 614.4 | 980 |
| 5G16 | Orange | 1.21 | 71 | 26.9 | 768 | 1192 |
H07BQ-F – Without Filler
| Nominal Size mm² |
Sheath Colour | Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|---|
| 1 mm² | ||||||
| 2×1 | Crna | 19.5 | 15 | 7.4 | 19.2 | 66 |
| 1.5 mm² | ||||||
| 2×1.5 | Orange | 13.3 | 18.5 | 8.4 | 28.8 | 86 |
| 3G1.5 | Orange | 13.3 | 19.5 | 8.9 | 43.2 | 100 |
| 4G1.5 | Orange | 13.3 | 16 | 9.9 | 57.6 | 136 |
| 5G1.5 | Orange | 13.3 | 16.5 | 10.8 | 72 | 164 |
| 2.5 mm² | ||||||
| 2×2.5 | Orange | 7.98 | 25 | 10.0 | 48 | 125 |
| 3G2.5 | Orange | 7.98 | 26 | 10.6 | 72 | 155 |
| 4G2.5 | Orange | 7.98 | 22 | 11.8 | 96 | 201 |
| 5G2.5 | Orange | 7.98 | 23 | 13.1 | 120 | 244 |
| 4 mm² | ||||||
| 3G4 | Orange | 4.95 | 35 | 12.9 | 115.2 | 211 |
| 4G4 | Orange | 4.95 | 30 | 14.5 | 154 | 254 |
| 5G4 | Orange | 4.95 | 30 | 16.0 | 192 | 336 |
| 6 mm² | ||||||
| 4G6 | Orange | 3.3 | 37 | 16.2 | 230.4 | 436 |
| 5G6 | Orange | 3.3 | 38 | 17.9 | 288 | 518 |
| 10 mm² | ||||||
| 4G10 | Orange | 1.91 | 52 | 21.6 | 384 | 722 |
| 5G10 | Orange | 1.91 | 54 | 23.2 | 480 | 864 |
| 16 mm² | ||||||
| 4G16 | Orange | 1.21 | 69 | 24.2 | 614.4 | 1103 |
| 5G16 | Orange | 1.21 | 71 | 26.9 | 768 | 1382 |
X07BQ-F – With Filler
| Nominal Size mm² |
Sheath Colour | Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|---|
| Single-Core Cables | ||||||
| 1×25 | Orange | 0.78 | 94 | 13.8 | 240 | 375 |
| 1×35 | Orange | 0.554 | 117 | 15.4 | 336 | 492 |
| 1×50 | Orange | 0.386 | 148 | 17.7 | 480 | 675 |
| 1×70 | Orange | 0.272 | 185 | 20.0 | 672 | 908 |
| 1×95 | Orange | 0.206 | 222 | 22.2 | 912 | 1171 |
| 1×120 | Orange | 0.161 | 260 | 24.6 | 1152 | 1445 |
| 1×150 | Orange | 0.129 | 300 | 26.9 | 1440 | 1783 |
| 1×185 | Orange | 0.106 | 341 | 28.9 | 1776 | 2125 |
| 1×240 | Orange | 0.0801 | 407 | 32.7 | 2304 | 2733 |
| 1×300 | Orange | 0.0641 | 468 | 36.5 | 2880 | 3350 |
| Four-Core Cables | ||||||
| 4G25 | Orange | 0.78 | 92 | 29.2 | 960 | 1609 |
| 4G35 | Orange | 0.554 | 114 | 32.4 | 1344 | 1893 |
| 4G50 | Orange | 0.386 | 143 | 37.6 | 1920 | 2642 |
| 4G70 | Orange | 0.272 | 178 | 42.4 | 2688 | 3597 |
| 4G95 | Orange | 0.206 | 210 | 49.2 | 3648 | 5121 |
| 4G120 | Orange | 0.161 | 246 | 56.0 | 4608 | 6550 |
| Five-Core Cables | ||||||
| 5G25 | Orange | 0.78 | 94 | 35.0 | 1200 | 1744 |
| 5G35 | Orange | 0.554 | 117 | 39.0 | 1680 | 2340 |
| 5G50 | Orange | 0.386 | 148 | 46.5 | 2400 | 3290 |
| 5G70 | Orange | 0.272 | 185 | 53.0 | 3360 | 4522 |
| 5G95 | Orange | 0.206 | 222 | 60.0 | 4560 | 5800 |
| Multicore Cables | ||||||
| 7G1.5 | Orange | 13.3 | 15.5 | 13.2 | 101 | 267 |
| 7G2.5 | Orange | 7.98 | 21 | 15.2 | 168 | 352 |
| 12G2.5 | Orange | 7.98 | 21 | 20.8 | 288 | 520 |
X07BQ-F – Without Filler
| Nominal Size mm² |
Sheath Colour | Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|---|
| Four-Core Cables | ||||||
| 4G25 | Orange | 0.78 | 92 | 26.8 | 960 | 1348 |
| 4G35 | Orange | 0.554 | 114 | 30.2 | 1344 | 1810 |
| 4G50 | Orange | 0.386 | 143 | 35.2 | 1920 | 2516 |
| 4G70 | Orange | 0.272 | 178 | 40.0 | 2688 | 3413 |
| 4G95 | Orange | 0.206 | 210 | 46.8 | 3648 | 4535 |
| Multicore Cables | ||||||
| 12G1.5 | Orange | 13.3 | 15.5 | 16.0 | 172.8 | 340 |
| 12G2.5 | Orange | 7.98 | 21 | 20.8 | 288 | 520 |
G = with green-yellow protective conductor. × = without green-yellow protective conductor.
Core identification is according to VDE 0293 / HD 308 as specified for each construction. For X07BQ-F without filler and more than five cores, the reference documentation specifies numbered cores with a green-yellow protective conductor.
Outer diameters and cable weights are approximate. Copper weights are stated according to the GER copper weight convention and do not represent measured recoverable copper content.
Current ratings refer to ampacity in air at 30°C. Actual permissible current depends on installation conditions, ambient temperature, cable grouping and the number of loaded conductors.
Technical parameters, available constructions, delivery lengths, certification and availability are subject to final order confirmation.