MEDIUM VOLTAGE POWER CABLES · COPPER CONDUCTOR

N2XSY Medium Voltage Power Cable

N2XSY is a single-core medium voltage power cable with a stranded copper conductor, XLPE insulation, copper wire screen and red PVC outer sheath.

Designed for electrical distribution networks, power stations and industrial installations. Suitable for installation in the ground, in water, indoors, outdoors and in cable ducts. Outdoor installations require protection against direct sunlight.

6/10–18/30 kV Radni napon
Copper Conductor
XLPE Insulation
90°C Max. Conductor Temp.
VDE 0276-620 Standard
01

Cable Construction

Single-core screened medium voltage cable

1
Conductor

Bare copper, Class 2 stranded conductor.

2
Inner Semiconducting Layer

Extruded conductor screen for electrical field control.

3
Insulation

XLPE DIX8 insulation.

4
Outer Semiconducting Layer

Extruded insulation screen. Triple-extrusion construction.

5
Metallic Screen

Copper wires with copper counter helix.

6
Outer Sheath

Red PVC DMV6 protective sheath.

02

Voltage Ratings

Available medium voltage configurations

6/10 kV
Nominal U₀/U 6/10 kV
Maximum Um 12 kV
Test Voltage 24 kV
12/20 kV
Nominal U₀/U 12/20 kV
Maximum Um 24 kV
Test Voltage 42 kV
18/30 kV
Nominal U₀/U 18/30 kV
Maximum Um 36 kV
Test Voltage 63 kV
03

Technical Characteristics

Electrical, thermal and installation properties

Materijal vodiča Copper
Conductor Construction Class 2 Stranded
Insulation XLPE DIX8
Metallic Screen Copper Wires + Counter Helix
Outer Sheath PVC DMV6, Red
Max. Conductor Temperature +90°C
Permitted Outer Cable Temp. – Fixed +70°C
Permitted Outer Cable Temp. – Moved −5°C to +70°C
Minimum Bending Radius 15 × Outer Diameter
Partial Discharge 2 pC
Flame Retardance IEC 60332-1-2
04

Standardi

Design and flame-retardance requirements

VDE 0276-620 Medium voltage cable construction
IEC 60332-1-2 Single cable flame propagation test
VDE 0482-332-1-2 Flame-retardance test
05

Primjene

Medium voltage energy distribution

Power Distribution Medium voltage distribution networks
Power Stations Electrical power infrastructure
Industrial Installations Industrial energy supply systems
Underground Installation Direct burial in the ground
Cable Ducts Protected cable routes and conduits
Indoor & Outdoor Use Outdoor use with sunlight protection
N2XSY · INSTALLATION INFORMATION

Suitable for installation in the ground, in water, indoors, outdoors and in cable ducts. The cable must be protected from sunlight in accordance with the installation guidance in the source technical documentation. Dimensions, weights, current ratings and delivery availability depend on the selected cable configuration.

N2XSY · MEDIUM VOLTAGE TECHNICAL DIMENSIONS

N2XSY – Cable Sizes & Technical Data

Complete technical specifications for N2XSY single-core copper medium voltage cables. All available constructions are listed below by voltage rating.

6/10 kV15 Constructions
12/20 kV18 Constructions
18/30 kV12 Constructions
45Total Constructions
45 constructions

N2XSY 6/10 kV

U₀/U (Um): 6/10 (12) kV · Test Voltage: 24 kV

15 sizes
Size
mm²
Conductor Ø
mm
Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Short Circuit
kA / 1s
Sheath
mm
Bending Radius
mm
Outer Ø
mm
Pulling Force
N
Copper
kg/km
Weight
kg/km
1x35/167.50.5243.419718752.1360241750518920
1x50/168.60.3873.42362207.152.13752525006621100
1x70/1610.20.2683.4294268102.14052735008541300
1x95/16120.1933.435832013.62.142028475010941600
1x120/1613.50.1533.441336317.22.145030600013341850
1x150/16150.1243.446840521.42.146531750016222050
1x150/25150.1243.446840521.42.146531750017232200
1x185/1616.80.09913.453545626.52.149533925019582450
1x185/2516.80.09913.453545626.52.149533925020592550
1x240/1619.20.07543.463152634.32.1525351200024863000
1x240/2519.20.07543.463152634.32.1525351200025873150
1x300/2521.60.06013.472259142.92.1555371500031633750
1x400/3524.60.0473.482766257.22.1615412000042344650
1x500/3527.60.03663.494974471.52.1660442500051945700
1x630/3532.50.02833.4109082090.12.1735493150064427090

N2XSY 12/20 kV

U₀/U (Um): 12/20 (24) kV · Test Voltage: 42 kV

18 sizes
Size
mm²
Conductor Ø
mm
Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Short Circuit
kA / 1s
Sheath
mm
Bending Radius
mm
Outer Ø
mm
Pulling Force
N
Copper
kg/km
Weight
kg/km
1x35/167.50.5245.520018952.14202817505181100
1x50/168.60.3875.52392227.152.14352925006621250
1x70/1610.20.2685.5297271102.14653135008541500
1x95/16120.1935.536132313.62.148032475010941800
1x120/1613.50.1535.541636717.22.151034600013342050
1x150/16150.1245.547040921.42.152535750016222300
1x150/25150.1245.547040921.42.152535750017232400
1x185/1616.80.09915.553846126.52.155537925019582650
1x185/2516.80.09915.553846126.52.155537925020592800
1x240/1619.20.07545.563453234.32.1600401200024863250
1x240/2519.20.07545.563453234.32.1600401200025873400
1x240/5019.20.07545.563453234.32.1600401200028643499
1x300/2521.60.06015.572459942.92.1630421500031634000
1x400/3524.60.0475.582967157.22.1675452000042344950
1x500/3527.60.03665.595375471.52.1735492500051946050
1x630/3532.50.02835.5107582090.12.1795533150064427090
1x800/5037.60.02215.51205890114.42.4900604000082409249
1x800/3537.60.02215.51205890114.42.4900604000080949032

N2XSY 18/30 kV

U₀/U (Um): 18/30 (36) kV · Test Voltage: 63 kV

12 sizes
Size
mm²
Conductor Ø
mm
Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Short Circuit
kA / 1s
Sheath
mm
Bending Radius
mm
Outer Ø
mm
Pulling Force
N
Copper
kg/km
Weight
kg/km
1x35/167.50.524820219152.14953317505181350
1x50/168.60.38782412257.152.15103425006621550
1x70/1610.20.2688299274102.15403635008541750
1x95/16120.193836332713.62.155537475010942050
1x120/1613.50.153841837117.22.158539600013342350
1x150/25150.124847241421.42.160040750017232700
1x185/2516.80.0991853946626.52.163042925020593100
1x240/2519.20.0754863553934.32.1660441200025873700
1x300/2521.60.0601872560642.92.1705471500031634350
1x400/3524.60.047883168057.22.1750502000042345350
1x500/3527.60.0366895376571.52.1795532500051946450
1x800/3537.60.02218——114.42.4930624000080749500
Technical Information

Current ratings refer to installation in air at 30°C and in ground at 20°C. Short-circuit values are based on a duration of 1 second. Cable diameters and weights are approximate. Copper values include the metallic screen. Bending radius values refer to fixed installation. The source does not specify current ratings for the 18/30 kV 1x800/35 construction.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

UNIMA CABLE

N2XSY Cable Calculator

Calculate cable weight, copper content and approximate cable length.

m
Cable Weight 0 kg
Cable Length 0 m
Copper Content 0 kg
Copper Share 0 %
Cable weight: 0 kg/km
Copper: 0 kg/km
Approximate values based on technical cable data. Actual values may vary due to manufacturing tolerances.