NA2XS(FL)2Y

Single-core medium-voltage power cable with a stranded aluminium conductor, XLPE insulation, metallic screen and black polyethylene outer sheath. The longitudinally and transversely water-blocked construction provides additional protection against moisture penetration in underground power distribution networks and industrial installations.

NA2XS(FL)2Y 6/10 (12) kV 12/20 (24) kV 18/30 (36) kV Class 2 Aluminium XLPE Insulation Water-Blocked PE Outer Sheath
6–30 kV Nominal Voltage Classes
90°C Maximum Conductor Temperature
Class 2 Aluminium Conductor
15 × D Minimum Bending Radius
2 pC Partial Discharge Reference
FL Longitudinal & Transverse Water Blocking

Construction

  • Conductor: Stranded aluminium, Class 2
  • Conductor screen: Semiconductive layer
  • Insulation: Cross-linked polyethylene (XLPE), DIX8
  • Insulation screen: Semiconductive layer
  • Metallic screen: Copper wire screen
  • Water blocking: Longitudinal and transverse moisture protection
  • Outer sheath: Polyethylene (PE), DMP2
  • Sheath colour: Crna

Primjene

  • Medium-voltage power distribution networks
  • Underground cable installations
  • Industrial power supply systems
  • Power stations and substations
  • Outdoor power distribution installations
  • Cable ducts and underground routes
  • Installations requiring water-blocked cable construction

Technical Characteristics

Cable Designation NA2XS(FL)2Y
Reference Standard VDE 0276-620
Radni napon 6/10, 12/20, 18/30 kV
Highest System Voltage 12 / 24 / 36 kV
Materijal vodiča Aluminium
Conductor Class Class 2
Izolacijski materijal XLPE (DIX8)
Outer Sheath PE (DMP2)
Maximum Conductor Temperature +90°C
Fixed Installation Bending Radius 15 × D
Water Blocking Longitudinal & Transverse
UV Resistance Yes
Flame Retardance Not flame-retardant
Outer Sheath Colour Crna

Voltage Classes

Radni napon
U₀/U
Highest Voltage
Um
AC Test Voltage
6/10 kV 12 kV 21 kV
12/20 kV 24 kV 42 kV
18/30 kV 36 kV 63 kV
Technical Note: Cable dimensions, conductor resistance, metallic screen cross-section, current-carrying capacity and weight depend on the selected voltage class and conductor size. Refer to the corresponding technical size tables. CPR classification is subject to the applicable manufacturer's Declaration of Performance (DoP).
UNIMA CABLE | MEDIUM VOLTAGE POWER CABLES

NA2XS(FL)2Y – Cable Dimensions

Technical dimensions, electrical characteristics, current ratings and material weights for longitudinally and transversely water-blocked medium-voltage aluminium power cables.

Technical Size Table

VoltagekV Poprečni presjekmm² ResistanceΩ/km AirA GroundA Short CircuitkA / 1 s Diametermm Cable Weightkg/km Aluminiumkg/km Copperkg/km

Cable Weight Calculator

— Total Cable Weight (kg)
— Aluminium Weight (kg)
— Copper Weight (kg)
Technical Note: Values are based on the referenced NA2XS(FL)2Y technical data. Current ratings refer to air temperature 30°C and ground temperature 20°C. Cable diameters and weights are approximate. Material weights are shown separately for aluminium and copper. Calculated weights exclude drums and packaging.