NHXMH-J / NHXMH-O is a 300/500 V halogen-free installation cable with copper conductors and cross-linked polyethylene (XLPE) insulation, designed for fixed electrical installations in residential, commercial and public buildings.
The cable is suitable for fixed installation on or under plaster, in dry and wet rooms, and in concrete, excluding shaken, jolted or tamped concrete. Its halogen-free construction helps reduce corrosive gas emissions in the event of fire.
300/500 V
Radni napon
Copper
Conductor
XLPE
Insulation
70°C
Max. Conductor Temp.
Dca*
CPR razred
NHXMH Cable Construction
Conductor
Bare Copper
Solid or stranded, depending on cross-section
Conductor Construction
RE / RM
Class 1 or Class 2 according to EN 60228
Insulation
XLPE – 2XI1
Cross-linked polyethylene
Outer Sheath
Halogen-Free HM2
Flame-retardant, low-smoke compound
Protective Conductor
J / O Versions
J with green/yellow PE; O without PE
CPR
Dca*
Verify classification for each variant and DoP
Technical Data
| Rated Voltage U₀/U | 300/500 V |
|---|---|
| Test Voltage | 2 kV AC |
| Conductor | Copper – Class 1 or Class 2 |
| Conductor Standard | EN 60228 |
| Insulation | XLPE, type 2XI1 |
| Outer Sheath | Halogen-free compound, type HM2 |
| Maximum Conductor Temperature | +70°C |
| Fixed Installation Temperature | -40°C to +70°C |
| Minimum Installation Temperature | +5°C |
| CPR Classification | Dca* – depending on variant and DoP |
| Product Standard | VDE 0250-214 |
| Fire Performance | IEC 60332-3-24 / IEC 61034 / IEC 60754 |
Applications
Residential Buildings
Fixed electrical installations in apartments,
houses and residential complexes.
Commercial Buildings
Electrical distribution in offices,
shopping centres and business facilities.
Public Buildings
Suitable for schools, hospitals and public
facilities where halogen-free cables are required.
On and Under Plaster
Suitable for fixed installation on or
beneath plaster in building structures.
Dry and Wet Rooms
For indoor installation in dry and wet
environments under suitable conditions.
Concrete Installation
Installation in concrete is permitted,
excluding shaken, jolted or tamped concrete.
Core Identification
According to VDE 0293 / HD 308
3 Core with PE
Green/Yellow · Brown · Blue
3 Core without PE
Brown · Black · Grey
4 Core with PE
Green/Yellow · Brown · Black · Grey
4 Core without PE
Blue · Brown · Black · Grey
5 Core with PE
Green/Yellow · Blue · Brown · Black · Grey
Protective Conductor
NHXMH-J: with PE · NHXMH-O: without PE
⚡
NHXMH-J / NHXMH-O Cable Range
Available in selected single-core and multicore
configurations. Cable dimensions, weights and
electrical properties depend on the selected
cross-section and conductor construction.
* CPR classification depends on the exact cable variant
and Declaration of Performance (DoP).
Dimensions and weights are nominal manufacturer values.
Consult the detailed technical tables for each cross-section.
UNIMA CABLE | Technical Product Range
NHXMH-J / NHXMH-O – Dimensions & Technical Data
Select a cable configuration to view nominal dimensions, conductor construction, approximate cable weight and copper content.
NHXMH-J – 3 Core with Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 3G1.5 | RE | 8.6 | 130 | 43 |
| 3G2.5 | RE | 9.5 | 165 | 72 |
| 3G4 | RE | 10.7 | 235 | 115 |
| 3G6 | RE | 12.3 | 320 | 173 |
| 3G10 | RE | 14.8 | 480 | 288 |
NHXMH-J – 4 Core with Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 4G1.5 | RE | 9.2 | 150 | 58 |
| 4G2.5 | RE | 10.2 | 200 | 96 |
| 4G4 | RE | 12.2 | 300 | 154 |
| 4G6 | RE | 13.2 | 395 | 230 |
| 4G10 | RE | 15.8 | 595 | 384 |
| 4G16 | RM | 20.0 | 935 | 614 |
| 4G25 | RM | 24.5 | 1420 | 960 |
| 4G35 | RM | 27.5 | 1910 | 1344 |
NHXMH-J – 5 Core with Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 5G1.5 | RE | 9.8 | 175 | 72 |
| 5G2.5 | RE | 10.7 | 235 | 120 |
| 5G4 | RE | 13.2 | 350 | 192 |
| 5G6 | RE | 14.8 | 480 | 288 |
| 5G10 | RE | 17.4 | 710 | 480 |
| 5G16 | RM | 22.0 | 1140 | 768 |
| 5G25 | RM | 28.0 | 1900 | 1200 |
NHXMH-O – Single Core without Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 1×1.5 | RE | 5.2 | 92 | 15 |
| 1×2.5 | RE | 5.6 | 110 | 24 |
| 1×4 | RE | 7.1 | 135 | 39 |
| 1×6 | RE | 7.4 | 160 | 58 |
| 1×10 | RE | 7.8 | 215 | 96 |
| 1×16 | RM | 8.8 | 295 | 154 |
NHXMH-O – 2 Core without Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 2×1.5 | RE | 8.2 | 110 | 29 |
| 2×2.5 | RE | 9.0 | 130 | 48 |
| 2×4 | RE | 9.8 | 173 | 77 |
| 2×6 | RE | 10.8 | 226 | 115 |
| 2×10 | RE | 13.3 | 356 | 192 |
NHXMH-O – 4 Core without Protective Conductor
| Cross-section | Conductor | Outer Ø (mm) | Weight (kg/km) | Copper (kg/km) |
|---|---|---|---|---|
| 4×10 | RE | 15.7 | 615 | 384 |
| 4×16 | RM | 19.5 | 935 | 614 |
| 4×25 | RM | 23.8 | 1420 | 960 |
Dimensions and weights are nominal values and may vary
depending on the manufacturer and cable construction.
The listed configurations are based on the reference range
and must be verified against the applicable manufacturer datasheet.
Electrical current-carrying capacities are not shown because
they depend on installation conditions.
UNIMA CABLE | NHXMH-J / NHXMH-O | 300/500 V
Technical information for product selection