UNIMA CABLE | MEDIUM VOLTAGE POWER CABLES

N2XS2Y – Copper Medium Voltage Power Cable

Single-core medium voltage power cable with stranded copper conductor, XLPE insulation, copper wire screen and black polyethylene outer sheath. Designed for underground power distribution, industrial installations and medium voltage electrical infrastructure.

6/10 kV 12/20 kV 18/30 kV 35–500 mm² Class 2 Copper XLPE Insulation Copper Wire Screen PE Outer Sheath Direct Burial DIN VDE 0276-620 HD 620

Product Overview

N2XS2Y is a single-core copper medium voltage power cable designed for electrical energy transmission and distribution in underground, outdoor and indoor installations.

The cable incorporates a round stranded bare copper conductor (RM), manufactured according to DIN EN 60228 Class 2.

The conductor is surrounded by an inner semiconducting layer, cross-linked polyethylene (XLPE) insulation and an outer semiconducting layer.

A metallic screen consisting of copper wires surrounds the insulated cable core. The screen forms part of the electrical protection and earthing arrangement of the medium voltage cable system.

The black polyethylene outer sheath provides external protection for the cable during installation and service.

N2XS2Y is suitable for direct burial, outdoor installations, indoor installations and installation in cable channels.

The reference product range includes rated voltages of 6/10 kV, 12/20 kV and 18/30 kV, with copper conductor cross-sections ranging from 35 to 500 mm² depending on the selected voltage rating.

Key Technical Features

6–30 kVRated Voltage Range U
35–500 mm²Conductor Range
Class 2Stranded Copper
+90°CMaximum Specified Temperature

Voltage Classes

N2XS2Y 6/10 kV

35–500 mm²

11 reference configurations.

Test voltage: 21 kV for 5 minutes.

N2XS2Y 12/20 kV

35–500 mm²

11 reference configurations.

Test voltage: 42 kV for 5 minutes.

N2XS2Y 18/30 kV

50–500 mm²

10 reference configurations.

Test voltage: 63 kV for 5 minutes.

Construction & Technical Properties

Cable Construction

Materijal vodičaBare Copper
Conductor ConstructionRound Stranded (RM)
Conductor ClassClass 2
Conductor StandardDIN EN 60228
Number of Cores1
Conductor Cross-Section35–500 mm²
Conductor ScreenInner Semiconducting Layer
Core InsulationCross-Linked Polyethylene (XLPE)
Insulation ScreenOuter Semiconducting Layer
Metallic ScreenCopper Wires
Screen Cross-Section16 / 25 / 35 mm²
ArmourNone
Outer SheathPolyethylene (PE)
Sheath ColourCrna
Water-Blocking LayersNot Specified

Electrical & Mechanical Data

Rated Voltage U0/U6/10, 12/20, 18/30 kV
Test Voltage 6/10 kV21 kV / 5 min
Test Voltage 12/20 kV42 kV / 5 min
Test Voltage 18/30 kV63 kV / 5 min
Temperature During Bending-20°C to +90°C
Fixed Installation Temperature-20°C to +90°C
Short-Circuit Temperature+250°C
Maximum Short-Circuit Duration5 Seconds
Minimum Bending Radius15 x Cable Diameter
Approx. Outer Diameter23–52 mm
Reference Maximum Diameter28–57 mm
Approx. Cable Weight820–6200 kg/km
Current Rating in Ground187–765 A
Current Rating in Air197–953 A
Reference Cable FormationTrefoil

XLPE Insulation & Copper Wire Screen

XLPE Insulation System

Cross-linked polyethylene insulation provides the dielectric insulation required for medium voltage power distribution.

The inner and outer semiconducting layers support controlled electrical field distribution around the conductor and insulation.

The reference documentation specifies a short-circuit temperature of +250°C for a maximum duration of 5 seconds.

Metallic Copper Wire Screen

The metallic copper wire screen is available in reference cross-sections of 16, 25 and 35 mm².

The screen cross-section depends on the selected conductor size and must be suitable for the earthing arrangement and anticipated earth-fault current.

Screen bonding and earthing must be designed according to the requirements of the complete medium voltage installation.

PE Outer Sheath & Underground Installation

The black polyethylene outer sheath provides external protection for underground and outdoor installations.

N2XS2Y is suitable for direct burial in the ground, installation in cable channels and installation in indoor and outdoor environments.

The reference construction does not specify additional longitudinal or transverse water-blocking layers.

Where longitudinal or radial watertightness is required, a separately specified water-blocked cable construction must be selected.

Typical Applications

Medium Voltage Distribution Networks
Utility Power Infrastructure
Underground Power Distribution
Industrial Power Distribution
Transformer and Substation Connections
Medium Voltage Switchgear Connections
Solar Farm Medium Voltage Networks
Wind Farm Power Collection Networks
Battery Energy Storage Systems – MV Connections
Data Center Medium Voltage Infrastructure
Commercial Building Power Infrastructure
Indoor and Outdoor Cable Channels

Installation Conditions

N2XS2Y cables are intended for fixed medium voltage installations.

The reference documentation permits direct burial, outdoor installation, indoor installation and installation in cable channels.

The specified temperature range during bending and for fixed installation is -20°C to +90°C.

The minimum bending radius is 15 times the cable outer diameter.

The published current-carrying capacities are based on trefoil cable formation. Actual current ratings depend on installation conditions, ambient temperature, soil thermal resistivity, burial depth, cable spacing and screen bonding.

Installation design must be verified for the actual project conditions.

Applicable Standards

DIN VDE 0276-620 – Reference standard for medium voltage power cables with extruded insulation.

HD 620 S1:1996 – Reference harmonisation document for medium voltage distribution cables, as stated in the original technical documentation.

DIN EN 60228, Class 2 – Stranded copper conductor construction.

Related Medium Voltage Cable Constructions

Copper Conductor Versions

N2XS2Y – Copper conductor, XLPE insulation, copper wire screen and PE sheath.

N2XS(F)2Y – Related copper conductor construction with longitudinal water blocking.

N2XS(FL)2Y – Related copper conductor construction with longitudinal and transverse water blocking.

Aluminium Conductor Versions

NA2XS2Y – Related aluminium conductor construction with XLPE insulation and PE sheath.

NA2XS(F)2Y – Related aluminium conductor construction with longitudinal water blocking.

NA2XS(FL)2Y – Related aluminium conductor construction with longitudinal and transverse water blocking.

Technical Note: Related cable designations are provided for product orientation and are not declarations of technical equivalence or interchangeability. The reference documentation specifies HD 620 S1:1996. Compliance with current standard editions must be confirmed for the supplied cable. CPR classification, flame retardancy, water-blocking performance and detailed current-rating calculation conditions are not specified. Final technical characteristics and conformity documentation must be confirmed for each project.
UNIMA CABLE | TECHNICAL DIMENSIONS

N2XS2Y – Cable Sizes & Technical Data

Complete reference range of single-core copper medium voltage power cables rated 6/10 kV, 12/20 kV and 18/30 kV, including conductor and screen cross-sections, copper content, cable dimensions, approximate weights and current-carrying capacities.

32Reference Configurations
35–500 mm²Conductor Cross-Section
16–35 mm²Copper Wire Screen
3Voltage Classes

N2XS2Y 6/10 kV – Cable Sizes & Current Ratings

Cable Size (mm²) Copper Content (kg/km) Approx. Outer Diameter (mm) Max. Outer Diameter (mm) Approx. Weight (kg/km) Current in Ground (A)* Current in Air (A)*
1x35 RM/16518.42328820187197
1x50 RM/16662.42429960220236
1x70 RM/16854.426311150269292
1x95 RM/161094.427321450320358
1x120 RM/161334.429341700363413
1x150 RM/251723.230352000405468
1x185 RM/252059.232372350456535
1x240 RM/252587.234392900526631
1x300 RM/253163.236413550591722
1x400 RM/354233.640454500662827
1x500 RM/355193.643485550744949

N2XS2Y 12/20 kV – Cable Sizes & Current Ratings

Cable Size (mm²) Copper Content (kg/km) Approx. Outer Diameter (mm) Max. Outer Diameter (mm) Approx. Weight (kg/km) Current in Ground (A)* Current in Air (A)*
1x35 RM/16518.427321000189200
1x50 RM/16662.428331150222239
1x70 RM/16854.430351350271297
1x95 RM/161094.431361600323361
1x120 RM/161334.433381850367416
1x150 RM/251723.234392250409470
1x185 RM/252059.236412600461538
1x240 RM/252587.239443150532634
1x300 RM/253163.241463800599724
1x400 RM/354233.644494750671829
1x500 RM/355193.647525800754953

N2XS2Y 18/30 kV – Cable Sizes & Current Ratings

Cable Size (mm²) Copper Content (kg/km) Approx. Outer Diameter (mm) Max. Outer Diameter (mm) Approx. Weight (kg/km) Current in Ground (A)* Current in Air (A)*
1x50 RM/16662.433381350225241
1x70 RM/16854.435401600274299
1x95 RM/161094.436411900327363
1x120 RM/161334.438432200371418
1x150 RM/251723.239442550414472
1x185 RM/252059.241462950466539
1x240 RM/252587.243483500539635
1x300 RM/253163.246514150606725
1x400 RM/354233.649545150680831
1x500 RM/355193.652576200765953

* Current-carrying capacities: Reference values for cables installed in trefoil formation. The original documentation does not specify detailed calculation conditions such as ambient temperature, soil thermal resistivity, burial depth or screen bonding arrangement. Actual permissible current must be determined for the project-specific installation.

Copper content values are reproduced from the reference documentation and must not be interpreted as independently verified recoverable copper mass. Cable dimensions and weights are approximate.

Voltage Class Comparison

Parameter 6/10 kV 12/20 kV 18/30 kV
Rated Voltage U0/U6/10 kV12/20 kV18/30 kV
Conductor Range35–500 mm²35–500 mm²50–500 mm²
Screen Cross-Section16–35 mm²16–35 mm²16–35 mm²
Reference Configurations111110
Test Voltage21 kV42 kV63 kV
Test Duration5 min5 min5 min
Approx. Outer Diameter23–43 mm27–47 mm33–52 mm
Max. Outer Diameter28–48 mm32–52 mm38–57 mm
Approx. Cable Weight820–5550 kg/km1000–5800 kg/km1350–6200 kg/km
Current in Ground*187–744 A189–754 A225–765 A
Current in Air*197–949 A200–953 A241–953 A

Conductor & Copper Screen Configuration

Conductor Cross-Section (mm²) Copper Screen (mm²) Conductor Construction Copper Content (kg/km)
3516RM, Class 2518.4
5016RM, Class 2662.4
7016RM, Class 2854.4
9516RM, Class 21094.4
12016RM, Class 21334.4
15025RM, Class 21723.2
18525RM, Class 22059.2
24025RM, Class 22587.2
30025RM, Class 23163.2
40035RM, Class 24233.6
50035RM, Class 25193.6

Example: 1x240 RM/25 identifies a single-core cable with a 240 mm² round stranded copper conductor and a 25 mm² metallic copper screen.

Electrical Characteristics

ParameterReference Value
Rated Voltage U0/U6/10, 12/20 and 18/30 kV
Test Voltage 6/10 kV21 kV / 5 minutes
Test Voltage 12/20 kV42 kV / 5 minutes
Test Voltage 18/30 kV63 kV / 5 minutes
Materijal vodičaBare Copper
Conductor ConstructionRound Stranded (RM)
Conductor ClassClass 2
Conductor StandardDIN EN 60228
Izolacijski materijalXLPE
Metallic ScreenCopper Wires
Conductor DC ResistanceNot Specified
InductanceNot Specified
CapacitanceNot Specified
Screen Short-Circuit RatingNot Specified
Reference Current-Rating FormationTrefoil

Temperature Characteristics

Installation / Operating Condition Minimum Temperature Maximum Temperature
During Bending-20°C+90°C
Fixed Installation-20°C+90°C
Short-Circuit ConditionNot Specified+250°C

Maximum short-circuit duration: 5 seconds.

Minimum Cable Bending Radius

Cable Size (mm²) 6/10 kV (mm) 12/20 kV (mm) 18/30 kV (mm)
1x35/16345405—
1x50/16360420495
1x70/16390450525
1x95/16405465540
1x120/16435495570
1x150/25450510585
1x185/25480540615
1x240/25510585645
1x300/25540615690
1x400/35600660735
1x500/35645705780

The listed bending radii are indicative calculated values based on the approximate outer diameter multiplied by the specified bending factor of 15. For installation planning, the actual supplied cable diameter must be used. Where only the maximum reference diameter is available, a conservative planning radius may be calculated from that value.

Conservative Bending Radius Based on Maximum Diameter

Cable Size (mm²) 6/10 kV (mm) 12/20 kV (mm) 18/30 kV (mm)
1x35/16420480—
1x50/16435495570
1x70/16465525600
1x95/16480540615
1x120/16510570645
1x150/25525585660
1x185/25555615690
1x240/25585660720
1x300/25615690765
1x400/35675735810
1x500/35720780855

Calculated planning values based on 15 times the maximum reference outer diameter. These values are not separately declared manufacturer installation parameters.

Cable Construction Layers

Layer Component Material / Construction
1ConductorRound Stranded Bare Copper, RM, Class 2
2Conductor ScreenInner Semiconducting Layer
3Core InsulationCross-Linked Polyethylene (XLPE)
4Insulation ScreenOuter Semiconducting Layer
5Metallic ScreenCopper Wires
6Outer SheathBlack Polyethylene (PE)

Installation & Environmental Characteristics

Parameter Reference Value
Direct BurialSuitable
Outdoor InstallationSuitable
Indoor InstallationSuitable
Cable ChannelsSuitable
Fixed InstallationSuitable
Outer Sheath MaterialPolyethylene (PE)
Outer Sheath ColourCrna
Minimum Bending Radius15 x Cable Diameter
Longitudinal Water BlockingNot Specified
Transverse Water BlockingNot Specified
Permanent Water ImmersionNot Specified
UV Resistance TestNot Specified
Maximum Pulling ForceNot Specified
Flame RetardancyNot Specified
CPR ClassificationNot Specified

Applicable Standards

Standard Reference Application
DIN VDE 0276-620Medium Voltage Power Cable Construction
HD 620 S1:1996Reference Harmonisation Document for Medium Voltage Distribution Cables
DIN EN 60228Stranded Copper Conductors, Class 2
Technical Note: All cable dimensions, copper content, cable weights and current-carrying capacities are indicative reference values. Published configurations do not constitute a declaration of stock availability. Final dimensions, screen cross-section, electrical characteristics and conformity documentation must be confirmed for the supplied product.
Current-Carrying Capacity: Reference current ratings are reproduced for trefoil cable formation. Detailed environmental and installation assumptions are not provided in the reference documentation. The published values must not be used as final design ratings without project-specific engineering verification.
Data Verification: All 32 reference cable configurations are included. Bending radii are calculated from the specified bending factor and the published approximate or maximum outer diameters. HD 620 S1:1996 is retained as stated in the original documentation and does not establish conformity with the latest edition of HD 620. CPR classification, water-blocking performance and additional electrical parameters must be confirmed separately.