HSLH FRNC – Halogen-Free Control Cable 300/500 V
Flexible halogen-free multicore control and signal cable with Class 5 copper conductors, cross-linked polyolefin copolymer insulation and a grey halogen-free outer sheath. Designed for indoor fixed and movable installations requiring improved fire performance.
Product Overview
HSLH FRNC is a flexible halogen-free control and signal cable with improved behaviour under fire conditions.
The cable incorporates fine-stranded bare copper conductors according to DIN EN 60228 Class 5, providing flexibility for installation and equipment connections.
Both the individual core insulation and the grey outer sheath are manufactured from halogen-free, cross-linked polyolefin copolymer compounds.
The FRNC designation refers to flame-retardant and non-corrosive cable characteristics. The construction is intended to limit flame propagation, smoke generation and corrosive combustion gases.
HSLH FRNC is intended for installation in dry, damp and wet indoor environments. It is suitable for fixed and movable installations without excessive tensile stress or forced bending.
The reference product range includes conductor cross-sections from 0.75 to 25 mm² and configurations from 2 to 34 cores, depending on the selected cross-section.
Key Technical Features
Cable Variants
HSLH-JZ FRNC
With Protective Earth Conductor
One green/yellow protective earth conductor and remaining black cores with numerical identification.
Suitable for control circuits and equipment connections requiring a protective earth conductor.
HSLH-OZ FRNC
Without Protective Earth Conductor
All cores are black with numerical identification, without a green/yellow protective earth conductor.
Suitable for control and signal circuits where a protective earth conductor is not required within the cable.
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Fire Performance & Halogen-Free Properties
Flame Retardancy
HSLH FRNC is designed to provide improved flame propagation performance compared with conventional cable constructions without equivalent fire performance characteristics.
The reference documentation specifies EN 50266-2-4, EN 60332-1 and IEC 60332-3 Category C.
Low Smoke & Halogen-Free Construction
The halogen-free cross-linked polyolefin insulation and outer sheath are intended to reduce smoke and corrosive gas generation under fire conditions.
The reference construction is adapted to DIN EN 50267-2-2 and DIN EN 50268-2.
Typical Applications
Installation Conditions
HSLH FRNC is suitable for installation in dry, damp and wet indoor environments.
The cable can be used in fixed and movable installations, provided that it is not subjected to excessive tensile stress or forced bending.
The specified temperature range during bending is -5°C to +70°C.
For fixed installations, the specified temperature range is -30°C to +70°C.
The minimum bending radius during bending is 15 times the cable outer diameter.
Outdoor installation is not permitted. Suitability for direct burial, permanent immersion, drag chains and continuous-flex applications is not established by the reference documentation.
Applicable Standards
DIN EN 60228, Class 5 – Flexible copper conductor construction.
DIN EN 50266-2-4 – Reference standard for vertical flame propagation of vertically mounted bunched cables, Category C.
DIN EN 50267-2-2 – Reference standard for determining the acidity and conductivity of gases evolved during combustion.
DIN EN 50268-2 – Reference standard for smoke density measurement under defined combustion conditions.
EN 60332-1 – Vertical flame propagation test for a single insulated wire or cable.
IEC 60332-3 Category C – Vertical flame propagation performance of vertically mounted bunched cables.
FRNC and Fire-Resistant Cables
HSLH FRNC is a flame-retardant, halogen-free control cable. Improved fire behaviour does not automatically establish continued electrical circuit operation during a fire.
The reference documentation does not specify FE180, E30, E60, E90 or other circuit integrity classifications.
Where fire-resistant circuit integrity is required, a separately tested and certified cable system must be selected.
HSLH FRNC – Cable Sizes & Technical Data
Complete reference range of flexible halogen-free control and signal cables rated 300/500 V, including conductor construction, copper content, approximate cable dimensions, weights, electrical characteristics and installation parameters.
Available Cable Sizes & Construction Data
| Cable Size (mm²) | Number of Cores | Copper Content (kg/km) | Approx. Conductor Stranding | Approx. Outer Diameter (mm) | Approx. Cable Weight (kg/km) |
|---|---|---|---|---|---|
| HSLH FRNC – 0.75 mm² | |||||
| 2x0.75 | 2 | 14.4 | 24 x 0.21 | 5.4 | 47 |
| 3x0.75 | 3 | 21.6 | 24 x 0.21 | 5.7 | 56 |
| 4x0.75 | 4 | 28.8 | 24 x 0.21 | 6.2 | 69 |
| 5x0.75 | 5 | 36.0 | 24 x 0.21 | 6.8 | 83 |
| 7x0.75 | 7 | 50.4 | 24 x 0.21 | 7.4 | 104 |
| 12x0.75 | 12 | 86.4 | 24 x 0.21 | 9.9 | 172 |
| 18x0.75 | 18 | 129.6 | 24 x 0.21 | 12.4 | 263 |
| 25x0.75 | 25 | 180.0 | 24 x 0.21 | 14.4 | 352 |
| 34x0.75 | 34 | 244.8 | 24 x 0.21 | 15.9 | 512 |
| HSLH FRNC – 1 mm² | |||||
| 2x1 | 2 | 19.2 | 32 x 0.21 | 5.7 | 55 |
| 3x1 | 3 | 28.8 | 32 x 0.21 | 6.0 | 67 |
| 4x1 | 4 | 38.4 | 32 x 0.21 | 6.6 | 83 |
| 5x1 | 5 | 48.0 | 32 x 0.21 | 7.2 | 100 |
| 7x1 | 7 | 67.2 | 32 x 0.21 | 8.0 | 130 |
| 12x1 | 12 | 115.2 | 32 x 0.21 | 10.6 | 212 |
| 18x1 | 18 | 172.8 | 32 x 0.21 | 12.7 | 314 |
| 25x1 | 25 | 240.0 | 32 x 0.21 | 15.3 | 429 |
| HSLH FRNC – 1.5 mm² | |||||
| 2x1.5 | 2 | 28.8 | 30 x 0.26 | 6.3 | 72 |
| 3x1.5 | 3 | 43.2 | 30 x 0.26 | 6.7 | 88 |
| 4x1.5 | 4 | 57.6 | 30 x 0.26 | 7.3 | 110 |
| 5x1.5 | 5 | 72.0 | 30 x 0.26 | 8.1 | 135 |
| 7x1.5 | 7 | 100.8 | 30 x 0.26 | 8.9 | 174 |
| 12x1.5 | 12 | 172.8 | 30 x 0.26 | 12.0 | 289 |
| 18x1.5 | 18 | 259.2 | 30 x 0.26 | 14.4 | 433 |
| 25x1.5 | 25 | 360.0 | 30 x 0.26 | 17.4 | 596 |
| 34x1.5 | 34 | 489.6 | 30 x 0.26 | 19.6 | 786 |
| HSLH FRNC – 2.5 mm² | |||||
| 2x2.5 | 2 | 48.0 | 50 x 0.26 | 7.6 | 110 |
| 3x2.5 | 3 | 72.0 | 50 x 0.26 | 8.1 | 137 |
| 4x2.5 | 4 | 96.0 | 50 x 0.26 | 8.9 | 174 |
| 5x2.5 | 5 | 120.0 | 50 x 0.26 | 10.0 | 217 |
| 7x2.5 | 7 | 168.0 | 50 x 0.26 | 12.7 | 306 |
| 12x2.5 | 12 | 288.0 | 50 x 0.26 | 14.9 | 467 |
| HSLH FRNC – 4 mm² | |||||
| 4x4 | 4 | 153.6 | 56 x 0.31 | 10.8 | 267 |
| 5x4 | 5 | 192.0 | 56 x 0.31 | 12.1 | 331 |
| 7x4 | 7 | 268.8 | 56 x 0.31 | 13.4 | 432 |
| HSLH FRNC – 6 mm² | |||||
| 4x6 | 4 | 230.4 | 84 x 0.31 | 13.0 | 388 |
| 5x6 | 5 | 288.0 | 84 x 0.31 | 14.5 | 480 |
| HSLH FRNC – 10 mm² | |||||
| 4x10 | 4 | 384.0 | 80 x 0.41 | 16.2 | 616 |
| 5x10 | 5 | 480.0 | 80 x 0.41 | 18.1 | 766 |
| HSLH FRNC – 16 mm² | |||||
| 4x16 | 4 | 614.4 | 128 x 0.41 | 18.9 | 908 |
| 5x16 | 5 | 768.0 | 128 x 0.41 | 21.2 | 1134 |
| HSLH FRNC – 25 mm² | |||||
| 4x25 | 4 | 960.0 | 182 x 0.41 | 23.5 | 1620 |
Cable sizes are expressed as the number of cores multiplied by the nominal conductor cross-section in mm². The table uses generic cable size notation. The required JZ or OZ version must be specified when ordering.
Conductor stranding is expressed as the approximate number of individual wires multiplied by their nominal diameter in millimetres. Copper content values are indicative reference figures and must not be interpreted as independently verified recoverable copper mass.
Conductor Construction by Cross-Section
| Nominal Cross-Section (mm²) | Approx. Conductor Stranding | Conductor Class | Reference Configurations |
|---|---|---|---|
| 0.75 | 24 x 0.21 mm | Class 5 | 9 |
| 1 | 32 x 0.21 mm | Class 5 | 8 |
| 1.5 | 30 x 0.26 mm | Class 5 | 9 |
| 2.5 | 50 x 0.26 mm | Class 5 | 6 |
| 4 | 56 x 0.31 mm | Class 5 | 3 |
| 6 | 84 x 0.31 mm | Class 5 | 2 |
| 10 | 80 x 0.41 mm | Class 5 | 2 |
| 16 | 128 x 0.41 mm | Class 5 | 2 |
| 25 | 182 x 0.41 mm | Class 5 | 1 |
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Rated Voltage U0/U | 300/500 V |
| Test Voltage | 2000 V AC |
| Materijal vodiča | Bare Copper |
| Conductor Construction | Fine-Stranded, Flexible |
| Conductor Class | Class 5 |
| Conductor Standard | DIN EN 60228 |
| Core Insulation | Halogen-Free Cross-Linked Polyolefin Copolymer |
| Overall Screen | None |
| Current-Carrying Capacity | Not Specified |
| Conductor Resistance | Not Specified |
Temperature Characteristics
| Installation / Operating Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| During Bending | -5°C | +70°C |
| Fixed Installation | -30°C | +70°C |
| Short-Circuit Condition | Not Specified | +150°C |
Maximum short-circuit duration: 5 seconds.
Minimum Cable Bending Radius
| Cable Size (mm²) | Approx. Outer Diameter (mm) | Minimum Radius During Bending 15 x D (mm) |
|---|---|---|
| 0.75 mm² | ||
| 2x0.75 | 5.4 | 81 |
| 3x0.75 | 5.7 | 85.5 |
| 4x0.75 | 6.2 | 93 |
| 5x0.75 | 6.8 | 102 |
| 7x0.75 | 7.4 | 111 |
| 12x0.75 | 9.9 | 148.5 |
| 18x0.75 | 12.4 | 186 |
| 25x0.75 | 14.4 | 216 |
| 34x0.75 | 15.9 | 238.5 |
| 1 mm² | ||
| 2x1 | 5.7 | 85.5 |
| 3x1 | 6.0 | 90 |
| 4x1 | 6.6 | 99 |
| 5x1 | 7.2 | 108 |
| 7x1 | 8.0 | 120 |
| 12x1 | 10.6 | 159 |
| 18x1 | 12.7 | 190.5 |
| 25x1 | 15.3 | 229.5 |
| 1.5 mm² | ||
| 2x1.5 | 6.3 | 94.5 |
| 3x1.5 | 6.7 | 100.5 |
| 4x1.5 | 7.3 | 109.5 |
| 5x1.5 | 8.1 | 121.5 |
| 7x1.5 | 8.9 | 133.5 |
| 12x1.5 | 12.0 | 180 |
| 18x1.5 | 14.4 | 216 |
| 25x1.5 | 17.4 | 261 |
| 34x1.5 | 19.6 | 294 |
| 2.5 mm² | ||
| 2x2.5 | 7.6 | 114 |
| 3x2.5 | 8.1 | 121.5 |
| 4x2.5 | 8.9 | 133.5 |
| 5x2.5 | 10.0 | 150 |
| 7x2.5 | 12.7 | 190.5 |
| 12x2.5 | 14.9 | 223.5 |
| 4 mm² | ||
| 4x4 | 10.8 | 162 |
| 5x4 | 12.1 | 181.5 |
| 7x4 | 13.4 | 201 |
| 6 mm² | ||
| 4x6 | 13.0 | 195 |
| 5x6 | 14.5 | 217.5 |
| 10 mm² | ||
| 4x10 | 16.2 | 243 |
| 5x10 | 18.1 | 271.5 |
| 16 mm² | ||
| 4x16 | 18.9 | 283.5 |
| 5x16 | 21.2 | 318 |
| 25 mm² | ||
| 4x25 | 23.5 | 352.5 |
Minimum bending radii are calculated using the approximate cable outer diameters and the specified bending factor of 15 x D. A separate bending radius for fixed installation is not specified in the reference documentation.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Fine-Stranded Bare Copper, Class 5 |
| 2 | Core Insulation | Halogen-Free Cross-Linked Polyolefin Copolymer |
| 3 | Outer Sheath | Grey Halogen-Free Cross-Linked Polyolefin Copolymer |
Core Identification & Cable Variants
| Version | Core Identification | Protective Earth |
|---|---|---|
| HSLH-JZ FRNC | Black Numbered Cores and Green/Yellow Core | Yes |
| HSLH-OZ FRNC | Black Numbered Cores | No |
Fire Performance Characteristics
| Parameter | Reference Standard / Value |
|---|---|
| Halogen-Free Construction | Yes |
| Fire Performance Designation | FRNC |
| Single Cable Flame Propagation | EN 60332-1 |
| Bunched Cable Flame Propagation | EN 50266-2-4 |
| Bunched Cable Flame Category | IEC 60332-3 Category C |
| Combustion Gas Acidity and Conductivity | Construction Adapted to DIN EN 50267-2-2 |
| Smoke Density | Construction Adapted to DIN EN 50268-2 |
| CPR Euroclass | Not Specified |
| FE180 Circuit Integrity | Not Specified |
| E30 / E60 / E90 Functional Integrity | Not Specified |
Mechanical & Environmental Characteristics
| Parameter | Reference Value |
|---|---|
| Outer Sheath Material | Halogen-Free Cross-Linked Polyolefin Copolymer |
| Outer Sheath Colour | Grey |
| Dry Indoor Environments | Suitable |
| Damp Indoor Environments | Suitable |
| Wet Indoor Environments | Suitable |
| Fixed Installation | Suitable |
| Movable Installation | Suitable Without Excessive Tensile Stress or Forced Bending |
| Outdoor Installation | Not Permitted |
| Forced Bending | Not Permitted |
| High Tensile Stress | Not Permitted |
| Oil Resistance | Not Specified |
| UV Resistance | Not Specified |
| Direct Burial | Not Specified |
| Permanent Water Immersion | Not Specified |
| Continuous-Flex Applications | Not Specified |
Applicable Standards
| Standard | Reference Application |
|---|---|
| DIN EN 60228 | Flexible Copper Conductors, Class 5 |
| DIN EN 50266-2-4 | Adapted Construction – Bunched Cable Flame Propagation, Category C |
| DIN EN 50267-2-2 | Adapted Construction – Acidity and Conductivity of Combustion Gases |
| DIN EN 50268-2 | Adapted Construction – Smoke Density Measurement |
| EN 60332-1 | Single Cable Vertical Flame Propagation |
| IEC 60332-3 Category C | Bunched Cable Vertical Flame Propagation |