YSLCY – Screened PVC Control Cable 300/500 V
Flexible multicore control, measurement and signal cable with fine-stranded copper conductors, PVC insulation, tinned copper wire braid and a grey PVC outer sheath with enhanced oil resistance. Designed for applications requiring protection against external electromagnetic interference.
Product Overview
YSLCY is a flexible screened PVC control and signal cable designed for control, measurement, signalling and impulse transmission applications.
The cable incorporates fine-stranded bare copper conductors according to DIN EN 60228 Class 5, providing flexibility for installation and equipment connections.
Individual conductors are insulated with polyvinyl chloride (PVC). The assembled cable core is covered with plastic foil and an overall braid of round tinned copper wires.
The copper braid improves protection against external electromagnetic fields and signal interference, supporting reliable signal transmission in industrial control and measurement systems.
The outer sheath consists of grey PVC with enhanced oil resistance.
YSLCY is available in reference configurations ranging from 0.5 to 25 mm², with between 2 and 50 cores depending on the selected conductor cross-section.
Key Technical Features
Cable Variants
YSLCY-JZ
With Protective Earth Conductor
One green/yellow protective conductor and remaining black cores with numerical identification.
Suitable for control and equipment connections requiring a protective earth conductor.
YSLCY-OZ
Without Protective Earth Conductor
Black cores with numerical identification, without a green/yellow protective conductor.
Suitable for control, signal and measurement circuits where a protective earth conductor is not required within the cable.
Colour-Coded Versions
Selected YSLCY configurations are also available with coloured cores according to HD 308 S2.
These configurations are identified with an asterisk in the technical dimensions table.
The required core identification and protective conductor arrangement must be specified when ordering.
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Electromagnetic Compatibility & Screening
Tinned Copper Wire Braid
The overall tinned copper wire braid provides screening against external electromagnetic interference.
This construction is particularly relevant for control, measurement and signal circuits operating in environments containing electrical equipment and industrial machinery.
Screen coverage and transfer impedance are not specified in the reference documentation.
Industrial Signal Protection
The screened construction helps reduce the influence of external electromagnetic fields on transmitted signals.
Effective electromagnetic compatibility depends on cable routing, screen termination, grounding arrangements and the electrical characteristics of the complete installation.
Oil Resistance & Flame Performance
Enhanced Oil Resistance
The grey PVC outer sheath provides enhanced resistance to oils.
Compatibility with specific oils, chemicals, concentrations and exposure conditions must be confirmed for the intended application.
Flame Propagation Performance
The reference documentation specifies EN 60332-1-2 for vertical flame propagation testing of a single insulated wire or cable.
This test does not establish fire-resistant circuit integrity or a CPR Euroclass classification.
Typical Applications
Installation Conditions
YSLCY cables are intended for control, measurement and signal transmission installations requiring flexible conductors and overall electromagnetic screening.
The permitted temperature range during bending is -5°C to +70°C.
For fixed installations, the specified temperature range is -30°C to +70°C.
The minimum bending radius for fixed or one-time installation is 10 times the cable outer diameter.
During bending, the minimum radius is 20 times the cable outer diameter.
Suitability for outdoor installation, direct burial, permanent immersion, continuous-flex operation and drag-chain applications is not established by the reference documentation.
Applicable Standards
DIN VDE 0281 – Cable construction adapted to this reference standard.
DIN EN 60228, Class 5 – Flexible copper conductor construction.
HD 308 S2 – Core identification for selected colour-coded cable configurations.
EN 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.
YSLCY – Cable Sizes & Technical Data
Complete reference range of flexible screened PVC control and signal cables rated 300/500 V, including conductor stranding, copper content, cable dimensions, approximate weights, electrical characteristics and installation parameters.
Available Cable Sizes & Construction Data
| Cable Size (mm²) | Number of Cores | Copper Content (kg/km) | Approx. Conductor Stranding | Approx. Outer Diameter (mm) | Approx. Cable Weight (kg/km) |
|---|---|---|---|---|---|
| YSLCY – 0.5 mm² | |||||
| 2x0.5 | 2 | 34.6 | 16 x 0.21 | 5.6 | 45 |
| 3x0.5 | 3 | 41.3 | 16 x 0.21 | 5.9 | 55 |
| 4x0.5 | 4 | 47.0 | 16 x 0.21 | 6.4 | 73 |
| 5x0.5 | 5 | 54.7 | 16 x 0.21 | 7.0 | 91 |
| 12x0.5 | 12 | 99.8 | 16 x 0.21 | 9.8 | 208 |
| 25x0.5 | 25 | 202.6 | 16 x 0.21 | 13.7 | 354 |
| YSLCY – 0.75 mm² | |||||
| 2x0.75 | 2 | 41.3 | 24 x 0.21 | 6.2 | 56 |
| 3x0.75 | 3 | 49.9 | 24 x 0.21 | 6.5 | 70 |
| 4x0.75 | 4 | 58.6 | 24 x 0.21 | 7.0 | 96 |
| 5x0.75 | 5 | 69.1 | 24 x 0.21 | 7.8 | 157 |
| 7x0.75 | 7 | 85.4 | 24 x 0.21 | 8.4 | 168 |
| 10x0.75 | 10 | 116.2 | 24 x 0.21 | 10.4 | 217 |
| 12x0.75 | 12 | 132.5 | 24 x 0.21 | 10.9 | 231 |
| 18x0.75 | 18 | 202.6 | 24 x 0.21 | 12.8 | 314 |
| 25x0.75 | 25 | 268.8 | 24 x 0.21 | 15.2 | 434 |
| 34x0.75 | 34 | 332.2 | 24 x 0.21 | 17.1 | 529 |
| YSLCY – 1 mm² | |||||
| 2x1 | 2 | 49.0 | 32 x 0.21 | 6.5 | 83 |
| 3x1 | 3 | 59.5 | 32 x 0.21 | 6.7 | 111 |
| 4x1 | 4 | 71.0 | 32 x 0.21 | 7.4 | 131 |
| 5x1 | 5 | 84.5 | 32 x 0.21 | 8.1 | 155 |
| 7x1 | 7 | 107.5 | 32 x 0.21 | 8.8 | 190 |
| 12x1 | 12 | 177.6 | 32 x 0.21 | 11.5 | 286 |
| 18x1 | 18 | 257.3 | 32 x 0.21 | 13.8 | 393 |
| 25x1 | 25 | 339.8 | 32 x 0.21 | 16.0 | 658 |
| 34x1 | 34 | 439.7 | 32 x 0.21 | 18.4 | 759 |
| 50x1 | 50 | 644.2 | 32 x 0.21 | 22.0 | 994 |
| YSLCY – 1.5 mm² | |||||
| 2x1.5 * | 2 | 62.4 | 30 x 0.26 | 7.1 | 97 |
| 3x1.5 * | 3 | 78.7 | 30 x 0.26 | 7.6 | 124 |
| 4x1.5 * | 4 | 96.0 | 30 x 0.26 | 8.2 | 166 |
| 5x1.5 * | 5 | 114.2 | 30 x 0.26 | 9.0 | 192 |
| 7x1.5 | 7 | 147.8 | 30 x 0.26 | 9.8 | 245 |
| 12x1.5 | 12 | 257.3 | 30 x 0.26 | 13.0 | 365 |
| 18x1.5 | 18 | 358.1 | 30 x 0.26 | 15.5 | 556 |
| 25x1.5 | 25 | 508.8 | 30 x 0.26 | 18.0 | 737 |
| 27x1.5 | 27 | 537.6 | 30 x 0.26 | 20.0 | 750 |
| 34x1.5 | 34 | 658.2 | 30 x 0.26 | 20.9 | 966 |
| 50x1.5 | 50 | 961.0 | 30 x 0.26 | 24.8 | 1342 |
| YSLCY – 2.5 mm² | |||||
| 2x2.5 | 2 | 88.3 | 50 x 0.26 | 8.5 | 161 |
| 3x2.5 * | 3 | 113.3 | 50 x 0.26 | 9.0 | 187 |
| 4x2.5 | 4 | 141.1 | 50 x 0.26 | 9.9 | 241 |
| 5x2.5 | 5 | 169.0 | 50 x 0.26 | 11.0 | 274 |
| 7x2.5 | 7 | 242.9 | 50 x 0.26 | 12.0 | 344 |
| 12x2.5 | 12 | 391.7 | 50 x 0.26 | 15.9 | 407 |
| YSLCY – 4 mm² | |||||
| 4x4 | 4 | 238.1 | 56 x 0.31 | 11.6 | 307 |
| 5x4 | 5 | 276.5 | 50 x 0.31 | 12.8 | 370 |
| YSLCY – 6 mm² | |||||
| 2x6 | 2 | 163.2 | 84 x 0.31 | 12.5 | 180 |
| 4x6 | 4 | 329.3 | 84 x 0.31 | 14.0 | 402 |
| 5x6 | 5 | 386.9 | 84 x 0.31 | 15.5 | 506 |
| YSLCY – 10 mm² | |||||
| 4x10 * | 4 | 513.6 | 80 x 0.41 | 17.2 | 747 |
| 5x10 | 5 | 609.6 | 80 x 0.41 | 19.3 | 861 |
| YSLCY – 16 mm² | |||||
| 4x16 | 4 | 768.0 | 128 x 0.41 | 20.0 | 1041 |
| 5x16 | 5 | 921.6 | 128 x 0.41 | 22.2 | 1289 |
| YSLCY – 25 mm² | |||||
| 4x25 | 4 | 1228.8 | 200 x 0.41 | 24.7 | 1460 |
| 5x25 | 5 | 1468.8 | 200 x 0.41 | 27.5 | 1840 |
* Also available with colour-coded cores according to HD 308 S2.
Cable sizes are expressed as the number of cores multiplied by the nominal conductor cross-section in mm². The table uses generic size notation as listed in the reference documentation. The required JZ, OZ or colour-coded version must be specified when ordering.
Conductor stranding is expressed as the approximate number of individual wires multiplied by their nominal diameter in millimetres. Copper content values are reference figures and must not be interpreted as independently verified recoverable copper mass.
Conductor Construction by Cross-Section
| Nominal Cross-Section (mm²) | Approx. Conductor Stranding | Conductor Class | Reference Configurations |
|---|---|---|---|
| 0.5 | 16 x 0.21 mm | Class 5 | 6 |
| 0.75 | 24 x 0.21 mm | Class 5 | 10 |
| 1 | 32 x 0.21 mm | Class 5 | 10 |
| 1.5 | 30 x 0.26 mm | Class 5 | 11 |
| 2.5 | 50 x 0.26 mm | Class 5 | 6 |
| 4 | 56 x 0.31 / 50 x 0.31 mm | Class 5 | 2 |
| 6 | 84 x 0.31 mm | Class 5 | 3 |
| 10 | 80 x 0.41 mm | Class 5 | 2 |
| 16 | 128 x 0.41 mm | Class 5 | 2 |
| 25 | 200 x 0.41 mm | Class 5 | 2 |
The reference documentation specifies different conductor stranding for 4x4 mm² and 5x4 mm². These values are retained as published and must be confirmed for the supplied cable.
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Rated Voltage U0/U | 300/500 V |
| Test Voltage | 2000 V AC |
| Materijal vodiča | Bare Copper |
| Conductor Construction | Fine-Stranded, Flexible |
| Conductor Class | Class 5 |
| Conductor Standard | DIN EN 60228 |
| Core Insulation | PVC |
| Overall Screen | Tinned Copper Wire Braid |
| Screen Coverage | Not Specified |
| Transfer Impedance | Not Specified |
Temperature Characteristics
| Installation / Operating Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| During Bending | -5°C | +70°C |
| Fixed Installation | -30°C | +70°C |
| Short-Circuit Condition | Not Specified | +150°C |
Maximum short-circuit duration: 5 seconds.
Minimum Cable Bending Radius
| Cable Size (mm²) | Outer Diameter (mm) | Fixed Installation 10 x D (mm) | During Bending 20 x D (mm) |
|---|---|---|---|
| 0.5 mm² | |||
| 2x0.5 | 5.6 | 56 | 112 |
| 3x0.5 | 5.9 | 59 | 118 |
| 4x0.5 | 6.4 | 64 | 128 |
| 5x0.5 | 7.0 | 70 | 140 |
| 12x0.5 | 9.8 | 98 | 196 |
| 25x0.5 | 13.7 | 137 | 274 |
| 0.75 mm² | |||
| 2x0.75 | 6.2 | 62 | 124 |
| 3x0.75 | 6.5 | 65 | 130 |
| 4x0.75 | 7.0 | 70 | 140 |
| 5x0.75 | 7.8 | 78 | 156 |
| 7x0.75 | 8.4 | 84 | 168 |
| 10x0.75 | 10.4 | 104 | 208 |
| 12x0.75 | 10.9 | 109 | 218 |
| 18x0.75 | 12.8 | 128 | 256 |
| 25x0.75 | 15.2 | 152 | 304 |
| 34x0.75 | 17.1 | 171 | 342 |
| 1 mm² | |||
| 2x1 | 6.5 | 65 | 130 |
| 3x1 | 6.7 | 67 | 134 |
| 4x1 | 7.4 | 74 | 148 |
| 5x1 | 8.1 | 81 | 162 |
| 7x1 | 8.8 | 88 | 176 |
| 12x1 | 11.5 | 115 | 230 |
| 18x1 | 13.8 | 138 | 276 |
| 25x1 | 16.0 | 160 | 320 |
| 34x1 | 18.4 | 184 | 368 |
| 50x1 | 22.0 | 220 | 440 |
| 1.5 mm² | |||
| 2x1.5 * | 7.1 | 71 | 142 |
| 3x1.5 * | 7.6 | 76 | 152 |
| 4x1.5 * | 8.2 | 82 | 164 |
| 5x1.5 * | 9.0 | 90 | 180 |
| 7x1.5 | 9.8 | 98 | 196 |
| 12x1.5 | 13.0 | 130 | 260 |
| 18x1.5 | 15.5 | 155 | 310 |
| 25x1.5 | 18.0 | 180 | 360 |
| 27x1.5 | 20.0 | 200 | 400 |
| 34x1.5 | 20.9 | 209 | 418 |
| 50x1.5 | 24.8 | 248 | 496 |
| 2.5 mm² | |||
| 2x2.5 | 8.5 | 85 | 170 |
| 3x2.5 * | 9.0 | 90 | 180 |
| 4x2.5 | 9.9 | 99 | 198 |
| 5x2.5 | 11.0 | 110 | 220 |
| 7x2.5 | 12.0 | 120 | 240 |
| 12x2.5 | 15.9 | 159 | 318 |
| 4 mm² | |||
| 4x4 | 11.6 | 116 | 232 |
| 5x4 | 12.8 | 128 | 256 |
| 6 mm² | |||
| 2x6 | 12.5 | 125 | 250 |
| 4x6 | 14.0 | 140 | 280 |
| 5x6 | 15.5 | 155 | 310 |
| 10 mm² | |||
| 4x10 * | 17.2 | 172 | 344 |
| 5x10 | 19.3 | 193 | 386 |
| 16 mm² | |||
| 4x16 | 20.0 | 200 | 400 |
| 5x16 | 22.2 | 222 | 444 |
| 25 mm² | |||
| 4x25 | 24.7 | 247 | 494 |
| 5x25 | 27.5 | 275 | 550 |
Minimum bending radii are calculated from the approximate outer diameters and the specified bending factors of 10 x D for fixed or one-time installation and 20 x D during bending. Actual installation limits must be confirmed using the supplied cable dimensions.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Fine-Stranded Bare Copper, Class 5 |
| 2 | Core Insulation | Polyvinyl Chloride (PVC) |
| 3 | Wrapping Layer | Plastic Foil |
| 4 | Overall Screen | Braid of Round Tinned Copper Wires |
| 5 | Outer Sheath | Grey PVC with Enhanced Oil Resistance |
Core Identification & Cable Variants
| Version | Core Identification | Protective Earth |
|---|---|---|
| YSLCY-JZ | Black Numbered Cores and Green/Yellow Core | Yes |
| YSLCY-OZ | Black Numbered Cores | No |
| Colour-Coded Version | According to HD 308 S2 | Depending on Configuration |
Colour-Coded Cable Configurations
| Cable Size (mm²) | Additional Core Identification Option |
|---|---|
| 2x1.5 | Coloured Cores According to HD 308 S2 |
| 3x1.5 | Coloured Cores According to HD 308 S2 |
| 4x1.5 | Coloured Cores According to HD 308 S2 |
| 5x1.5 | Coloured Cores According to HD 308 S2 |
| 3x2.5 | Coloured Cores According to HD 308 S2 |
| 4x10 | Coloured Cores According to HD 308 S2 |
Mechanical & Environmental Characteristics
| Parameter | Reference Value |
|---|---|
| Outer Sheath Material | PVC |
| Outer Sheath Colour | Grey |
| Oil Resistance | Enhanced |
| Oil Resistance Test Standard | Not Specified |
| Electromagnetic Screening | Overall Tinned Copper Wire Braid |
| Flame Propagation Test | EN 60332-1-2 |
| Outdoor Installation | Not Specified |
| UV Resistance | Not Specified |
| Direct Burial | Not Specified |
| Continuous-Flex Applications | Not Specified |
| Maximum Tensile Load | Not Specified |
| CPR Classification | Not Specified |
Applicable Standards
| Standard | Reference Application |
|---|---|
| DIN VDE 0281 | Adapted Cable Construction |
| DIN EN 60228 | Flexible Copper Conductors, Class 5 |
| HD 308 S2 | Core Identification for Colour-Coded Versions |
| EN 60332-1-2 | Vertical Flame Propagation Test on a Single Cable |