Potraži kabel

Select a cable or enter another designation.


UNIMA CABLE | DATA & COMMUNICATION CABLES

J-Y(ST)Y – Shielded Telecommunication Installation Cable

Shielded indoor telecommunication installation cable with solid bare copper conductors, PVC core insulation, aluminium foil static screen with drain wire and a grey PVC outer sheath. Designed for fixed indoor telecommunication installations.

300 V Peak Solid Copper Class 1 0.6 / 0.8 mm PVC Insulation Aluminium Foil Screen PVC Sheath DIN VDE 0815 Indoor Installation

Product Overview

J-Y(ST)Y is a shielded telecommunication installation cable designed for permanent fixed installation in indoor communication systems.

The cable incorporates solid bare copper conductors with nominal conductor diameters of 0.6 mm or 0.8 mm. Each conductor is insulated with polyvinyl chloride (PVC).

A static screen consisting of plastic-coated aluminium foil with a drain wire provides electrostatic shielding for the communication circuits.

The cable construction is completed with a grey PVC outer sheath suitable for the specified indoor installation conditions.

The reference product range includes configurations from 1 to 100 pairs, depending on the selected conductor diameter.

Key Technical Features

300 V Peak Operating Voltage
1–100 Number of Pairs
0.6 / 0.8 mm Conductor Diameter
+70°C Maximum Fixed Installation Temperature

Cable Variants

J-Y(ST)Y – 0.6 mm

Solid Copper Conductor Diameter: 0.6 mm

Reference configurations from 1 to 100 pairs, with a conductor loop resistance of 130.0 Ω/km.

Approximate cable diameters range from 4.5 to 22.1 mm.

J-Y(ST)Y – 0.8 mm

Solid Copper Conductor Diameter: 0.8 mm

Reference configurations from 1 to 60 pairs, with a conductor loop resistance of 73.2 Ω/km.

Approximate cable diameters range from 5.5 to 25.8 mm.

Cable Designation

J Indoor Installation Cable
Y PVC Core Insulation
(ST) Static Screen
Y PVC Outer Sheath

Construction & Technical Properties

Cable Construction

Materijal vodiča Bare Copper
Conductor Class Class 1, Solid
Conductor Diameter 0.6 mm / 0.8 mm
Core Insulation PVC
Core Identification DIN VDE 0815
Static Screen Plastic-Coated Aluminium Foil
Drain Wire Yes
Outer Sheath PVC
Sheath Colour Grey
Number of Pairs – 0.6 mm 1–100
Number of Pairs – 0.8 mm 1–60
Installation Type Fixed Indoor Installation

Electrical & Mechanical Data

Peak Operating Voltage 300 V
Test Voltage – Core/Core 800 V AC, 50 Hz
Test Voltage – Core/Screen 800 V AC, 50 Hz
Loop Resistance – 0.6 mm 130.0 Ω/km
Loop Resistance – 0.8 mm 73.2 Ω/km
Minimum Insulation Resistance 100 MΩ/km (as stated)
Maximum Operating Capacitance 10 nF/km – To Be Confirmed
Capacitance Unbalance Max. 300 pF / 100 m
Temperature During Bending -5°C to +50°C
Fixed Installation Temperature -30°C to +70°C
Minimum Bending Radius 15 x Cable Diameter
Flame Test References EN 60332-1-2 / EN 60332-2-2

Typical Applications

Indoor Telecommunication Systems
Telephone Installation Networks
Fixed Communication Wiring
Commercial Building Communications
Industrial Facility Communication Systems
Indoor Utility Communication Infrastructure

Applicable Standards

DIN VDE 0815 – Reference standard for core identification of telecommunication installation cables.

DIN EN 60228, Class 1 – Solid conductor construction, as referenced in the technical documentation.

EN 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.

EN 60332-2-2 – Vertical flame propagation test for small insulated wires or cables.

Installation Conditions

J-Y(ST)Y is intended for fixed telecommunication installations inside buildings.

The permitted temperature range during bending is -5°C to +50°C. Once installed in a fixed position, the specified temperature range is -30°C to +70°C.

A minimum bending radius of 15 times the cable outer diameter must be maintained during bending.

The cable is intended for communication applications and is not specified as a general-purpose power distribution cable.

Technical Note: The 300 V value represents the peak operating voltage and must not be interpreted as a rated power cable voltage. Conductor sizes of 0.6 mm and 0.8 mm refer to conductor diameter, not cross-sectional area in mm². The operating capacitance of 10 nF/km and the insulation resistance unit are reproduced from the reference documentation and require confirmation. CPR classification, outdoor installation, direct burial suitability and circuit integrity performance are not specified. All technical characteristics must be confirmed for the supplied product.
UNIMA CABLE | TECHNICAL DIMENSIONS

J-Y(ST)Y – Cable Sizes & Technical Data

28 reference configurations of shielded telecommunication installation cables with solid copper conductors, nominal conductor diameters of 0.6 mm and 0.8 mm, copper content, insulation thickness, outer diameter and approximate cable weight.

28 Reference Configurations
1–100 Number of Pairs
0.6 / 0.8 mm Conductor Diameter
26–978 kg/km Cable Weight

Available Cable Sizes & Dimensions

Tip kabela Configuration Number of Pairs Conductor Diameter (mm) Copper Content (kg/km) Insulation Thickness (mm) Approx. Outer Diameter (mm) Approx. Cable Weight (kg/km)
J-Y(ST)Y – Solid Copper Conductor Ø 0.6 mm
J-Y(ST)Y1x2x0.610.66.71.14.526
J-Y(ST)Y2x2x0.620.612.51.14.935
J-Y(ST)Y3x2x0.630.618.21.16.249
J-Y(ST)Y4x2x0.640.623.01.16.658
J-Y(ST)Y5x2x0.650.628.81.17.159
J-Y(ST)Y6x2x0.660.634.61.17.661
J-Y(ST)Y10x2x0.6100.656.61.19.3113
J-Y(ST)Y12x2x0.6120.669.11.19.5129
J-Y(ST)Y20x2x0.6200.6111.41.110.9191
J-Y(ST)Y30x2x0.6300.6165.11.313.7284
J-Y(ST)Y40x2x0.6400.6218.91.314.5358
J-Y(ST)Y50x2x0.6500.6273.61.316.5438
J-Y(ST)Y60x2x0.6600.6328.31.317.5512
J-Y(ST)Y100x2x0.61000.6545.31.522.1829
J-Y(ST)Y – Solid Copper Conductor Ø 0.8 mm
J-Y(ST)Y1x2x0.810.810.61.15.538
J-Y(ST)Y2x2x0.820.820.21.16.154
J-Y(ST)Y3x2x0.830.829.81.18.077
J-Y(ST)Y4x2x0.840.839.41.18.794
J-Y(ST)Y5x2x0.850.849.91.19.4114
J-Y(ST)Y6x2x0.860.859.51.110.1135
J-Y(ST)Y10x2x0.8100.898.91.313.1205
J-Y(ST)Y12x2x0.8120.8118.11.313.5235
J-Y(ST)Y16x2x0.8160.8157.41.314.8299
J-Y(ST)Y20x2x0.8200.8194.91.315.6352
J-Y(ST)Y30x2x0.8300.8291.81.519.4522
J-Y(ST)Y40x2x0.8400.8387.81.520.9663
J-Y(ST)Y50x2x0.8500.8484.81.723.7832
J-Y(ST)Y60x2x0.8600.8581.81.725.8978

Cable configuration is expressed as number of pairs x two conductors x nominal conductor diameter in millimetres. All 28 configurations are reproduced from the reference technical documentation.

Conductor Characteristics

Parameter 0.6 mm Conductor 0.8 mm Conductor
Materijal vodiča Bare Copper Bare Copper
Conductor Class Class 1 Class 1
Nominal Conductor Diameter 0.6 mm 0.8 mm
Calculated Geometric Cross-Section 0.283 mm² 0.503 mm²
Conductor Loop Resistance 130.0 Ω/km 73.2 Ω/km
Reference Pair Range 1–100 Pairs 1–60 Pairs
Approximate Outer Diameter Range 4.5–22.1 mm 5.5–25.8 mm
Copper Content Range 6.7–545.3 kg/km 10.6–581.8 kg/km
Approximate Cable Weight Range 26–829 kg/km 38–978 kg/km

Geometric conductor cross-sections are calculated from the nominal conductor diameters using the circular area formula. They are provided for reference only and do not replace the original diameter-based cable designation.

Electrical Characteristics

Parameter Reference Value Condition
Peak Operating Voltage 300 V Telecommunication Applications
Test Voltage – Core/Core 800 V AC 50 Hz
Test Voltage – Core/Screen 800 V AC 50 Hz
Conductor Loop Resistance 130.0 Ω/km 0.6 mm Conductor
Conductor Loop Resistance 73.2 Ω/km 0.8 mm Conductor
Minimum Insulation Resistance 100 MΩ/km Unit as Stated in Reference
Maximum Operating Capacitance 10 nF/km To Be Confirmed
Maximum Capacitance Unbalance 300 pF Per 100 m

Mechanical & Installation Characteristics

Parameter Reference Value
Minimum Bending Radius 15 x Cable Outer Diameter
Installation Environment Indoor
Installation Type Fixed Installation
Conductor Construction Solid Copper, Class 1
Izolacijski materijal PVC
Insulation Thickness Range 1.1–1.7 mm (as labelled in reference)
Screen Construction Plastic-Coated Aluminium Foil with Drain Wire
Outer Sheath Material PVC
Outer Sheath Colour Grey
Approximate Outer Diameter Range 4.5–25.8 mm
Approximate Cable Weight Range 26–978 kg/km

Temperature Characteristics

Condition Minimum Temperature Maximum Temperature
During Bending -5°C +50°C
Fixed Installation -30°C +70°C

Minimum Bending Radius – Calculated Values

Configuration Approx. Outer Diameter (mm) Minimum Bending Radius – 15 x D (mm)
Conductor Diameter 0.6 mm
1x2x0.64.567.5
2x2x0.64.973.5
3x2x0.66.293.0
4x2x0.66.699.0
5x2x0.67.1106.5
6x2x0.67.6114.0
10x2x0.69.3139.5
12x2x0.69.5142.5
20x2x0.610.9163.5
30x2x0.613.7205.5
40x2x0.614.5217.5
50x2x0.616.5247.5
60x2x0.617.5262.5
100x2x0.622.1331.5
Conductor Diameter 0.8 mm
1x2x0.85.582.5
2x2x0.86.191.5
3x2x0.88.0120.0
4x2x0.88.7130.5
5x2x0.89.4141.0
6x2x0.810.1151.5
10x2x0.813.1196.5
12x2x0.813.5202.5
16x2x0.814.8222.0
20x2x0.815.6234.0
30x2x0.819.4291.0
40x2x0.820.9313.5
50x2x0.823.7355.5
60x2x0.825.8387.0

Minimum bending radii are calculated using the approximate outer diameters and the specified factor of 15 x D. Actual installation requirements must be based on the supplied cable dimensions.

Applicable Technical Standards

Standard Reference Application
DIN VDE 0815 Core Identification
DIN EN 60228 Class 1 Conductor Construction
EN 60332-1-2 Vertical Flame Propagation Test for a Single Insulated Wire or Cable
EN 60332-2-2 Vertical Flame Propagation Test for Small Insulated Wires or Cables
Technical Note: All cable dimensions, copper contents and cable weights are indicative. Conductor diameters are expressed in millimetres and must not be confused with conductor cross-sectional areas in mm². Cable weights are expressed in kg/km. Drum and packaging weights are not specified in the reference documentation. Reference configurations do not constitute a declaration of current stock availability.
Data Verification: The maximum operating capacitance of 10 nF/km, minimum insulation resistance of 100 MΩ/km and insulation thickness values of 1.1–1.7 mm are reproduced as stated in the reference documentation. These parameters and their units require confirmation before technical approval. The 300 V peak operating voltage is not a rated power cable voltage. CPR classification is not specified. All technical specifications, applicable standards and delivery conditions must be confirmed for the supplied product.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


KOLEKCIJA KABELA UNIMA

Istražite našu ponudu kabela

Otkrijte vrste kabela, tehničke specifikacije i rješenja za svoje projekte.

96 Cable Types Available