NSHXAFö – Halogen-Free Special Rubber Single-Core Cable 1.8/3 kV
Special flexible single-core rubber cable with a fine-stranded bare or tinned copper conductor, EPR rubber insulation and a black halogen-free polymer outer sheath. Designed for railway vehicles, trolleybuses, switchboards and electrical distribution equipment requiring short-circuit and earth fault protection.
Product Overview
NSHXAFö is a special halogen-free single-core rubber cable with a rated voltage of 1.8/3 kV, designed with reference to DIN VDE 0250 Part 602.
The cable incorporates a fine-stranded bare or tinned copper conductor according to DIN EN 60228 Class 5, providing flexibility for routing and termination within electrical equipment.
The conductor is insulated with an ethylene propylene rubber (EPR) compound and protected by a black halogen-free polymer outer sheath.
The outer sheath is specified as resistant to ozone, abrasion and oil, with flame-retardant performance according to EN 60332-1-2.
NSHXAFö is intended for railway vehicles, trolleybuses and installations in dry locations, including switchboards and distribution equipment up to 1,000 V, where short-circuit and earth fault protection cable construction is required.
The reference product range covers 15 nominal conductor cross-sections from 2.5 mm² to 300 mm².
Key Technical Features
Cable Construction & Technical Properties
Cable Construction
Electrical & Mechanical Properties
Flexible Copper Conductor
Class 5 Fine-Stranded Construction
The conductor consists of multiple fine copper wires arranged in a flexible stranded construction according to DIN EN 60228 Class 5.
The flexible construction facilitates routing and termination in electrical cabinets, distribution equipment and vehicle electrical installations.
Individual conductor wire diameters range from approximately 0.26 mm to 0.51 mm, depending on the nominal conductor cross-section.
Bare or Tinned Copper
The reference construction allows either bare copper or tinned copper conductors.
The required conductor finish should be specified according to the installation conditions and project requirements.
The final conductor material and finish must be confirmed during quotation.
EPR Insulation & Halogen-Free Outer Sheath
Ethylene Propylene Rubber Insulation
EPR rubber insulation provides the dielectric insulation required for the specified rated voltage of 1.8/3 kV.
The reference AC test voltage is 6 kV.
The specified maximum short-circuit temperature is +250°C for a maximum duration of five seconds.
The flexible rubber construction supports the documented installation and bending conditions.
Halogen-Free Polymer Outer Sheath
The black halogen-free polymer outer sheath provides mechanical protection and resistance to ozone, oil and abrasion.
Flame-retardant performance is specified according to EN 60332-1-2.
Oil resistance is specified according to EN 60811-2-1.
Additional smoke density and combustion gas performance classifications are not stated in the reference documentation.
Short-Circuit & Earth Fault Protection
NSHXAFö is designed for electrical installations requiring a short-circuit and earth fault protection cable construction.
The combination of flexible copper conductors, EPR insulation and a protective halogen-free sheath is intended for the documented applications in vehicle electrical systems, switchboards and distribution equipment.
The maximum specified short-circuit temperature is +250°C, with a maximum duration of five seconds.
The permissible short-circuit current must be determined according to conductor cross-section, prospective fault current, protective device operating time and the applicable installation requirements.
Typical Applications
Installation Conditions
Specified Installation Parameters
Additional Installation Considerations
Fire & Environmental Performance
Specified Properties
Additional Fire Performance Requirements
Applicable Standards
DIN VDE 0250-602 – Reference product standard for special rubber cable construction.
DIN EN 60228 Class 5 – Flexible stranded conductors of insulated cables.
EN 60811-2-1 – Oil resistance test standard as referenced in the original technical documentation.
EN 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.
NSHXAFö 1.8/3 kV – Cable Sizes & Technical Data
Complete reference range of halogen-free special single-core rubber cables with Class 5 copper conductors, EPR insulation and halogen-free polymer outer sheath, including copper figures, conductor construction, cable dimensions, current ratings and bending radii.
Complete Cable Size Range
| Cable Size (mm²) | Copper Figure (kg/km) | Approx. Conductor Construction (n × mm) | Approx. Outer Diameter (mm) | Current Rating in Air (A) | Approx. Cable Weight (kg/km) |
|---|---|---|---|---|---|
| Small Cross-Section Single-Core Cables | |||||
| 1x2.5 | 25 | 50 × 0.26 | 7.5 | 41 | 70 |
| 1x4 | 40 | 56 × 0.31 | 9.0 | 55 | 90 |
| 1x6 | 60 | 84 × 0.31 | 9.5 | 70 | 120 |
| 1x10 | 100 | 80 × 0.41 | 11.0 | 98 | 180 |
| Medium Cross-Section Single-Core Cables | |||||
| 1x16 | 160 | 126 × 0.41 | 13.0 | 132 | 250 |
| 1x25 | 250 | 196 × 0.41 | 15.0 | 176 | 390 |
| 1x35 | 350 | 276 × 0.41 | 16.5 | 218 | 470 |
| 1x50 | 500 | 396 × 0.41 | 18.0 | 276 | 625 |
| 1x70 | 700 | 360 × 0.51 | 20.5 | 347 | 880 |
| 1x95 | 950 | 475 × 0.51 | 24.0 | 416 | 1190 |
| Large Cross-Section Single-Core Cables | |||||
| 1x120 | 1200 | 608 × 0.51 | 26.0 | 488 | 1430 |
| 1x150 | 1500 | 756 × 0.51 | 28.0 | 566 | 1750 |
| 1x185 | 1850 | 925 × 0.51 | 31.0 | 644 | 2160 |
| 1x240 | 2400 | 1221 × 0.51 | 34.5 | 775 | 2718 |
| 1x300 | 3000 | 1530 × 0.51 | 30.6* | 898 | 3050 |
All conductor construction values, copper figures, cable dimensions, current ratings and weights are reproduced from the reference technical documentation. Copper figures are published reference metal factors and should not automatically be interpreted as measured net copper mass.
Minimum Bending Radius by Cable Size
| Cable Size (mm²) | Approx. Outer Diameter (mm) | Fixed / Single Bend 6 × D (mm) | In Motion 10 × D (mm) |
|---|---|---|---|
| 1x2.5 | 7.5 | 45 | 75 |
| 1x4 | 9.0 | 54 | 90 |
| 1x6 | 9.5 | 57 | 95 |
| 1x10 | 11.0 | 66 | 110 |
| 1x16 | 13.0 | 78 | 130 |
| 1x25 | 15.0 | 90 | 150 |
| 1x35 | 16.5 | 99 | 165 |
| 1x50 | 18.0 | 108 | 180 |
| 1x70 | 20.5 | 123 | 205 |
| 1x95 | 24.0 | 144 | 240 |
| 1x120 | 26.0 | 156 | 260 |
| 1x150 | 28.0 | 168 | 280 |
| 1x185 | 31.0 | 186 | 310 |
| 1x240 | 34.5 | 207 | 345 |
| 1x300 | 30.6* | 183.6* | 306* |
Bending radii are calculated from the published approximate outer diameters using the specified factors of 6 × D and 10 × D. Values marked with an asterisk require dimensional verification. Actual cable diameter must be used for final installation calculations.
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Rated Voltage U0 | 1,800 V |
| Rated Voltage U | 3,000 V |
| Rated Voltage U0/U | 1.8/3 kV |
| AC Test Voltage | 6,000 V AC |
| Materijal vodiča | Bare or Tinned Copper |
| Conductor Class | Class 5 Flexible |
| Conductor Standard | DIN EN 60228 |
| Nominal Cross-Section Range | 2.5–300 mm² |
| Current Rating in Air | 41–898 A |
| Maximum Short-Circuit Temperature | +250°C |
| Maximum Short-Circuit Duration | 5 Seconds |
| DC Conductor Resistance at 20°C | Not Specified |
| Insulation Resistance | Not Specified |
| Capacitance | Not Specified |
| Inductance | Not Specified |
| Test Voltage Duration | Not Specified |
Temperature Characteristics
| Operating Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| In Motion | -25°C | +70°C |
| Fixed Installation | -40°C | +70°C |
| Short-Circuit Temperature | Not Applicable | +250°C |
| Maximum Short-Circuit Duration | Not Applicable | 5 Seconds |
| Continuous Conductor Operating Temperature | Not Separately Specified | Not Separately Specified |
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Fine-Stranded Bare or Tinned Copper, Class 5 |
| 2 | Insulation | Ethylene Propylene Rubber Compound (EPR) |
| 3 | Outer Sheath | Black Halogen-Free Polymer, Ozone, Oil and Abrasion Resistant |
Conductor Stranding Overview
| Nominal Cross-Section Range | Approx. Individual Wire Diameter | Conductor Construction |
|---|---|---|
| 2.5 mm² | 0.26 mm | Class 5 Copper |
| 4–6 mm² | 0.31 mm | Class 5 Copper |
| 10–50 mm² | 0.41 mm | Class 5 Copper |
| 70–300 mm² | 0.51 mm | Class 5 Copper |
Mechanical & Environmental Properties
| Property | Standard / Reference Value | Status |
|---|---|---|
| Conductor Flexibility | DIN EN 60228 Class 5 | Specified |
| Oil Resistance | EN 60811-2-1 | Specified |
| Ozone Resistance | Halogen-Free Polymer Sheath | Specified |
| Abrasion Resistance | Halogen-Free Polymer Sheath | Specified |
| Minimum Fixed Bending Radius | 6 × D | Specified |
| Minimum Bending Radius in Motion | 10 × D | Specified |
| Fixed Temperature Range | -40°C to +70°C | Specified |
| Temperature in Motion | -25°C to +70°C | Specified |
| UV Resistance | Not Specified | Requires Verification |
| Water Immersion Resistance | Not Specified | Requires Verification |
| Continuous Drag Chain Operation | Not Specified | Requires Verification |
| Maximum Installation Tensile Load | Not Specified | Requires Verification |
| Outer Sheath Colour | Crna | Specified |
Fire Performance & Certification
| Property | Standard / Reference | Declared Performance |
|---|---|---|
| Halogen-Free Construction | Reference Product Description | Specified |
| Single-Cable Flame Retardancy | EN 60332-1-2 | Specified |
| Bunched Cable Flame Retardancy | IEC 60332-3 Series | Not Declared |
| CPR Reaction to Fire | EN 50575 / EN 13501-6 | Not Specified |
| Low-Smoke Performance | EN IEC 61034-2 | Not Declared |
| Halogen Gas Test Performance | EN IEC 60754 Series | Test Standard Not Specified |
| Fire-Resistant Circuit Integrity | IEC 60331 Series | Not Declared |
| Railway Fire Safety Classification | EN 45545-2 | Not Specified |
Installation & Application Conditions
| Application / Installation Method | Reference Status |
|---|---|
| Railway Vehicle Electrical Installations | Specified Application |
| Trolleybus Electrical Installations | Specified Application |
| Dry Locations | Specified Application |
| Electrical Switchboards | Specified Application |
| Distribution Equipment up to 1,000 V | Specified Application |
| Short-Circuit Protection Applications | Specified Application |
| Earth Fault Protection Applications | Specified Application |
| Outdoor Installation | Not Specified |
| Directly Buried Installation | Not Specified |
| Permanent Water Immersion | Not Specified |
| Battery Energy Storage Systems | Project-Specific Verification Required |
| Continuous Dynamic Flexing | Duty Cycle Not Specified |
Applicable Standards
| Standard | Područje primjene |
|---|---|
| DIN VDE 0250-602 | Special Rubber Cable Construction |
| DIN EN 60228 | Conductors of Insulated Cables, Class 5 |
| EN 60811-2-1 | Oil Resistance Test, as Referenced in Original Datasheet |
| EN 60332-1-2 | Vertical Flame Propagation Test for a Single Insulated Wire or Cable |