UNIMA CABLE | INSTRUMENTATION & CONTROL CABLES

Re-2X(St)H – LSZH Screened Instrumentation Cable 300/500 V

Overall screened multi-pair instrumentation and data transmission cable with stranded copper conductors, XLPE insulation, aluminium/polyester tape screening, tinned copper drain wire and a low-smoke halogen-free outer sheath. Designed for fixed indoor installations in demanding industrial environments.

300/500 V 0.50–1.50 mm² 1–24 Pairs Triad Construction Class 2 Copper XLPE Insulation Overall Aluminium Screen LSZH CPR Eca Oil Resistant Hydrocarbon Resistant EN 50288-7 -40°C to +90°C Fixed Indoor Installation

Product Overview

Re-2X(St)H is an overall screened instrumentation, control and data transmission cable designed for analogue and digital communication systems in industrial electrical installations.

The cable incorporates Class 2 stranded bare copper conductors insulated with cross-linked polyethylene (XLPE). The insulated conductors are twisted into pairs or selected triad configurations.

In multi-pair constructions, the twisted pairs are assembled in concentric layers. An overall aluminium/polyester tape screen with a flexible tinned copper drain wire provides electromagnetic screening for the complete cable assembly.

The outer sheath is manufactured from a low-smoke zero-halogen thermoplastic compound, with a standard black colour based on RAL 9005.

The reference cable construction is particularly suitable for demanding indoor industrial environments, including refineries, chemical plants and process instrumentation installations.

The reference range includes 70 cable configurations covering conductor cross-sections of 0.50, 0.75, 1.00, 1.30 and 1.50 mm², including single-pair, multi-pair and single-triad constructions.

Key Technical Features

300/500 VRadni napon
0.50–1.50 mm²Conductor Range
1–24Number of Pairs
EcaCPR Reaction to Fire
+90°CMaximum Conductor Temperature
+250°CShort-Circuit Temperature
10 × DMinimum Bending Radius
70Reference Configurations

Cable Construction & Technical Properties

Cable Construction

Materijal vodičaBare Copper
Conductor ConstructionClass 2 Stranded
Conductor StandardCEI 20-29 / EN IEC 60228
Conductor Cross-Sections0.50 / 0.75 / 1.00 / 1.30 / 1.50 mm²
Core InsulationCross-Linked Polyethylene (XLPE)
Core ArrangementTwisted Pairs / Triads
Multi-Pair AssemblyConcentric Layers
WrappingPolyester Tape
Overall ScreenAluminium/Polyester Tape
Drain WireFlexible Tinned Copper
Drain Wire Cross-Section0.50 mm²
Individual Pair ScreeningNo – Overall Screen Only
Outer SheathLSZH Thermoplastic Compound
Sheath ColourBlack, Based on RAL 9005
Cable GeometryRound

Electrical & Mechanical Properties

Rated Voltage U0/U300/500 V
Sheath Operating Voltage300/500 V
Maximum AC Voltage U0/U320/550 V AC
Maximum DC Voltage U0/U410/820 V DC
Test Voltage Core-to-Core2.0 kV AC, 50 Hz, 5 min
Test Voltage Core-to-Screen1.5 kV AC, 50 Hz, 1 min
Insulation Resistance>200 MΩ·km
Operating Temperature-40°C to +90°C
Minimum Handling Temperature0°C
Maximum Conductor Temperature+90°C
Maximum Short-Circuit Temperature+250°C
Minimum Bending Radius10 × Outer Diameter
Maximum Installation Tensile Load50 N/mm² of Copper Conductor Cross-Section
Approximate Outer Diameter6.0–31.4 mm
Approximate Cable Weight55–1330 kg/km

Twisted Pair & Triad Construction

Single-Pair Construction

Two XLPE-insulated conductors twisted together to form one signal transmission pair.

Core identification: White and black.

Reference sizes: 1x2x0.50, 1x2x0.75, 1x2x1.00, 1x2x1.30 and 1x2x1.50 mm².

Multi-Pair Construction

Multiple twisted pairs assembled in concentric layers under a common aluminium/polyester tape screen.

Core identification: White and black with progressive numbering for each pair.

Pair configurations: 2, 3, 4, 5, 6, 7, 8, 10, 12, 16, 20 and 24 pairs.

Single-Triad Construction

Three insulated conductors twisted together to form one triad for instrumentation circuits requiring three conductors.

Core identification: White, black and red.

Reference sizes: 1x3x0.50 to 1x3x1.50 mm².

Custom Cable Construction

Alternative core identification and outer sheath colours are available on request according to the reference documentation.

Triad cable constructions can also be requested, subject to technical and commercial confirmation.

Overall Electromagnetic Screening

Aluminium/Polyester Tape Screen

The complete cable assembly is protected by an overall aluminium/polyester tape screen.

The screen helps reduce external electromagnetic interference affecting instrumentation, control and signal transmission circuits.

This construction uses a common overall screen rather than individually screened pairs.

Tinned Copper Drain Wire

A flexible tinned copper drain wire with a nominal cross-section of 0.50 mm² is incorporated into the screening system.

The drain wire facilitates electrical connection of the screen during cable termination.

Screen bonding and earthing must follow the requirements of the instrumentation system and electrical installation design.

LSZH & Fire Performance

CPR Reaction to Fire – Eca

The reference product is classified as Eca according to EN 13501-6 and EN 50575:2014+A1:2016.

Single-cable flame propagation performance is specified according to IEC 60332-1-2.

The cable is not declared fire resistant and must not be used as a substitute for a certified circuit-integrity cable.

Low Smoke & Halogen-Free Properties

The LSZH thermoplastic sheath provides low-smoke and halogen-free characteristics according to the specified reference tests.

Smoke density: EN IEC 61034-2.

Halogen acid gas: EN IEC 60754-1.

Gas acidity and conductivity: EN IEC 60754-2.

Industrial Environmental Resistance

Specified Resistance Properties

Oil ResistanceEN IEC 60811-404
Hydrocarbon ResistanceENI 181
Low Temperature ResistanceEN 60811-504 + 505 + 506
Low SmokeEN IEC 61034-2
Halogen-Free PerformanceEN IEC 60754-1 / 60754-2

Application Limitations

UV ResistanceNot Declared
Ozone ResistanceNot Declared
Water Exposure SuitabilityNot Declared
Impact ResistanceNot Declared
Rodent ProtectionNo
Fire-Resistant Circuit IntegrityNo

Typical Applications

Industrial Instrumentation Systems
Analogue Signal Transmission
Digital Signal Transmission
Industrial Process Control
Oil Refinery Instrumentation
Chemical Processing Plants
Industrial Automation Systems
PLC and DCS Signal Connections
Measurement and Monitoring Systems
Industrial Sensor Connections
Indoor Control Panel Connections
Fixed Industrial Cable Tray Installations

Installation Conditions

Permitted Installation Methods

Fixed InstallationPermitted
Indoor InstallationPermitted
Indoor Free-Air InstallationPermitted
Indoor Protected Installation in AirPermitted
Minimum Bending Radius10 × D
Minimum Handling Temperature0°C

Prohibited Installation Methods

Outdoor InstallationNot Permitted
Direct BurialNot Permitted
Protected Buried InstallationNot Permitted
Mobile InstallationNot Permitted
Occasional Mobile InstallationNot Permitted
Protected Outdoor InstallationNot Permitted

Applicable Standards

EN 50288-7 P.Q.A. – Sectional specification for instrumentation and control cables used in analogue and digital communication systems.

EN IEC 60228 / CEI 20-29 – Conductors of insulated cables.

CEI UNEL 36762 – Identification and testing of cables for category 0 systems in relation to coexistence with category I system cables.

EN 50575:2014+A1:2016 – Power, control and communication cables for construction works subject to reaction-to-fire requirements.

EN 13501-6 – Reaction-to-fire classification of electrical cables: Eca.

IEC 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.

EN IEC 61034-2 – Smoke density measurement.

EN IEC 60754-1 – Halogen acid gas content.

EN IEC 60754-2 – Acidity and conductivity of gases evolved during combustion.

EN IEC 60811-404 – Mineral oil immersion tests for sheathing compounds.

EN 60811-504 / 505 / 506 – Low-temperature mechanical tests.

ENI 181 – Hydrocarbon resistance reference specification.

Related Instrumentation Cable Types

Instrumentation Cable Families

Re-2X(St)H – XLPE-insulated instrumentation cable with overall screen and LSZH sheath.

RE-2X(St)Y – Related instrumentation cable designation with PVC outer sheath.

RE-2X(St)H PiMF – Related designation for instrumentation constructions with individual pair screening, subject to manufacturer specification.

Cable Selection

Overall screened instrumentation cables.

Individually screened pair cables.

Individually and collectively screened instrumentation cables.

Armoured instrumentation cables.

Each construction must be selected according to its specific electrical, mechanical, environmental and installation requirements.

Technical Note: Technical characteristics are based on the Specialcavi Baldassari Re-2X(St)H reference datasheet. CPR classification Eca applies to the documented reference construction. Final product dimensions, conformity documentation, availability and project-specific requirements must be confirmed during quotation. Related cable designations do not constitute declarations of technical equivalence.
Installation Warning: Outdoor and buried installations are not permitted, even when additional protection is provided. The cable is intended for fixed indoor installations only. Flame retardancy must not be interpreted as fire-resistant circuit integrity.
UNIMA CABLE | TECHNICAL DIMENSIONS

Re-2X(St)H – Cable Sizes & Technical Data

Complete reference range of overall screened LSZH instrumentation cables rated 300/500 V, including single-pair, multi-pair and single-triad configurations, approximate cable dimensions, weights, conductor resistance and minimum bending radii.

70Reference Configurations
0.50–1.50 mm²Conductor Cross-Section
6.0–31.4 mmOuter Diameter
55–1330 kg/kmApproximate Cable Weight

Complete Cable Size Range

Cable Formation (mm²) Number of Cores Construction Outer Diameter (mm) Approx. Weight (kg/km) Conductor Resistance at 20°C (Ω/km) Calculated Min. Bending Radius (mm)
0.50 mm² – Single Pair, Triad & Multi-Pair Cables
1x2x0.502Single Pair6.05536.760
1x3x0.503Single Triad6.26336.762
2x2x0.5042 Pairs9.29336.792
3x2x0.5063 Pairs9.910736.799
4x2x0.5084 Pairs10.813036.7108
5x2x0.50105 Pairs12.115836.7121
6x2x0.50126 Pairs13.318936.7133
7x2x0.50147 Pairs13.320536.7133
8x2x0.50168 Pairs14.122736.7141
10x2x0.502010 Pairs16.429036.7164
12x2x0.502412 Pairs17.232936.7172
16x2x0.503216 Pairs19.542136.7195
20x2x0.504020 Pairs21.752536.7217
24x2x0.504824 Pairs23.762236.7237
0.75 mm² – Single Pair, Triad & Multi-Pair Cables
1x2x0.752Single Pair6.46325.064
1x3x0.753Single Triad6.77525.067
2x2x0.7542 Pairs10.111825.0101
3x2x0.7563 Pairs10.613125.0106
4x2x0.7584 Pairs11.816625.0118
5x2x0.75105 Pairs13.220325.0132
6x2x0.75126 Pairs14.323325.0143
7x2x0.75147 Pairs14.325525.0143
8x2x0.75168 Pairs15.529325.0155
10x2x0.752010 Pairs17.736225.0177
12x2x0.752412 Pairs18.842725.0188
16x2x0.753216 Pairs21.555725.0215
20x2x0.754020 Pairs22.661125.0226
24x2x0.754824 Pairs23.868125.0238
1.00 mm² – Single Pair, Triad & Multi-Pair Cables
1x2x1.002Single Pair6.87318.668
1x3x1.003Single Triad7.18718.671
2x2x1.0042 Pairs10.813718.6108
3x2x1.0063 Pairs11.616218.6116
4x2x1.0084 Pairs12.920418.6129
5x2x1.00105 Pairs14.124218.6141
6x2x1.00126 Pairs15.628918.6156
7x2x1.00147 Pairs15.631718.6156
8x2x1.00168 Pairs16.836218.6168
10x2x1.002010 Pairs19.345118.6193
12x2x1.002412 Pairs20.452618.6204
16x2x1.003216 Pairs23.369118.6233
20x2x1.004020 Pairs25.884118.6258
24x2x1.004824 Pairs28.099118.6280
1.30 mm² – Single Pair, Triad & Multi-Pair Cables
1x2x1.302Single Pair7.28214.272
1x3x1.303Single Triad7.710514.277
2x2x1.3042 Pairs11.616414.2116
3x2x1.3063 Pairs12.418914.2124
4x2x1.3084 Pairs13.824014.2138
5x2x1.30105 Pairs15.329514.2153
6x2x1.30126 Pairs16.935014.2169
7x2x1.30147 Pairs16.938514.2169
8x2x1.30168 Pairs18.144214.2181
10x2x1.302010 Pairs20.754414.2207
12x2x1.302412 Pairs22.063814.2220
16x2x1.303216 Pairs25.183614.2251
20x2x1.304020 Pairs27.8102014.2278
24x2x1.304824 Pairs30.4122014.2304
1.50 mm² – Single Pair, Triad & Multi-Pair Cables
1x2x1.502Single Pair7.48712.374
1x3x1.503Single Triad7.911312.379
2x2x1.5042 Pairs12.117612.3121
3x2x1.5063 Pairs13.021112.3130
4x2x1.5084 Pairs14.225912.3142
5x2x1.50105 Pairs15.831812.3158
6x2x1.50126 Pairs17.437812.3174
7x2x1.50147 Pairs17.441712.3174
8x2x1.50168 Pairs18.747912.3187
10x2x1.502010 Pairs21.660312.3216
12x2x1.502412 Pairs22.869212.3228
16x2x1.503216 Pairs26.090812.3260
20x2x1.504020 Pairs28.8112412.3288
24x2x1.504824 Pairs31.4133012.3314

Cable diameters and weights are approximate reference values. Minimum bending radii are calculated using the specified factor of 10 times the approximate outer diameter. The actual supplied cable diameter must be used for final installation calculations.

Cable Range Summary

Conductor Cross-Section Pair Range Triad Configurations Total Configurations Outer Diameter (mm) Weight (kg/km)
0.50 mm²1–241146.0–23.755–622
0.75 mm²1–241146.4–23.863–681
1.00 mm²1–241146.8–28.073–991
1.30 mm²1–241147.2–30.482–1220
1.50 mm²1–241147.4–31.487–1330
Total Reference Configurations70

Conductor Resistance at 20°C

Nominal Conductor Cross-Section (mm²) Conductor Resistance (Ω/km) Conductor Class
0.5036.7Class 2
0.7525.0Class 2
1.0018.6Class 2
1.3014.2Class 2
1.5012.3Class 2

Electrical Characteristics

Parameter Reference Value
Nominal Voltage U0300 V
Nominal Voltage U500 V
Sheath Operating Voltage300/500 V
Maximum AC Voltage U0/U320/550 V AC
Maximum DC Voltage U0/U410/820 V DC
Core-to-Core Test Voltage2.0 kV AC, 50 Hz, 5 minutes
Core-to-Screen Test Voltage1.5 kV AC, 50 Hz, 1 minute
Minimum Insulation Resistance>200 MΩ·km
Materijal vodičaBare Copper
Conductor ClassClass 2 Stranded
Conductor StandardCEI 20-29 / EN IEC 60228
Overall ScreenAluminium/Polyester Tape
Drain Wire0.50 mm² Flexible Tinned Copper
Mutual CapacitanceNot Specified
InductanceNot Specified
Inductance-to-Resistance RatioNot Specified
Characteristic ImpedanceNot Specified
AttenuationNot Specified
Permissible Current RatingNot Specified

Temperature Characteristics

Condition Minimum Temperature Maximum Temperature
Operating Temperature-40°C+90°C
Assembly / Handling0°CNot Specified
Conductor Operating TemperatureNot Specified+90°C
Short-Circuit TemperatureNot Specified+250°C

The maximum permitted short-circuit duration is not stated in the reference datasheet.

Cable Construction Layers

Layer Component Material / Construction
1ConductorClass 2 Stranded Bare Copper
2Core InsulationCross-Linked Polyethylene (XLPE)
3Core ArrangementTwisted Pairs or Single Triad
4Multi-Pair AssemblyPairs Stranded in Concentric Layers
5Wrapping and ProtectionPolyester Tape
6Overall ScreenAluminium/Polyester Tape
7Drain WireFlexible Tinned Copper, 0.50 mm²
8Outer SheathLSZH Thermoplastic Compound
9Outer Sheath ColourBlack, Based on RAL 9005

Core Identification

Cable Formation Core Identification Construction
1x2White / BlackTwo Cores Twisted in One Pair
1x3White / Black / RedThree Cores Twisted in One Triad
2x2 to 24x2White / Black with Progressive Numbering for Each PairTwisted Pairs Stranded in Concentric Layers
Custom ConstructionAlternative Colours on RequestSubject to Manufacturer Confirmation

Mechanical & Environmental Properties

Property Standard / Reference Value Status
Oil ResistanceEN IEC 60811-404Yes
Low Temperature ResistanceEN 60811-504 + 505 + 506Yes
Hydrocarbon ResistanceENI 181Yes
UV ResistanceNot SpecifiedNot Declared
Ozone ResistanceNot SpecifiedNot Declared
Water ExposureHD 60364-5-54:2009, as ReferencedNot Declared
Impact ResistanceHD 60364-5-54:2009, as ReferencedNot Declared
Rodent ProtectionNot ProvidedNo
Minimum Bending Radius10 × Outer DiameterSpecified
Maximum Installation Tensile Load0.050 kN/mm² of Copper Conductor Cross-SectionSpecified
Cable GeometryRoundSpecified

Fire Performance & CPR Classification

Property Test Standard Reference Performance
CPR Reaction to FireEN 13501-6Eca
Construction Products StandardEN 50575:2014+A1:2016Referenced
Single-Cable Flame RetardancyIEC 60332-1-2Yes
Bunched Cable Flame Retardancy – Cat. A F/RIEC 60332-3-21Not Declared
Bunched Cable Flame Retardancy – Cat. AIEC 60332-3-22Not Declared
Bunched Cable Flame Retardancy – Cat. BIEC 60332-3-23Not Declared
Bunched Cable Flame Retardancy – Cat. CIEC 60332-3-24Not Declared
Bunched Cable Flame Retardancy – Cat. DIEC 60332-3-25Not Declared
Low SmokeEN IEC 61034-2Yes
Halogen Acid Gas ContentEN IEC 60754-1Yes
Gas Acidity and ConductivityEN IEC 60754-2Yes
Low Halogen Content TestEN IEC 60754-3Not Declared
Fire-Resistant Circuit IntegrityIEC 60331-1 / EN 50200Not Declared

The Eca reaction-to-fire classification does not include additional CPR smoke, flaming droplet or acidity subclasses. Separate LSZH test characteristics must not be interpreted as a higher CPR Euroclass.

Installation Conditions

Installation Method Suitability
Fixed InstallationPermitted
Indoor InstallationPermitted
Indoor Free-Air InstallationPermitted
Indoor Protected Installation in AirPermitted
Mobile InstallationNot Permitted
Occasional Mobile Installation Without StressNot Permitted
Outdoor InstallationNot Permitted
Protected Outdoor InstallationNot Permitted
Directly Buried InstallationNot Permitted
Buried Installation with ProtectionNot Permitted

Applicable Standards

Standard Područje primjene
EN 50288-7 P.Q.A.Instrumentation and Control Cable Sectional Specification
EN IEC 60228Conductors of Insulated Cables
CEI 20-29Insulated Cable Conductors
CEI UNEL 36762Category 0 Cable Identification and Coexistence Testing with Category I Systems
EN 50575:2014+A1:2016Construction Products Cable Requirements
EN 13501-6Electrical Cable Reaction-to-Fire Classification
IEC 60332-1-2Single-Cable Vertical Flame Propagation
EN IEC 61034-2Smoke Density Measurement
EN IEC 60754-1Halogen Acid Gas Content
EN IEC 60754-2Gas Acidity and Conductivity
EN IEC 60811-404Mineral Oil Immersion Test
EN 60811-504Low-Temperature Bending Test
EN 60811-505Low-Temperature Elongation Test
EN 60811-506Low-Temperature Impact Test
ENI 181Hydrocarbon Resistance Reference Specification

Additional Options & Project Documentation

Option / Document Reference Status
Custom Core ColoursOn Request
Custom Outer Sheath ColourOn Request
Triad Cable ConstructionOn Request / Selected Reference Configurations
CPR Declaration of PerformanceConfirm for Supplied Product
Declaration of ConformityConfirm for Supplied Product
Manufacturer Test DocumentationSubject to Project Requirements
ATEX / Intrinsically Safe Circuit SuitabilityNot Specified – Requires Separate Verification
Technical Note: All 70 cable formations listed in the Specialcavi Baldassari Re-2X(St)H reference datasheet are included. Published diameters and weights are approximate. The listed cable configurations do not constitute a declaration of stock availability.
Calculated Values: The number of insulated cores is derived from each cable formation and excludes the drain wire. Minimum bending radii are calculated as 10 times the published approximate outer diameter. The maximum installation tensile load of 0.050 kN/mm² corresponds to 50 N/mm² of copper conductor cross-section.
Installation Warning: This cable is intended for fixed indoor installations. Outdoor installation and buried installation are not permitted, even when protected. Suitability for intrinsically safe circuits, hazardous areas and specific communication protocols must be verified separately.