UNIMA CABLE | FIRE PERFORMANCE & LOW VOLTAGE POWER CABLES

N2XH FE180 – Fire-Resistant LSZH Power Cable 0.6/1 kV

Halogen-free, flame-retardant power cable with copper conductors, XLPE insulation, mica fire barrier and HFFR outer sheath, designed for electrical installations with enhanced fire safety requirements.

0.6/1 kV FE180 Copper Conductor Mica Tape XLPE Insulation HFFR LSZH Single & Multicore Fixed Installation

Product Overview

N2XH FE180 is a halogen-free, flame-retardant and fire-resistant low-voltage power cable intended for electrical energy distribution in commercial buildings, industrial facilities and infrastructure projects.

The cable incorporates solid or stranded copper conductors, a mica tape fire barrier, cross-linked polyethylene insulation and a halogen-free flame-retardant outer sheath.

The mica fire barrier is designed to provide additional electrical insulation protection under fire exposure.

The reference product range includes single-core and multicore configurations suitable for different electrical distribution requirements.

Key Technical Features

0.6/1 kVRadni napon
FE180Fire Resistance Designation
+90°CMaximum Operating Temperature
+250°CMaximum Short-Circuit Temperature
CuCopper Conductor
XLPECore Insulation
MicaFire Barrier
HFFROuter Sheath

Cable Construction & Technical Properties

Cable Construction

Conductor materialCopper
Conductor constructionSolid or stranded
Fire barrierMica tape
Core insulationXLPE
FillerHFFR compound, where applicable
Outer sheathHFFR compound
Reference sheath colourOrange
Cable configurationsSingle-core and multicore

Electrical & Thermal Properties

Rated voltage0.6/1 kV
Maximum operating temperature+90°C
Maximum short-circuit temperature+250°C
Fire resistance designationFE180
Conductor resistanceSize-dependent
Current-carrying capacitySize and installation dependent
CPR classificationSubject to applicable DoP
Installation typeFixed installation

Fire-Resistant Cable Construction

The fire-resistant cable design combines copper conductors with a mica tape barrier and XLPE insulation.

The mica layer provides additional protection of the electrical insulation when exposed to elevated temperatures during a fire.

The FE180 designation refers to insulation integrity under specified fire test conditions. The applicable test standard and certified performance must be confirmed using the corresponding manufacturer documentation.

Halogen-Free Flame-Retardant Materials

XLPE Insulation

Cross-linked polyethylene insulation provides electrical insulation and thermal performance for low-voltage power distribution.

The reference maximum operating temperature is +90°C.

HFFR Outer Sheath

Halogen-free flame-retardant materials are used for the outer sheath and applicable filler layers.

The cable construction is intended for installations where fire behaviour and smoke characteristics are important selection criteria.

Typical Project Applications

Commercial buildings
Industrijski pogoni
Hospitals and healthcare facilities
Hotels and public buildings
Data centre power distribution
Transport infrastructure
Shopping centres
High-rise buildings
Emergency power distribution
Safety-related electrical installations
Power generation facilities
Electrical distribution networks

Installation & Engineering Considerations

Cable selection must consider the rated voltage, conductor cross-section, installation method, ambient temperature, grouping conditions and required fire performance.

Applications involving emergency lighting, fire alarm systems, smoke extraction equipment and other safety-related circuits require verification of the applicable system-level fire resistance requirements.

Current-carrying capacities, bending radii, pulling forces and installation temperatures must be confirmed for the selected cable configuration.

Fire Performance & Certification

FE180Fire resistance designation
Flame retardancyHalogen-free flame-retardant construction
CPR reaction to fireAccording to applicable Declaration of Performance
E30 / E60 / E90Requires separate system-level certification
Fire test documentationSubject to selected manufacturer and configuration
Important Technical Note: FE180 insulation integrity, CPR reaction-to-fire classification and E30/E60/E90 functional integrity are different performance characteristics. FE180 designation alone does not establish an E90 installation system or a specific CPR classification. All project-specific requirements must be verified before ordering.
UNIMA CABLE | TECHNICAL DATA & DIMENSIONS

N2XH FE180 – Cable Sizes & Technical Data

Fire-resistant, halogen-free, XLPE-insulated copper power cables with mica fire barrier and HFFR outer sheath for low-voltage electrical distribution systems.

0.6/1 kVRadni napon
FE180Fire Resistance Designation
90°CMaximum Operating Temperature
250°CShort-Circuit Temperature
1–5Number of Cores
CuMaterijal vodiča
XLPEIzolacijski materijal
HFFROuter Sheath Material

Single-Core Cable Sizes

Reference single-core cable configurations. Detailed dimensional and electrical values are subject to manufacturer confirmation.

Cable Size Number of Cores Nominal Cross-Section (mm²) Materijal vodiča Radni napon
Single-Core Power Cables
1 × 414Cu0.6/1 kV
1 × 616Cu0.6/1 kV
1 × 10110Cu0.6/1 kV
1 × 16116Cu0.6/1 kV
1 × 25125Cu0.6/1 kV
1 × 35135Cu0.6/1 kV
1 × 50150Cu0.6/1 kV
1 × 70170Cu0.6/1 kV
1 × 95195Cu0.6/1 kV
1 × 1201120Cu0.6/1 kV
1 × 1501150Cu0.6/1 kV
1 × 1851185Cu0.6/1 kV
1 × 2401240Cu0.6/1 kV
1 × 3001300Cu0.6/1 kV
1 × 4001400Cu0.6/1 kV
1 × 5001500Cu0.6/1 kV

Multicore Cable Configurations

Configuration Number of Cores Materijal vodiča Insulation Outer Sheath
Two-core2CopperXLPEHFFR
Three-core3CopperXLPEHFFR
Four-core4CopperXLPEHFFR
Five-core5CopperXLPEHFFR
Reduced additional conductorConfiguration dependentCopperXLPEHFFR

Electrical Characteristics

ParameterTechnical Specification
Rated Voltage U0/U0.6/1 kV
Materijal vodičaCopper
Conductor ConstructionSolid or stranded
Core InsulationCross-linked polyethylene (XLPE)
Fire BarrierMica tape
DC Conductor Resistance at 20°CConfiguration-specific value
AC Conductor ResistanceConfiguration-specific value
Current-Carrying CapacityAccording to cable size and installation conditions
Voltage DropAccording to cable configuration and electrical load

Cable Construction Layers

LayerMaterialFunction
1. ConductorSolid or stranded copperElectrical energy transmission
2. Fire BarrierMica tapeAdditional insulation protection under fire exposure
3. Core InsulationXLPEElectrical insulation
4. FillerHFFR compoundMulticore cable assembly, where applicable
5. Outer SheathHFFR compoundExternal cable protection

Thermal Characteristics

ParameterReference Value
Maximum Continuous Operating Temperature+90°C
Maximum Short-Circuit Temperature+250°C
Minimum Installation TemperatureSubject to manufacturer specification
Ambient Temperature CorrectionAccording to installation calculation

Mechanical & Dimensional Characteristics

ParameterTechnical Specification
Outer Sheath ColourOrange reference construction
Overall Cable DiameterConfiguration dependent
Net Cable WeightConfiguration dependent
Minimum Bending RadiusSubject to manufacturer specification
Maximum Pulling ForceSubject to manufacturer specification
Standard Delivery LengthAccording to selected cable configuration
PakiranjeAccording to order requirements

Fire Performance & Certification

CharacteristicPerformance
Fire Resistance DesignationFE180
Fire BarrierMica tape
Halogen-Free ConstructionHFFR materials
Flame RetardancyAccording to applicable test documentation
CPR ClassificationAccording to applicable Declaration of Performance
Functional Integrity E30/E60/E90Separate system certification required
Fire Resistance Test StandardSubject to manufacturer test documentation

Technical Documentation

DocumentDescription
TDSTehnički list
DoPDeclaration of Performance, where applicable
DoCDeclaration of Conformity, where applicable
Fire Test ReportVerification of declared fire resistance performance
CoCPCertificate of Constancy of Performance, where applicable
Technical Data: Detailed cable diameters, conductor resistance, current-carrying capacities, voltage drop values, cable weights and copper calculation factors must be confirmed for the selected cable configuration.
Fire Performance: FE180 insulation integrity must not be interpreted as automatic compliance with E30, E60 or E90 functional integrity requirements. CPR reaction-to-fire classification must be verified separately.
Availability: Cable configurations listed on this page are reference product configurations and do not constitute confirmation of stock availability. Delivery lengths, packaging and technical documentation are subject to order confirmation.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ