(N)A2XS(F)2Y Aluminium XLPE Medium Voltage Cable
(N)A2XS(F)2Y is a single-core medium-voltage power cable with a Class 2 circular compacted aluminium conductor, XLPE insulation, a copper wire and tape screen, longitudinal water-blocking layers and a black polyethylene (PE) outer sheath.
Designed for fixed medium-voltage power distribution in underground networks, cable ducts, substations, power infrastructure and industrial installations. The swellable water-blocking tapes help limit longitudinal water propagation within the cable.
Construction
AL / XLPE / CWS + CWT / WATER-BLOCKING / PE
Circular compacted aluminium conductor, Class 2 according to IEC 60228
Extruded semiconductive conductor screen
Cross-linked polyethylene (XLPE)
Extruded semiconductive insulation screen, bonded construction
Semiconductive swellable tape providing longitudinal water-blocking protection
Copper wires and copper tape. Screen cross-section depends on cable size.
Non-conductive swellable tape beneath the outer sheath
Black polyethylene (PE), ST7 according to IEC 60502-2
Technical Data
Electrical and thermal characteristics
1×185/25 mm² – Technical Reference
Confirmed 20.3/35 (42) kV construction
Standardi
Referenced technical specifications
Primjene
Medium-voltage energy distribution
Dimensions & Technical Data
Standard single-core cable configurations with nominal dimensions, weights, conductor resistance and current carrying capacity.
Single Core
NA2XS2Y · Aluminium conductor · Copper wire screen
| Cross Section mm² |
Overall Ø mm |
Net Weight kg/km |
Dostava m |
Resistance 20°C Ω/km |
Resistance 90°C Ω/km |
Inductance mH/km |
Capacitance µF/km |
Ground Flat A |
Ground Trefoil A |
Air Flat A |
Air Trefoil A |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1×35/16 | 37.5 | 1000 | 1000 | 0.868 | 1.1110 | 0.690 | 0.115 | – | – | – | – |
| 1×50/16 | 38.5 | 1100 | 1000 | 0.641 | 0.8205 | 0.664 | 0.125 | 196 | 175 | 217 | 187 |
| 1×70/16 | 40.5 | 1250 | 1000 | 0.443 | 0.5670 | 0.633 | 0.140 | 238 | 214 | 270 | 232 |
| 1×95/16 | 42.0 | 1400 | 1000 | 0.320 | 0.4096 | 0.609 | 0.153 | 284 | 256 | 328 | 281 |
| 1×120/16 | 44.0 | 1500 | 1000 | 0.253 | 0.3238 | 0.590 | 0.165 | 322 | 290 | 378 | 323 |
| 1×150/25 | 45.5 | 1750 | 1000 | 0.206 | 0.2637 | 0.572 | 0.178 | 355 | 324 | 425 | 365 |
| 1×185/25 | 47.5 | 1950 | 1000 | 0.164 | 0.2099 | 0.556 | 0.191 | 400 | 366 | 485 | 418 |
| 1×240/25 | 50.0 | 2200 | 1000 | 0.125 | 0.1600 | 0.535 | 0.209 | 461 | 426 | 572 | 494 |
| 1×300/25 | 52.5 | 2450 | 1000 | 0.100 | 0.1280 | 0.519 | 0.226 | 516 | 479 | 649 | 564 |
| 1×400/35 | 55.5 | 2950 | 1000 | 0.0778 | 0.1009 | 0.497 | 0.252 | 572 | 545 | 737 | 654 |
| 1×500/35 | 59.0 | 3400 | 1000 | 0.0605 | 0.0774 | 0.481 | 0.274 | 638 | 614 | 835 | 747 |
| 1×630/35 | 62.5 | 3900 | 1000 | 0.0469 | 0.0600 | 0.464 | 0.300 | 728 | 690 | 950 | 851 |
Available Cable Dimensions
Aluminium conductor · XLPE insulation · Copper wire and tape screen · Longitudinal water blocking · PE sheath
| Cable Size | Conductor | Resistance 20°C Ω/km |
Outer Diameter mm |
Aluminium kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|
| 1×185/25 | RM, Class 2 | 0.164 | 46.0 | 478 | 1845 |
Technical values for 1×185/25 mm² are based on the confirmed 20.3/35 (42) kV specification. Other dimensions and values are subject to confirmation for the selected manufacturing variant.