(N)HXH-J / (N)HXH-O FE180/E90
(N)HXH FE180/E90 is a halogen-free, fire-resistant power cable rated 0.6/1 kV, designed for fixed electrical installations in buildings with elevated fire safety requirements.
The cable provides FE180 fire resistance and E90 circuit integrity in appropriately tested installation systems. Its flame-retardant, low-smoke and halogen-free construction helps reduce smoke and corrosive gas emissions during a fire.
Available as (N)HXH-J with a protective conductor and (N)HXH-O without a protective conductor.
Construction
Copper Conductor
Bare copper conductor, Class 1 solid (RE); from 25 mm², Class 2 stranded (RM).
Core Insulation
Fire-resistant, halogen-free FRNC insulation compound, type HI1.
Core Identification
Core colours according to HD 308 / VDE 0293. The J version includes a green-yellow protective conductor; the O version has no protective conductor.
Outer Sheath
Flame-retardant, halogen-free FRNC compound, type HM1, with orange outer sheath.
Technical Characteristics
| Product designation | (N)HXH-J / (N)HXH-O FE180/E90 |
|---|---|
| Rated voltage U₀/U | 0.6/1 kV |
| Maximum operating voltage | 1.2 kV (three-phase systems) |
| Test voltage | 4 kV |
| Product standard | VDE 0266 |
| Conductor | Bare copper, Class 1 / Class 2 |
| Insulation | FRNC compound HI1 |
| Outer sheath | FRNC compound HM1 |
| Sheath colour | Orange |
| Maximum conductor temperature | +90°C |
| Fixed installation temperature | -30°C to +90°C |
| Minimum temperature during movement | -5°C |
| Minimum bending radius, multicore | 12 × outer diameter |
| Minimum bending radius, single-core | 15 × outer diameter |
| Fire resistance | FE180 |
| Circuit integrity | E90, with tested installation systems |
| CPR classification | According to the applicable Declaration of Performance (DoP) |
Typical Applications
Fire Performance & Standards
Technical Data & Cable Dimensions
(N)HXH-J / (N)HXH-O FE180/E90 | 0.6/1 kV | VDE 0266
| Cross-Section (mm²) |
Conductor Class |
Resistance (Ω/km) |
Current (A) |
Bending Radius (mm) |
Outer Ø (mm) |
Copper (kg/km) |
Cable Weight (kg/km) |
|---|
Resistance values refer to conductors at 20°C. Current ratings are specified for air at 30°C. Outer diameters are approximate. Copper and cable weights are expressed in kg/km. A dash indicates data not specified in the manufacturer's table.
Fire safety: E90 circuit integrity requires an appropriately tested installation system. Verify project-specific certificates and the applicable Declaration of Performance before installation.