Re-2X(St)H – LSZH Screened Instrumentation Cable 300/500 V
Overall screened multi-pair instrumentation and data transmission cable with stranded copper conductors, XLPE insulation, aluminium/polyester tape screening, tinned copper drain wire and a low-smoke halogen-free outer sheath. Designed for fixed indoor installations in demanding industrial environments.
Product Overview
Re-2X(St)H is an overall screened instrumentation, control and data transmission cable designed for analogue and digital communication systems in industrial electrical installations.
The cable incorporates Class 2 stranded bare copper conductors insulated with cross-linked polyethylene (XLPE). The insulated conductors are twisted into pairs or selected triad configurations.
In multi-pair constructions, the twisted pairs are assembled in concentric layers. An overall aluminium/polyester tape screen with a flexible tinned copper drain wire provides electromagnetic screening for the complete cable assembly.
The outer sheath is manufactured from a low-smoke zero-halogen thermoplastic compound, with a standard black colour based on RAL 9005.
The reference cable construction is particularly suitable for demanding indoor industrial environments, including refineries, chemical plants and process instrumentation installations.
The reference range includes 70 cable configurations covering conductor cross-sections of 0.50, 0.75, 1.00, 1.30 and 1.50 mm², including single-pair, multi-pair and single-triad constructions.
Key Technical Features
Cable Construction & Technical Properties
Cable Construction
Electrical & Mechanical Properties
Twisted Pair & Triad Construction
Single-Pair Construction
Two XLPE-insulated conductors twisted together to form one signal transmission pair.
Core identification: White and black.
Reference sizes: 1x2x0.50, 1x2x0.75, 1x2x1.00, 1x2x1.30 and 1x2x1.50 mm².
Multi-Pair Construction
Multiple twisted pairs assembled in concentric layers under a common aluminium/polyester tape screen.
Core identification: White and black with progressive numbering for each pair.
Pair configurations: 2, 3, 4, 5, 6, 7, 8, 10, 12, 16, 20 and 24 pairs.
Single-Triad Construction
Three insulated conductors twisted together to form one triad for instrumentation circuits requiring three conductors.
Core identification: White, black and red.
Reference sizes: 1x3x0.50 to 1x3x1.50 mm².
Custom Cable Construction
Alternative core identification and outer sheath colours are available on request according to the reference documentation.
Triad cable constructions can also be requested, subject to technical and commercial confirmation.
Overall Electromagnetic Screening
Aluminium/Polyester Tape Screen
The complete cable assembly is protected by an overall aluminium/polyester tape screen.
The screen helps reduce external electromagnetic interference affecting instrumentation, control and signal transmission circuits.
This construction uses a common overall screen rather than individually screened pairs.
Tinned Copper Drain Wire
A flexible tinned copper drain wire with a nominal cross-section of 0.50 mm² is incorporated into the screening system.
The drain wire facilitates electrical connection of the screen during cable termination.
Screen bonding and earthing must follow the requirements of the instrumentation system and electrical installation design.
LSZH & Fire Performance
CPR Reaction to Fire – Eca
The reference product is classified as Eca according to EN 13501-6 and EN 50575:2014+A1:2016.
Single-cable flame propagation performance is specified according to IEC 60332-1-2.
The cable is not declared fire resistant and must not be used as a substitute for a certified circuit-integrity cable.
Low Smoke & Halogen-Free Properties
The LSZH thermoplastic sheath provides low-smoke and halogen-free characteristics according to the specified reference tests.
Smoke density: EN IEC 61034-2.
Halogen acid gas: EN IEC 60754-1.
Gas acidity and conductivity: EN IEC 60754-2.
Industrial Environmental Resistance
Specified Resistance Properties
Application Limitations
Typical Applications
Installation Conditions
Permitted Installation Methods
Prohibited Installation Methods
Applicable Standards
EN 50288-7 P.Q.A. – Sectional specification for instrumentation and control cables used in analogue and digital communication systems.
EN IEC 60228 / CEI 20-29 – Conductors of insulated cables.
CEI UNEL 36762 – Identification and testing of cables for category 0 systems in relation to coexistence with category I system cables.
EN 50575:2014+A1:2016 – Power, control and communication cables for construction works subject to reaction-to-fire requirements.
EN 13501-6 – Reaction-to-fire classification of electrical cables: Eca.
IEC 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.
EN IEC 61034-2 – Smoke density measurement.
EN IEC 60754-1 – Halogen acid gas content.
EN IEC 60754-2 – Acidity and conductivity of gases evolved during combustion.
EN IEC 60811-404 – Mineral oil immersion tests for sheathing compounds.
EN 60811-504 / 505 / 506 – Low-temperature mechanical tests.
ENI 181 – Hydrocarbon resistance reference specification.
Related Instrumentation Cable Types
Instrumentation Cable Families
Re-2X(St)H – XLPE-insulated instrumentation cable with overall screen and LSZH sheath.
RE-2X(St)Y – Related instrumentation cable designation with PVC outer sheath.
RE-2X(St)H PiMF – Related designation for instrumentation constructions with individual pair screening, subject to manufacturer specification.
Cable Selection
Overall screened instrumentation cables.
Individually screened pair cables.
Individually and collectively screened instrumentation cables.
Armoured instrumentation cables.
Each construction must be selected according to its specific electrical, mechanical, environmental and installation requirements.
Re-2X(St)H – Cable Sizes & Technical Data
Complete reference range of overall screened LSZH instrumentation cables rated 300/500 V, including single-pair, multi-pair and single-triad configurations, approximate cable dimensions, weights, conductor resistance and minimum bending radii.
Complete Cable Size Range
| Cable Formation (mm²) | Number of Cores | Construction | Outer Diameter (mm) | Approx. Weight (kg/km) | Conductor Resistance at 20°C (Ω/km) | Calculated Min. Bending Radius (mm) |
|---|---|---|---|---|---|---|
| 0.50 mm² – Single Pair, Triad & Multi-Pair Cables | ||||||
| 1x2x0.50 | 2 | Single Pair | 6.0 | 55 | 36.7 | 60 |
| 1x3x0.50 | 3 | Single Triad | 6.2 | 63 | 36.7 | 62 |
| 2x2x0.50 | 4 | 2 Pairs | 9.2 | 93 | 36.7 | 92 |
| 3x2x0.50 | 6 | 3 Pairs | 9.9 | 107 | 36.7 | 99 |
| 4x2x0.50 | 8 | 4 Pairs | 10.8 | 130 | 36.7 | 108 |
| 5x2x0.50 | 10 | 5 Pairs | 12.1 | 158 | 36.7 | 121 |
| 6x2x0.50 | 12 | 6 Pairs | 13.3 | 189 | 36.7 | 133 |
| 7x2x0.50 | 14 | 7 Pairs | 13.3 | 205 | 36.7 | 133 |
| 8x2x0.50 | 16 | 8 Pairs | 14.1 | 227 | 36.7 | 141 |
| 10x2x0.50 | 20 | 10 Pairs | 16.4 | 290 | 36.7 | 164 |
| 12x2x0.50 | 24 | 12 Pairs | 17.2 | 329 | 36.7 | 172 |
| 16x2x0.50 | 32 | 16 Pairs | 19.5 | 421 | 36.7 | 195 |
| 20x2x0.50 | 40 | 20 Pairs | 21.7 | 525 | 36.7 | 217 |
| 24x2x0.50 | 48 | 24 Pairs | 23.7 | 622 | 36.7 | 237 |
| 0.75 mm² – Single Pair, Triad & Multi-Pair Cables | ||||||
| 1x2x0.75 | 2 | Single Pair | 6.4 | 63 | 25.0 | 64 |
| 1x3x0.75 | 3 | Single Triad | 6.7 | 75 | 25.0 | 67 |
| 2x2x0.75 | 4 | 2 Pairs | 10.1 | 118 | 25.0 | 101 |
| 3x2x0.75 | 6 | 3 Pairs | 10.6 | 131 | 25.0 | 106 |
| 4x2x0.75 | 8 | 4 Pairs | 11.8 | 166 | 25.0 | 118 |
| 5x2x0.75 | 10 | 5 Pairs | 13.2 | 203 | 25.0 | 132 |
| 6x2x0.75 | 12 | 6 Pairs | 14.3 | 233 | 25.0 | 143 |
| 7x2x0.75 | 14 | 7 Pairs | 14.3 | 255 | 25.0 | 143 |
| 8x2x0.75 | 16 | 8 Pairs | 15.5 | 293 | 25.0 | 155 |
| 10x2x0.75 | 20 | 10 Pairs | 17.7 | 362 | 25.0 | 177 |
| 12x2x0.75 | 24 | 12 Pairs | 18.8 | 427 | 25.0 | 188 |
| 16x2x0.75 | 32 | 16 Pairs | 21.5 | 557 | 25.0 | 215 |
| 20x2x0.75 | 40 | 20 Pairs | 22.6 | 611 | 25.0 | 226 |
| 24x2x0.75 | 48 | 24 Pairs | 23.8 | 681 | 25.0 | 238 |
| 1.00 mm² – Single Pair, Triad & Multi-Pair Cables | ||||||
| 1x2x1.00 | 2 | Single Pair | 6.8 | 73 | 18.6 | 68 |
| 1x3x1.00 | 3 | Single Triad | 7.1 | 87 | 18.6 | 71 |
| 2x2x1.00 | 4 | 2 Pairs | 10.8 | 137 | 18.6 | 108 |
| 3x2x1.00 | 6 | 3 Pairs | 11.6 | 162 | 18.6 | 116 |
| 4x2x1.00 | 8 | 4 Pairs | 12.9 | 204 | 18.6 | 129 |
| 5x2x1.00 | 10 | 5 Pairs | 14.1 | 242 | 18.6 | 141 |
| 6x2x1.00 | 12 | 6 Pairs | 15.6 | 289 | 18.6 | 156 |
| 7x2x1.00 | 14 | 7 Pairs | 15.6 | 317 | 18.6 | 156 |
| 8x2x1.00 | 16 | 8 Pairs | 16.8 | 362 | 18.6 | 168 |
| 10x2x1.00 | 20 | 10 Pairs | 19.3 | 451 | 18.6 | 193 |
| 12x2x1.00 | 24 | 12 Pairs | 20.4 | 526 | 18.6 | 204 |
| 16x2x1.00 | 32 | 16 Pairs | 23.3 | 691 | 18.6 | 233 |
| 20x2x1.00 | 40 | 20 Pairs | 25.8 | 841 | 18.6 | 258 |
| 24x2x1.00 | 48 | 24 Pairs | 28.0 | 991 | 18.6 | 280 |
| 1.30 mm² – Single Pair, Triad & Multi-Pair Cables | ||||||
| 1x2x1.30 | 2 | Single Pair | 7.2 | 82 | 14.2 | 72 |
| 1x3x1.30 | 3 | Single Triad | 7.7 | 105 | 14.2 | 77 |
| 2x2x1.30 | 4 | 2 Pairs | 11.6 | 164 | 14.2 | 116 |
| 3x2x1.30 | 6 | 3 Pairs | 12.4 | 189 | 14.2 | 124 |
| 4x2x1.30 | 8 | 4 Pairs | 13.8 | 240 | 14.2 | 138 |
| 5x2x1.30 | 10 | 5 Pairs | 15.3 | 295 | 14.2 | 153 |
| 6x2x1.30 | 12 | 6 Pairs | 16.9 | 350 | 14.2 | 169 |
| 7x2x1.30 | 14 | 7 Pairs | 16.9 | 385 | 14.2 | 169 |
| 8x2x1.30 | 16 | 8 Pairs | 18.1 | 442 | 14.2 | 181 |
| 10x2x1.30 | 20 | 10 Pairs | 20.7 | 544 | 14.2 | 207 |
| 12x2x1.30 | 24 | 12 Pairs | 22.0 | 638 | 14.2 | 220 |
| 16x2x1.30 | 32 | 16 Pairs | 25.1 | 836 | 14.2 | 251 |
| 20x2x1.30 | 40 | 20 Pairs | 27.8 | 1020 | 14.2 | 278 |
| 24x2x1.30 | 48 | 24 Pairs | 30.4 | 1220 | 14.2 | 304 |
| 1.50 mm² – Single Pair, Triad & Multi-Pair Cables | ||||||
| 1x2x1.50 | 2 | Single Pair | 7.4 | 87 | 12.3 | 74 |
| 1x3x1.50 | 3 | Single Triad | 7.9 | 113 | 12.3 | 79 |
| 2x2x1.50 | 4 | 2 Pairs | 12.1 | 176 | 12.3 | 121 |
| 3x2x1.50 | 6 | 3 Pairs | 13.0 | 211 | 12.3 | 130 |
| 4x2x1.50 | 8 | 4 Pairs | 14.2 | 259 | 12.3 | 142 |
| 5x2x1.50 | 10 | 5 Pairs | 15.8 | 318 | 12.3 | 158 |
| 6x2x1.50 | 12 | 6 Pairs | 17.4 | 378 | 12.3 | 174 |
| 7x2x1.50 | 14 | 7 Pairs | 17.4 | 417 | 12.3 | 174 |
| 8x2x1.50 | 16 | 8 Pairs | 18.7 | 479 | 12.3 | 187 |
| 10x2x1.50 | 20 | 10 Pairs | 21.6 | 603 | 12.3 | 216 |
| 12x2x1.50 | 24 | 12 Pairs | 22.8 | 692 | 12.3 | 228 |
| 16x2x1.50 | 32 | 16 Pairs | 26.0 | 908 | 12.3 | 260 |
| 20x2x1.50 | 40 | 20 Pairs | 28.8 | 1124 | 12.3 | 288 |
| 24x2x1.50 | 48 | 24 Pairs | 31.4 | 1330 | 12.3 | 314 |
Cable diameters and weights are approximate reference values. Minimum bending radii are calculated using the specified factor of 10 times the approximate outer diameter. The actual supplied cable diameter must be used for final installation calculations.
Cable Range Summary
| Conductor Cross-Section | Pair Range | Triad Configurations | Total Configurations | Outer Diameter (mm) | Weight (kg/km) |
|---|---|---|---|---|---|
| 0.50 mm² | 1–24 | 1 | 14 | 6.0–23.7 | 55–622 |
| 0.75 mm² | 1–24 | 1 | 14 | 6.4–23.8 | 63–681 |
| 1.00 mm² | 1–24 | 1 | 14 | 6.8–28.0 | 73–991 |
| 1.30 mm² | 1–24 | 1 | 14 | 7.2–30.4 | 82–1220 |
| 1.50 mm² | 1–24 | 1 | 14 | 7.4–31.4 | 87–1330 |
| Total Reference Configurations | 70 | ||||
Conductor Resistance at 20°C
| Nominal Conductor Cross-Section (mm²) | Conductor Resistance (Ω/km) | Conductor Class |
|---|---|---|
| 0.50 | 36.7 | Class 2 |
| 0.75 | 25.0 | Class 2 |
| 1.00 | 18.6 | Class 2 |
| 1.30 | 14.2 | Class 2 |
| 1.50 | 12.3 | Class 2 |
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Nominal Voltage U0 | 300 V |
| Nominal Voltage U | 500 V |
| Sheath Operating Voltage | 300/500 V |
| Maximum AC Voltage U0/U | 320/550 V AC |
| Maximum DC Voltage U0/U | 410/820 V DC |
| Core-to-Core Test Voltage | 2.0 kV AC, 50 Hz, 5 minutes |
| Core-to-Screen Test Voltage | 1.5 kV AC, 50 Hz, 1 minute |
| Minimum Insulation Resistance | >200 MΩ·km |
| Conductor Material | Bare Copper |
| Conductor Class | Class 2 Stranded |
| Conductor Standard | CEI 20-29 / EN IEC 60228 |
| Overall Screen | Aluminium/Polyester Tape |
| Drain Wire | 0.50 mm² Flexible Tinned Copper |
| Mutual Capacitance | Not Specified |
| Inductance | Not Specified |
| Inductance-to-Resistance Ratio | Not Specified |
| Characteristic Impedance | Not Specified |
| Attenuation | Not Specified |
| Permissible Current Rating | Not Specified |
Temperature Characteristics
| Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| Operating Temperature | -40°C | +90°C |
| Assembly / Handling | 0°C | Not Specified |
| Conductor Operating Temperature | Not Specified | +90°C |
| Short-Circuit Temperature | Not Specified | +250°C |
The maximum permitted short-circuit duration is not stated in the reference datasheet.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Class 2 Stranded Bare Copper |
| 2 | Core Insulation | Cross-Linked Polyethylene (XLPE) |
| 3 | Core Arrangement | Twisted Pairs or Single Triad |
| 4 | Multi-Pair Assembly | Pairs Stranded in Concentric Layers |
| 5 | Wrapping and Protection | Polyester Tape |
| 6 | Overall Screen | Aluminium/Polyester Tape |
| 7 | Drain Wire | Flexible Tinned Copper, 0.50 mm² |
| 8 | Outer Sheath | LSZH Thermoplastic Compound |
| 9 | Outer Sheath Colour | Black, Based on RAL 9005 |
Core Identification
| Cable Formation | Core Identification | Construction |
|---|---|---|
| 1x2 | White / Black | Two Cores Twisted in One Pair |
| 1x3 | White / Black / Red | Three Cores Twisted in One Triad |
| 2x2 to 24x2 | White / Black with Progressive Numbering for Each Pair | Twisted Pairs Stranded in Concentric Layers |
| Custom Construction | Alternative Colours on Request | Subject to Manufacturer Confirmation |
Mechanical & Environmental Properties
| Property | Standard / Reference Value | Status |
|---|---|---|
| Oil Resistance | EN IEC 60811-404 | Yes |
| Low Temperature Resistance | EN 60811-504 + 505 + 506 | Yes |
| Hydrocarbon Resistance | ENI 181 | Yes |
| UV Resistance | Not Specified | Not Declared |
| Ozone Resistance | Not Specified | Not Declared |
| Water Exposure | HD 60364-5-54:2009, as Referenced | Not Declared |
| Impact Resistance | HD 60364-5-54:2009, as Referenced | Not Declared |
| Rodent Protection | Not Provided | No |
| Minimum Bending Radius | 10 × Outer Diameter | Specified |
| Maximum Installation Tensile Load | 0.050 kN/mm² of Copper Conductor Cross-Section | Specified |
| Cable Geometry | Round | Specified |
Fire Performance & CPR Classification
| Property | Test Standard | Reference Performance |
|---|---|---|
| CPR Reaction to Fire | EN 13501-6 | Eca |
| Construction Products Standard | EN 50575:2014+A1:2016 | Referenced |
| Single-Cable Flame Retardancy | IEC 60332-1-2 | Yes |
| Bunched Cable Flame Retardancy – Cat. A F/R | IEC 60332-3-21 | Not Declared |
| Bunched Cable Flame Retardancy – Cat. A | IEC 60332-3-22 | Not Declared |
| Bunched Cable Flame Retardancy – Cat. B | IEC 60332-3-23 | Not Declared |
| Bunched Cable Flame Retardancy – Cat. C | IEC 60332-3-24 | Not Declared |
| Bunched Cable Flame Retardancy – Cat. D | IEC 60332-3-25 | Not Declared |
| Low Smoke | EN IEC 61034-2 | Yes |
| Halogen Acid Gas Content | EN IEC 60754-1 | Yes |
| Gas Acidity and Conductivity | EN IEC 60754-2 | Yes |
| Low Halogen Content Test | EN IEC 60754-3 | Not Declared |
| Fire-Resistant Circuit Integrity | IEC 60331-1 / EN 50200 | Not Declared |
The Eca reaction-to-fire classification does not include additional CPR smoke, flaming droplet or acidity subclasses. Separate LSZH test characteristics must not be interpreted as a higher CPR Euroclass.
Installation Conditions
| Installation Method | Suitability |
|---|---|
| Fixed Installation | Permitted |
| Indoor Installation | Permitted |
| Indoor Free-Air Installation | Permitted |
| Indoor Protected Installation in Air | Permitted |
| Mobile Installation | Not Permitted |
| Occasional Mobile Installation Without Stress | Not Permitted |
| Outdoor Installation | Not Permitted |
| Protected Outdoor Installation | Not Permitted |
| Directly Buried Installation | Not Permitted |
| Buried Installation with Protection | Not Permitted |
Applicable Standards
| Standard | Application |
|---|---|
| EN 50288-7 P.Q.A. | Instrumentation and Control Cable Sectional Specification |
| EN IEC 60228 | Conductors of Insulated Cables |
| CEI 20-29 | Insulated Cable Conductors |
| CEI UNEL 36762 | Category 0 Cable Identification and Coexistence Testing with Category I Systems |
| EN 50575:2014+A1:2016 | Construction Products Cable Requirements |
| EN 13501-6 | Electrical Cable Reaction-to-Fire Classification |
| IEC 60332-1-2 | Single-Cable Vertical Flame Propagation |
| EN IEC 61034-2 | Smoke Density Measurement |
| EN IEC 60754-1 | Halogen Acid Gas Content |
| EN IEC 60754-2 | Gas Acidity and Conductivity |
| EN IEC 60811-404 | Mineral Oil Immersion Test |
| EN 60811-504 | Low-Temperature Bending Test |
| EN 60811-505 | Low-Temperature Elongation Test |
| EN 60811-506 | Low-Temperature Impact Test |
| ENI 181 | Hydrocarbon Resistance Reference Specification |
Additional Options & Project Documentation
| Option / Document | Reference Status |
|---|---|
| Custom Core Colours | On Request |
| Custom Outer Sheath Colour | On Request |
| Triad Cable Construction | On Request / Selected Reference Configurations |
| CPR Declaration of Performance | Confirm for Supplied Product |
| Declaration of Conformity | Confirm for Supplied Product |
| Manufacturer Test Documentation | Subject to Project Requirements |
| ATEX / Intrinsically Safe Circuit Suitability | Not Specified – Requires Separate Verification |