Find Your Cable

Select a cable or enter another designation.


UNIMA CABLE | LOW VOLTAGE POWER CABLES

NAY2Y 0.6/1 kV – Aluminium Power Cable

PVC insulated aluminium power cable with a black polyethylene (PE DMP2) outer sheath, designed for fixed low-voltage power distribution indoors, outdoors, underground, in water and in concrete.

0.6/1 kV Aluminium PVC Insulation PE DMP2 Sheath UV Resistant NAY2Y-J / NAY2Y-O

Product Overview

NAY2Y 0.6/1 kV is a low-voltage power cable with aluminium conductors, PVC insulation and a black polyethylene DMP2 outer sheath.

The cable is designed for fixed installation indoors, outdoors, directly in the ground, in water and in concrete. Its outer sheath provides UV resistance for outdoor use.

Two configurations are covered: NAY2Y-J, with a protective conductor, and NAY2Y-O, without a protective conductor.

Key Technical Features

0.6/1 kV Rated Voltage
Al Conductor Material
+70°C Max. Conductor Temp.
PE DMP2 Outer Sheath

Construction & Technical Properties

Cable Construction

Conductor Aluminium
Insulation PVC
Outer Sheath Polyethylene DMP2
Sheath Colour Black
Core Identification VDE 0293 / HD 308
Configurations NAY2Y-J / NAY2Y-O
Meter Marking Yes

Electrical & Mechanical Data

Rated Voltage 0.6/1 kV
Max. System Voltage 1.2 kV
Test Voltage 4 kV
Max. Conductor Temp. +70°C
Moved Temp. Range -20°C to +70°C
Bending Radius, Multicore 12 × D
Bending Radius, Single-Core 15 × D
UV Resistance Yes
Flame Retardance No

Typical Applications

Low-Voltage Power Distribution
Fixed Indoor Installations
Outdoor Electrical Installations
Underground Cable Installation
Installation in Water
Installation in Concrete

Applicable Standards

VDE 0276-603 – Power cable construction standard.
VDE 0293 / HD 308 – Core identification.
Technical Note: NAY2Y is not classified as flame-retardant in the reference documentation. No CPR reaction-to-fire class is specified. Verify the applicable fire-performance requirements and manufacturer documentation before selecting this cable for a project. Dimensions and weights depend on the selected cable configuration.
UNIMA CABLE | TECHNICAL DIMENSIONS

NAY2Y – Cable Dimensions & Weight Calculator

Reference dimensions and aluminium weights for NAY2Y-J and NAY2Y-O 0.6/1 kV cables. Calculate cable weight for your required length.

NAY2Y-J – With Protective Conductor

Cable Size Outer Diameter (mm) Aluminium Weight (kg/km) Cable Weight (kg/km)
1x120 RMv22.2348685
3x240/120 SMv56.22,4364,050
4x35 RE284061,020
4x50 SE295801,040
4x70 SE328121,330
4x95 SE371,1021,785
4x120 SE401,3922,140
4x150 SE441,7402,635
4x185 SE48.52,1463,210
4x240 SE54.52,7844,085
4x150 SMv441,7402,635

NAY2Y-O – Without Protective Conductor

Cable Size Outer Diameter (mm) Aluminium Weight (kg/km) Cable Weight (kg/km)
1x120 RMv22.2348685
4x150 SE48.71,7402,950
13 cable configurations – 11 NAY2Y-J and 2 NAY2Y-O

Cable Weight Calculator

685 Total Cable Weight (kg)
348 Aluminium Weight (kg)
1,000 Selected Length (m)
Technical Note: Aluminium weight and cable weight are calculated from reference values per 1,000 metres. Outer diameters are approximate. NAY2Y is not classified as flame-retardant in the reference documentation. Confirm project fire-performance requirements before installation.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


UNIMA CABLE COLLECTION

Explore Our Cable Range

Discover cable types, technical specifications and solutions for your projects.

80 Cable Types Available