UNIMA CABLE | POWER CABLES
U-1000 R2V
Low Voltage Power Cable | XLPE Insulation | PVC Outer Sheath | 0.6/1 kV
U-1000 R2V is a low-voltage power cable designed for electrical energy distribution in industrial facilities, buildings, urban networks and fixed installations. Its copper conductors, XLPE insulation and PVC outer sheath provide reliable operation at conductor temperatures up to 90°C, with resistance to sunlight and atmospheric conditions.
0.6/1 kV
Rated Voltage
90°C
Max. Operating Temperature
250°C
Short-Circuit Temperature
Eca
CPR Classification
Cable Construction
| Conductor | Copper, Class 1 or Class 2 |
| Conductor Standard | EN 60228 |
| Insulation | XLPE Compound |
| Bedding | Extruded elastomeric or plastomeric compound, or plastic tape |
| Outer Sheath | PVC Compound |
| Sheath Colour | Black |
| Core Identification | HD 308 S2 |
Technical Characteristics
| Rated Voltage | 0.6/1 kV |
| Test Voltage | 4 kV |
| Operating Temperature | Up to +90°C |
| Short-Circuit Temperature | Up to +250°C |
| Minimum Laying Temperature | -5°C |
| Bending Radius – Multicore | 12 × D |
| Bending Radius – Single-Core | 15 × D |
| Standards | NF C 32-321 / IEC 60502-1 |
| CPR Class | Eca |
Typical Applications
Low-voltage power distribution
Industrial electrical installations
Commercial and residential buildings
Urban distribution networks
Outdoor fixed installations
Cable trays, walls and raceways
Protected underground installations
Installations requiring resistance to sunlight and weather
Installation Note:
Direct underground installation requires suitable
mechanical protection. Prolonged installation in
waterlogged ground is not recommended.
Cable dimensions, conductor resistance and weights
depend on the selected configuration.
UNIMA CABLE | TECHNICAL DIMENSIONS
U-1000 R2V – Available Cable Dimensions
Nominal cross-sections, maximum conductor resistance at 20°C, maximum outer diameter, copper weight and approximate cable weight.
0.6/1 kV
Rated Voltage
Cu / XLPE
Conductor / Insulation
77
Cable Configurations
| Cable Size (mm²) |
Max. Resistance at 20°C (Ω/km) |
Max. Outer Diameter (mm) |
Copper Weight (kg/km) |
Approx. Cable Weight (kg/km) |
|---|
Technical Note:
Outer diameters are maximum values.
Cable weights are approximate.
Electrical characteristics and installation
conditions must be verified for the selected
cable configuration.