RE-2Y(St)Y-PiMF / TiMF 300 V

Instrumentation Cable | PE Insulation | Individual & Overall Screening | PVC Sheath

Product Description

RE-2Y(St)Y-PiMF and RE-2Y(St)Y-TiMF are individually and overall screened instrumentation cables designed for reliable transmission of analogue and digital signals in industrial process control and data processing systems.

The cables feature stranded Class 2 copper conductors, polyethylene (PE) insulation, individual aluminium foil screens around each pair or triplet, an overall electrostatic screen and a protective PVC outer sheath.

Individual screening reduces crosstalk between signal circuits, while overall screening provides protection against external electromagnetic interference. Low operating capacitance and low signal attenuation support long-distance signal transmission.

Available Cable Versions

Cable Designation Construction
RE-2Y(St)Y-PiMF Individually screened twisted pairs with overall electrostatic screening
RE-2Y(St)Y-TiMF Individually screened twisted triplets with overall electrostatic screening

Applications

  • Industrial instrumentation and measurement systems.
  • Industrial automation and process control.
  • Analogue and digital signal transmission.
  • Industrial data processing systems.
  • Chemical and petrochemical plants.
  • Oil and gas process instrumentation.
  • Power generation plants.
  • Monitoring and industrial control systems.
  • Fixed installations and installations involving bending.
  • Indoor installations in dry and damp environments.
  • Outdoor and underground installations, subject to applicable installation requirements.

Cable Construction

Component Description
Conductor Bare stranded copper, Class 2 according to IEC 60228 / HD 383 / DIN VDE 0295
Insulation Polyethylene (PE) compound according to EN 50290-2-23
Core Arrangement Twisted pairs (PiMF) or twisted triplets (TiMF), stranded in layers
Individual Screen Aluminium-laminated polyester tape around each pair or triplet
Drain Wire Stranded copper 0.5 mm² (7 × 0.3 mm) or solid copper wire, diameter 0.60 mm
Separator Transparent plastic foil around each pair or triplet and around the cable core
Overall Screen Aluminium-laminated polyester tape with copper drain wire
Outer Sheath PVC compound according to EN 50290-2-22
Sheath Colour Blue (RAL 5015) or black
Nominal Conductor Cross-sections 0.50 / 0.75 / 1.0 / 1.3 / 1.5 mm²
Number of Pairs or Triplets 2 / 4 / 5 / 6 / 8 / 10 / 12 / 16 / 20 / 24

Technical Characteristics

Parameter Value
Rated Voltage 300 V (signal transmission only)
Test Voltage – Core to Core 1500 V
Test Voltage – Core to Screen 1500 V
Fixed Installation Temperature -30°C to +70°C
Installation and Bending Temperature -5°C to +50°C
Minimum Insulation Resistance 5 GΩ × km
Operating Capacitance at 1 kHz Max. 120 pF/m
Inductance Approx. 0.75 mH/km
Minimum Internal Bending Radius 7.5 × cable outer diameter
Flame Retardancy IEC 60332-1 / EN 60332-1

Core Identification

  • Core A: Black.
  • Core B: White with black numerical marking.
  • Core C: Red (TiMF version only).
  • Alternative identification by numbered tape beneath the separator foil.
  • Additional orange communication conductor, 0.5 mm², in multicore constructions as specified.

Standards

  • EN 50288-7 – Instrumentation and control cables.
  • DIN VDE 0819-7 – Instrumentation cables.
  • IEC 60228 – Conductors of insulated cables.
  • EN 50290-2-23 – Polyethylene insulation compounds.
  • EN 50290-2-22 – PVC sheathing compounds.
  • IEC 60332-1 / EN 60332-1 – Flame propagation test.

Related Cable Variants

  • RE-2Y(St)Yv-PiMF – Reinforced PVC outer sheath.
  • RE-2X(St)Y-PiMF – Cross-linked polyethylene (XLPE) insulation, fixed installation temperature from -30°C to +90°C.
Installation Notice: These cables are intended for signal transmission, not power supply. The referenced cable construction is not intended for permanent installation in occupied building spaces. No CPR Euroclass is declared in the reference technical documentation. Related cable variants and individual sizes are subject to technical and commercial confirmation.

RE-2Y(St)Y-PiMF / TiMF – Technical Data & Dimensions

300 V | Class 2 Copper | PE Insulation | Individual & Overall Screening | PVC Sheath

RE-2Y(St)Y-PiMF – Individually Screened Pairs

Nominal Size
mm²
Conductor Stranding
n × mm
Outer Diameter
mm
Insulation Thickness
mm
Max. Resistance at 20°C
Ω/km
Max. L/R Ratio
µH/Ω
Copper Weight
kg/km
Cable Weight
kg/km
0.50 mm²
2 × 2 × 0.507 × 0.309.10.436.7253480
4 × 2 × 0.507 × 0.3010.50.436.72562120
5 × 2 × 0.507 × 0.3011.40.436.72577145
6 × 2 × 0.507 × 0.3012.20.436.72591165
8 × 2 × 0.507 × 0.3013.90.436.725120215
10 × 2 × 0.507 × 0.3015.20.436.725149260
12 × 2 × 0.507 × 0.3016.60.436.725178305
16 × 2 × 0.507 × 0.3018.70.436.725235390
20 × 2 × 0.507 × 0.3020.80.436.725293480
24 × 2 × 0.507 × 0.3022.60.436.725350570
0.75 mm²
2 × 2 × 0.757 × 0.379.90.425254390
4 × 2 × 0.757 × 0.3711.60.4252582150
5 × 2 × 0.757 × 0.3712.40.42525101175
6 × 2 × 0.757 × 0.3713.60.42525120210
8 × 2 × 0.757 × 0.3715.20.42525158265
10 × 2 × 0.757 × 0.3716.90.42525197325
12 × 2 × 0.757 × 0.3718.20.42525235380
16 × 2 × 0.757 × 0.3720.80.42525312495
20 × 2 × 0.757 × 0.3723.00.42525389610
24 × 2 × 0.757 × 0.3725.10.42525466725
1.0 mm²
2 × 2 × 17 × 0.4310.90.418.52553110
4 × 2 × 17 × 0.4312.60.418.525101175
5 × 2 × 17 × 0.4313.60.418.525125215
6 × 2 × 17 × 0.4314.70.418.525149250
8 × 2 × 17 × 0.4316.70.418.525197325
10 × 2 × 17 × 0.4318.30.418.525245390
12 × 2 × 17 × 0.4320.00.418.525293465
16 × 2 × 17 × 0.4322.80.418.525389600
20 × 2 × 17 × 0.4325.30.418.525485740
24 × 2 × 17 × 0.4327.60.418.525581880
1.3 mm²
2 × 2 × 1.37 × 0.4912.10.4514.24064130
4 × 2 × 1.37 × 0.4914.20.4514.240123220
5 × 2 × 1.37 × 0.4915.20.4514.240153260
6 × 2 × 1.37 × 0.4916.60.4514.240183310
8 × 2 × 1.37 × 0.4918.70.4514.240242390
10 × 2 × 1.37 × 0.4920.70.4514.240302480
12 × 2 × 1.37 × 0.4922.60.4514.240361575
16 × 2 × 1.37 × 0.4925.80.4514.240480745
20 × 2 × 1.37 × 0.4928.60.4514.240600920
24 × 2 × 1.37 × 0.4931.20.4514.2407191090
1.5 mm²
2 × 2 × 1.57 × 0.5212.40.4512.34072140
4 × 2 × 1.57 × 0.5214.70.4512.340139235
5 × 2 × 1.57 × 0.5215.70.4512.340173280
6 × 2 × 1.57 × 0.5217.10.4512.340206335
8 × 2 × 1.57 × 0.5219.50.4512.340274435
10 × 2 × 1.57 × 0.5221.70.4512.340341535
12 × 2 × 1.57 × 0.5223.40.4512.340408625
16 × 2 × 1.57 × 0.5226.70.4512.340542815
20 × 2 × 1.57 × 0.5229.80.4512.3406771020
24 × 2 × 1.57 × 0.5232.50.4512.3408111215

RE-2Y(St)Y-TiMF – Individually Screened Triplets

Nominal Size
mm²
Conductor Stranding
n × mm
Outer Diameter
mm
Insulation Thickness
mm
Max. Resistance at 20°C
Ω/km
Max. L/R Ratio
µH/Ω
Copper Weight
kg/km
Cable Weight
kg/km
0.50 mm²
2 × 3 × 0.507 × 0.3010.90.436.72543100
4 × 3 × 0.507 × 0.3012.40.436.72582160
5 × 3 × 0.507 × 0.3013.10.436.725101185
6 × 3 × 0.507 × 0.3014.30.436.725120220
8 × 3 × 0.507 × 0.3016.00.436.725158280
10 × 3 × 0.507 × 0.3017.80.436.725197345
12 × 3 × 0.507 × 0.3019.40.436.725235410
16 × 3 × 0.507 × 0.3022.10.436.725312530
20 × 3 × 0.507 × 0.3024.50.436.725389650
24 × 3 × 0.507 × 0.3026.50.436.725466765
0.75 mm²
2 × 3 × 0.757 × 0.3711.90.4252558125
4 × 3 × 0.757 × 0.3713.70.42525110200
5 × 3 × 0.757 × 0.3714.50.42525137240
6 × 3 × 0.757 × 0.3715.60.42525163275
8 × 3 × 0.757 × 0.3717.80.42525216360
10 × 3 × 0.757 × 0.3719.70.42525267440
12 × 3 × 0.757 × 0.3721.50.42525322525
16 × 3 × 0.757 × 0.3724.50.42525427680
20 × 3 × 0.757 × 0.3727.20.42525533840
24 × 3 × 0.757 × 0.3729.40.42525638985
1.0 mm²
2 × 3 × 17 × 0.4312.80.418.52572145
4 × 3 × 17 × 0.4314.90.418.525139240
5 × 3 × 17 × 0.4315.70.418.525173285
6 × 3 × 17 × 0.4317.10.418.525206335
8 × 3 × 17 × 0.4319.50.418.525274440
10 × 3 × 17 × 0.4321.70.418.525341540
12 × 3 × 17 × 0.4323.40.418.525408635
16 × 3 × 17 × 0.4326.90.418.525542840
20 × 3 × 17 × 0.4329.80.418.5256771035
24 × 3 × 17 × 0.4332.50.418.5258111230
1.3 mm²
2 × 3 × 1.37 × 0.4914.50.4514.24089180
4 × 3 × 1.37 × 0.4916.80.4514.240174300
5 × 3 × 1.37 × 0.4917.80.4514.240216355
6 × 3 × 1.37 × 0.4919.40.4514.240258425
8 × 3 × 1.37 × 0.4922.10.4514.240343550
10 × 3 × 1.37 × 0.4924.50.4514.240427675
12 × 3 × 1.37 × 0.4926.50.4514.240512795
16 × 3 × 1.37 × 0.4930.40.4514.2406811050
20 × 3 × 1.37 × 0.4933.70.4514.2408501290
24 × 3 × 1.37 × 0.4936.70.4514.24010191535
1.5 mm²
2 × 3 × 1.57 × 0.5215.00.4512.340101195
4 × 3 × 1.57 × 0.5217.40.4512.340197325
5 × 3 × 1.57 × 0.5218.40.4512.340245390
6 × 3 × 1.57 × 0.5220.00.4512.340292465
8 × 3 × 1.57 × 0.5222.80.4512.340389605
10 × 3 × 1.57 × 0.5225.30.4512.340485745
12 × 3 × 1.57 × 0.5227.60.4512.340581885
16 × 3 × 1.57 × 0.5231.50.4512.3407731155
20 × 3 × 1.57 × 0.5234.90.4512.3409651420
24 × 3 × 1.57 × 0.5238.30.4512.34011571710

Outer diameters and cable weights are approximate. Copper weights are stated according to the reference technical documentation. Values apply to the RE-2Y(St)Y-PiMF and RE-2Y(St)Y-TiMF constructions.

Packaging: drums or reels. Cut-to-length supply is subject to confirmation. Technical parameters, available lengths and individual constructions are subject to final order confirmation.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


UNIMA CABLE COLLECTION

Explore Our Cable Range

Discover cable types, technical specifications and solutions for your projects.

80 Cable Types Available