HSLCH-JZ / HSLCH-OZ 300/500 V Dca
Screened Halogen-Free Control Cable | Flexible Class 5 Copper | EMC Protection | FRNC | LSZH
Product Description
HSLCH-JZ and HSLCH-OZ are flexible, screened, low-smoke and halogen-free control cables designed for industrial control and measurement circuits with specific electromagnetic compatibility (EMC) requirements.
The cable construction combines fine-stranded Class 5 copper conductors, halogen-free FRNC insulation, a tinned copper braided screen and a halogen-free FRNC outer sheath.
The braided screen provides protection against electromagnetic interference in industrial control and measurement systems. The cable is flame-retardant and largely resistant to oil and grease.
HSLCH cables are intended for indoor fixed installations and moving applications within the specified temperature and bending radius limits.
Cable Versions
| Designation | Core Identification | Protective Conductor |
|---|---|---|
| HSLCH-JZ | Numbered cores and green-yellow core | Yes |
| HSLCH-OZ | Numbered cores | No |
Applications
- Industrial automation and control systems.
- Industrial machinery and equipment.
- Electrical control and measurement circuits.
- Manufacturing and production facilities.
- Electrical control panels and cabinets.
- Process control and monitoring systems.
- EMC-sensitive industrial installations.
- Indoor fixed and moving installations.
- Industrial environments requiring low-smoke and halogen-free cable construction.
Cable Construction
| Component | Description |
|---|---|
| Conductor | Bare copper |
| Conductor Class | Class 5, fine-stranded according to DIN EN IEC 60228 (VDE 0295) |
| Core Insulation | Halogen-free FRNC compound HI2 |
| Core Wrapping | Plastic foil |
| Screen | Tinned copper braid |
| Screen Coverage | Approx. 70% |
| Outer Sheath | Halogen-free FRNC compound HM2 |
| Sheath Colour | Grey, RAL 7001 |
| Protective Conductor | JZ: Yes / OZ: No |
Technical Characteristics
| Parameter | Value |
|---|---|
| Rated Voltage Uo/U | 300/500 V |
| Test Voltage | 2 kV |
| Maximum Conductor Temperature | +70°C |
| Temperature Range – Fixed | -30°C to +70°C |
| Temperature Range – Moving | -5°C to +70°C |
| Minimum Bending Radius – Fixed | 5 × outer cable diameter |
| Bending Radius – Moving | 10 × outer cable diameter |
| CPR Classification | Dca according to EN 50575 |
| Flame Retardancy | IEC 60332-3-24, Category C |
| Smoke Density | IEC 61034 / DIN EN 61034 |
| Halogen-Free | IEC 60754 / DIN EN 50267 |
| Oil Resistance | Yes |
| Installation Environment | Indoor use only |
Standards & Fire Performance
- EN 50575 – CPR classification Dca.
- DIN EN IEC 60228 / VDE 0295 – Class 5 flexible copper conductors.
- IEC 60332-3-24 / VDE 0482-266-2-4 – Flame propagation, Category C.
- IEC 61034 / DIN EN 61034 – Smoke density measurement.
- IEC 60754 / DIN EN 50267 – Halogen-free characteristics.
Available Cross-Sections
HSLCH-JZ: 0.5 mm² to 120 mm², with 3 to 25 cores depending on the conductor cross-section.
HSLCH-OZ: 0.5 mm² to 10 mm², with 2 to 25 cores depending on the conductor cross-section.
HSLCH-JZ / HSLCH-OZ – Technical Data & Dimensions
300/500 V | Dca | Class 5 Copper | Tinned Copper Braid | FRNC | LSZH
HSLCH-JZ – With Protective Conductor
Numbered cores with green-yellow protective conductor.
| Nominal Size mm² |
Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|
| 0.5 mm² | |||||
| 3G0.5 | 39 | 6 | 6.2 | 50 | 55 |
| 4G0.5 | 39 | 6 | 6.6 | 55 | 66 |
| 5G0.5 | 39 | 6 | 7.2 | 66 | 80 |
| 7G0.5 | 39 | 6 | 8.6 | 80.5 | 108 |
| 10G0.5 | 39 | 6 | 9.3 | 94.3 | TBC |
| 12G0.5 | 39 | 6 | 9.9 | 139 | 162 |
| 18G0.5 | 39 | 6 | 11.9 | 156.2 | 227 |
| 25G0.5 | 39 | 6 | 13.7 | 250 | 317 |
| 0.75 mm² | |||||
| 3G0.75 | 26 | 12 | 6.7 | 58 | 70 |
| 4G0.75 | 26 | 12 | 7.5 | 64 | 80 |
| 5G0.75 | 26 | 12 | 8.1 | 77.4 | 100 |
| 7G0.75 | 26 | 12 | 9.0 | 102 | 133 |
| 10G0.75 | 26 | 12 | 10.3 | 140 | 164 |
| 12G0.75 | 26 | 12 | 11.3 | 177 | 203 |
| 18G0.75 | 26 | 12 | 13.5 | 245 | 284 |
| 25G0.75 | 26 | 12 | 15.8 | 276 | 380 |
| 1 mm² | |||||
| 3G1 | 19.5 | 15 | 6.9 | 65.3 | 80 |
| 4G1 | 19.5 | 15 | 7.5 | 78.1 | 98 |
| 5G1 | 19.5 | 15 | 8.5 | 91 | 121 |
| 7G1 | 19.5 | 15 | 9.5 | 117 | 160 |
| 10G1 | 19.5 | 12 | 10.9 | 156 | TBC |
| 12G1 | 19.5 | 15 | 11.7 | 188 | 245 |
| 18G1 | 19.5 | 15 | 13.9 | 286 | 376 |
| 25G1 | 19.5 | 15 | 16.4 | 389 | 502 |
| 1.5 mm² | |||||
| 3G1.5 | 13.3 | 18 | 7.5 | 77 | 119 |
| 4G1.5 | 13.3 | 18 | 8.2 | 96.2 | 125 |
| 5G1.5 | 13.3 | 18 | 8.9 | 125 | 182 |
| 7G1.5 | 13.3 | 18 | 10.5 | 159 | 232 |
| 10G1.5 | 13.3 | 18 | 12.1 | 216.3 | 298 |
| 12G1.5 | 13.3 | 18 | 13.2 | 254.5 | 360 |
| 18G1.5 | 13.3 | 18 | 15.6 | 367.7 | 507 |
| 25G1.5 | 13.3 | 18 | 18.2 | 492.4 | 694 |
| 2.5 mm² | |||||
| 3G2.5 | 7.98 | 26 | 9.3 | 149 | 160 |
| 4G2.5 | 7.98 | 26 | 10.0 | 174.2 | 194 |
| 5G2.5 | 7.98 | 26 | 11.5 | 200.8 | 386 |
| 7G2.5 | 7.98 | 26 | 13.8 | 288 | 498 |
| 10G2.5 | 7.98 | 26 | 15.0 | 365.9 | TBC |
| 12G2.5 | 7.98 | 26 | 17.0 | 441 | 796 |
| 18G2.5 | 7.98 | 26 | 19.3 | 540 | 710 |
| 4 mm² | |||||
| 3G4 | 4.95 | 34 | 10.7 | 178.1 | 249 |
| 4G4 | 4.95 | 34 | 11.9 | 248 | 288 |
| 5G4 | 4.95 | 34 | 13.1 | 328 | 337 |
| 7G4 | 4.95 | 34 | 15.1 | 388 | 488 |
| 6 mm² | |||||
| 3G6 | 3.3 | 44 | 12.5 | 280 | 347 |
| 4G6 | 3.3 | 44 | 14.2 | 362 | 399 |
| 5G6 | 3.3 | 44 | 16.0 | 453 | 770 |
| 7G6 | 3.3 | 44 | 19.2 | 542 | 670 |
| 10 mm² | |||||
| 3G10 | 1.91 | 61 | 15.9 | 385 | 501 |
| 4G10 | 1.91 | 61 | 17.8 | 558 | 698 |
| 5G10 | 1.91 | 61 | 19.6 | 640 | 828 |
| 7G10 | 1.91 | 61 | 21.6 | 850 | 1254 |
| 16 mm² | |||||
| 4G16 | 1.21 | 82 | 20.8 | 910 | 987 |
| 5G16 | 1.21 | 82 | 22.9 | 1051 | 1207 |
| 7G16 | 1.21 | 82 | 25.2 | 1470 | 1816 |
| 25 mm² | |||||
| 3G25 | 0.78 | 108 | 24.8 | 900 | 1214 |
| 4G25 | 0.78 | 108 | 26.2 | 1289 | 1592 |
| 5G25 | 0.78 | 108 | 29.4 | 1486 | 2002 |
| 35 mm² | |||||
| 3G35 | 0.554 | 135 | 27.9 | 1130 | 1622 |
| 4G35 | 0.554 | 135 | 33.5 | 1690 | 2380 |
| 5G35 | 0.554 | 135 | 33.8 | 2015 | 2664 |
| 50 mm² | |||||
| 3G50 | 0.386 | 168 | 35.7 | 1766 | 2471 |
| 4G50 | 0.386 | 168 | 39.2 | 2325 | 3003 |
| 5G50 | 0.386 | 168 | 43.3 | 2781 | 3882 |
| 70 mm² | |||||
| 3G70 | 0.272 | 207 | 41.4 | 2218 | 3840 |
| 4G70 | 0.272 | 207 | 45.3 | 3089 | 4939 |
| 5G70 | 0.272 | 207 | 49.6 | 3696 | 6572 |
| 95 mm² | |||||
| 3G95 | 0.206 | 250 | 47.7 | 3010 | 5651 |
| 4G95 | 0.206 | 250 | 52.4 | 4013 | 6690 |
| 5G95 | 0.206 | 250 | 57.5 | 5016 | 8370 |
| 120 mm² | |||||
| 3G120 | 0.161 | 292 | 51.0 | 3802 | 6342 |
| 4G120 | 0.161 | 292 | 56.1 | 5067 | 8453 |
HSLCH-OZ – Without Protective Conductor
Numbered cores without green-yellow protective conductor.
| Nominal Size mm² |
Conductor Resistance Ω/km |
Ampacity in Air at 30°C A |
Outer Diameter mm |
Copper Weight (GER) kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|
| 2×0.5 | 39 | 6 | 5.8 | 35 | 47 |
| 2×0.75 | 26 | 12 | 6.4 | 45 | 58 |
| 2×1 | 19.5 | 15 | 6.6 | 50 | 64 |
| 2×1.5 | 13.3 | 18 | 7.9 | 63.3 | 97 |
| 5×1.5 | 13.3 | 18 | 8.9 | 125 | 182 |
| 7×1.5 | 13.3 | 18 | 10.5 | 159 | 232 |
| 12×1.5 | 13.3 | 18 | 13.2 | 254.5 | 360 |
| 25×1.5 | 13.3 | 18 | 18.2 | 492.4 | 694 |
| 2×2.5 | 7.98 | 26 | 8.5 | 98 | 132 |
| 12×2.5 | 7.98 | 26 | 17.0 | 441 | 796 |
| 25×2.5 | 7.98 | 26 | 28.7 | 790 | 980 |
| 2×4 | 4.95 | 34 | 10.0 | 163 | 209 |
| 2×6 | 3.3 | 44 | 11.9 | 200 | 278 |
| 2×10 | 1.91 | 61 | 14.9 | 328 | 434 |
G = with green-yellow protective conductor. × = without protective conductor in the OZ version. TBC = To Be Confirmed.
Outer diameters and cable weights are indicative. Copper values refer to the GER copper weight convention in the reference technical documentation and should not be interpreted as measured recoverable copper content.
Current ratings are reference values for air at 30°C. Actual permissible current depends on installation conditions, ambient temperature, grouping and the number of loaded conductors.
Technical parameters, cable weights, CPR documentation and availability are subject to final order confirmation.