N2XSEY 6/10 kV – Medium Voltage Copper Power Cable

Three-core medium voltage power cable with stranded copper conductors, XLPE DIX8 insulation, individual copper wire screens and a red PVC DMV6 outer sheath. Designed for power distribution networks, power stations and industrial installations.

6/10 kV 12 kV Um Copper Class 2 XLPE DIX8 Individual Copper Screens PVC DMV6 VDE 0276-620

Product Overview

N2XSEY 6/10 kV is a three-core medium voltage power cable designed for electrical energy distribution in power stations, industrial facilities and distribution networks.

The cable features stranded bare copper conductors with XLPE DIX8 insulation. Inner and outer semiconducting layers are applied using triple extrusion for electrical field control.

Each insulated core is individually screened with copper wires and a counter helix. The red PVC DMV6 outer sheath provides mechanical protection and flame-retardant properties according to IEC 60332-1-2.

The cable is suitable for indoor and outdoor installation, underground installation, installation in water and routing through cable ducts. Protection from sunlight is required.

Key Technical Features

6/10 kVRated Voltage
21 kVTest Voltage
+90°CMax. Conductor Temperature
2 pCPartial Discharge

Construction & Technical Properties

Cable Construction

ConductorBare Copper
Conductor ClassClass 2, Stranded
Conductor ConstructionRM
InsulationXLPE DIX8
Electrical Field ControlInner and Outer Semiconducting Layers
ExtrusionTriple Extrusion
Metallic ScreenCopper Wires + Counter Helix on Each Core
Outer SheathPVC DMV6
Sheath ColourRed
Core Configuration3 Cores

Electrical & Mechanical Data

Rated Voltage Uo/U6/10 kV
Max. System Voltage12 kV (Three-Phase)
Test Voltage21 kV
Max. Conductor Temp.+90°C
Fixed Cable Temp.Max. +70°C
Moved Cable Temp.-5°C to +70°C
Min. Bending Radius15 × D (Fixed)
Partial Discharge2 pC
Flame RetardancyIEC 60332-1-2
Sunlight ProtectionRequired

Typical Applications

Medium Voltage Distribution Networks
Power Stations
Industrial Power Installations
Underground Cable Installations
Installation in Water
Cable Duct Installations
Indoor Electrical Infrastructure
Outdoor Installations with Sunlight Protection

Applicable Standards

VDE 0276-620 – Medium voltage power cable specification.
IEC 60332-1-2 – Vertical flame propagation test for a single insulated cable.
VDE 0482-332-1-2 – Flame propagation testing.
VDE 0276-603 – Reference for sunlight protection requirements.
Installation Note: The cable must be protected from sunlight in accordance with the referenced VDE 0276-603 requirements. Observe the specified installation temperature, bending radius and permissible pulling force. Technical values are reference data and may vary by manufacturer. Availability and CPR classification are subject to confirmation.
UNIMA CABLE | TECHNICAL DIMENSIONS

N2XSEY 6/10 kV – Cable Sizes & Technical Data

Complete dimensional, electrical and mechanical reference data for nine three-core medium voltage cable sizes, including copper weight and total cable weight per kilometre.

9 SizesReference Cable Configurations
35–300 mm²Conductor Cross-Section
16–25 mm²Copper Screen Cross-Section
6/10 kVRated Voltage

Available Cable Sizes & Weights

Size (mm²) Resistance (Ω/km) Current Air 30°C (A) Current Ground 20°C (A) Outer Diameter (mm) Copper Weight (kg/km) Cable Weight (kg/km)
N2XSEY 6/10 kV – Three-Core Cables
3x35/16 RM0.5241781874912093300
3x50/16 RM0.3872132135216713900
3x70/16 RM0.2682652615522474700
3x95/16 RM0.1933223126029945850
3x120/16 RM0.1533703556437146800
3x150/25 RM0.1244203996746387950
3x185/25 RM0.09914814517156469300
3x240/25 RM0.075456652377727211550
3x300/25 RM0.060164859080916012200

Mechanical & Short-Circuit Data

Size (mm²) Conductor Diameter (mm) Insulation Thickness (mm) Sheath Thickness (mm) Short-Circuit Current 1s (kA) Bending Radius (mm) Pulling Force (N)
N2XSEY 6/10 kV – Installation Parameters
3x35/16 RM7.53.42.157355250
3x50/16 RM8.63.42.17.157807500
3x70/16 RM10.23.42.11082510500
3x95/16 RM123.42.113.690014250
3x120/16 RM13.53.42.117.296018000
3x150/25 RM153.42.121.4100522500
3x185/25 RM16.83.42.126.5106527750
3x240/25 RM19.23.42.134.3115536000
3x300/25 RM21.63.42.142.9120045000
Technical Note: Current ratings refer to air at 30°C and ground at 20°C. Short-circuit current values refer to a duration of one second. Bending radius values apply to fixed installations. Pulling force values refer to installation conditions. Copper weight is stated according to the GER reference convention. Cable weight represents net cable weight per 1,000 metres and excludes drums and packaging. Outer diameters are approximate. All technical values are subject to manufacturing tolerances and confirmation for the supplied product.