NA2XS(F)2Y – Aluminium Medium Voltage Cable

Longitudinally watertight single-core aluminium medium voltage power cable with XLPE insulation, copper wire screen and UV-resistant PE outer sheath. Designed for demanding underground, industrial, utility and power distribution installations.

6/10 kV 12/20 kV 18/30 kV VDE 0276-620 Longitudinal Water Blocking UV Resistant

Product Overview

NA2XS(F)2Y is a single-core medium voltage cable with a Class 2 stranded aluminium conductor and XLPE DIX8 insulation. Inner and outer semiconducting layers provide electrical field control through a triple extrusion process.

The cable includes a copper wire screen with counter helix and a black polyethylene DMP2 outer sheath. Longitudinal water blocking reduces water migration along the cable following mechanical damage.

Suitable for installation in the ground, water, cable ducts, outdoors and indoors. Typical uses include substations, industrial facilities, power stations and electricity distribution networks.

Key Technical Features

Al / Class 2 Stranded Aluminium Conductor
XLPE DIX8 Cross-Linked Insulation
90°C Maximum Conductor Temperature
15 × Ø Minimum Fixed Bending Radius

Cable Construction & Technical Data

Cable Construction

ConductorAluminium, Class 2 Stranded
InsulationXLPE DIX8
Field ControlInner and Outer Semiconducting Layers
ScreenCopper Wires + Counter Helix
Water BlockingLongitudinally Watertight
Outer SheathPolyethylene DMP2
Sheath ColourBlack

Electrical & Mechanical Properties

Rated Voltage6/10, 12/20, 18/30 kV
Maximum System Voltage12 / 24 / 36 kV
Test Voltage21 / 42 / 63 kV
Conductor TemperatureMaximum 90°C
Outer Cable, FixedMaximum +70°C
Outer Cable, Moving-20°C to +70°C
Bending Radius15 × Outer Diameter
Partial Discharge2 pC
UV ResistanceYes
Flame RetardanceNot Specified / None

Typical Applications

Medium Voltage Distribution Networks
Electrical Substations
Solar & Wind Energy Infrastructure
Industrial Power Installations
Underground Cable Routes
Cable Ducts and Outdoor Installations
Power Stations
Installations Requiring Longitudinal Water Blocking

Applicable Standard

VDE 0276-620 – Medium voltage cable construction and technical requirements. Specific electrical and dimensional values depend on the voltage class and cable size.
Technical Notice: This cable is not described as flame-retardant in the referenced manufacturer datasheet. The PE outer sheath provides mechanical durability and UV resistance. Current ratings depend on installation conditions. Technical values and approximate dimensions should be confirmed for the selected configuration.

Technical Data & Cable Dimensions

NA2XS(F)2Y | Aluminium Medium Voltage Cable | 6/10 – 18/30 kV | UNIMA CABLE

3Voltage Classes
57Cable Configurations
90°CMax. Conductor Temperature
XLPEInsulation

6/10 kV – Cable Sizes

Configuration Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Outer Ø
mm
Aluminium
kg/km
Copper Screen
kg/km
Cable Weight
kg/km
1x50/160.6413.418317125145182635
1x70/160.4433.422820827203182735
1x95/160.323.427824828276182835
1x120/160.2533.432128330348182935
1x150/250.2063.4364315314352831118
1x185/250.1643.4418357335372831263
1x240/250.1253.4494413356962831463
1x300/250.13.4568466378702831687
1x400/350.07783.46605294011603942096
1x400/500.07783.46605294011605602200
1x500/350.06053.47676024414503942477
1x630/350.04693.48906754918273942969
1x800/350.03673.410227335223203943400
1x1000/350.02913.411518566329003944780
14 configurations | 6/10 kV

12/20 kV – Cable Sizes

Configuration Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Outer Ø
mm
Aluminium
kg/km
Copper Screen
kg/km
Cable Weight
kg/km
1x50/160.6415.518517229145182784
1x70/160.4435.523121031203182902
1x95/160.325.5280251322761821013
1x120/160.2535.5323285343481821117
1x150/160.2065.5366319364351821254
1x150/250.2065.5366319364352831313
1x150/500.2065.536631936.44355601560
1x185/250.1645.5420361375372831467
1x240/250.1255.5496417406962831682
1x300/250.15.5569471428702831920
1x300/500.15.5569471428705602120
1x400/350.07785.56605354511603942355
1x500/350.06055.57666094814503942760
1x500/500.06055.576660948.314505602840
1x630/350.04695.58906755218273943268
1x630/500.04695.589067552.218275603320
1x800/350.03675.510157506023203943938
1x1000/350.02915.5113582062.629003944610
1x1200/350.02475.512789986534803945100
1x70/16 reinforced0.4435.523121031.6203182930
1x150/25 reinforced0.2065.5366319364352831300
1x240/25 reinforced0.1255.5496417406962831700
1x630/35 reinforced0.04695.589067553.318273943200
23 configurations | 12/20 kV

18/30 kV – Cable Sizes

Configuration Resistance
Ω/km
Insulation
mm
Air
A
Ground
A
Outer Ø
mm
Aluminium
kg/km
Copper Screen
kg/km
Cable Weight
kg/km
1x50/160.641818717434145182998
1x70/160.4438232213362031821128
1x95/160.328282254372761821255
1x95/350.32828225437.52763961420
1x120/160.2538325289393481821375
1x120/350.2538325289393483961560
1x150/250.2068367322404352831573
1x150/350.206836732240.54353961670
1x185/250.1648421364425372831740
1x185/350.1648421364425373961825
1x240/250.1258496422446962831979
1x300/250.18568476478702832221
1x300/350.18568476468703962285
1x400/350.077886595415011603942674
1x500/350.060587646165314503943132
1x500/500.0605876461654.514505653310
1x630/350.046988906756018273943668
1x800/350.0367810157506523203944367
1x1000/350.0291811358206629003944800
1x300/25 reinforced0.18568476478702832200
20 configurations | 18/30 kV
Technical Notes: Air current ratings refer to 30°C ambient temperature. Ground current ratings refer to 20°C ground temperature. Actual current-carrying capacity depends on installation conditions, thermal resistivity, cable grouping and applicable correction factors.

Special Variants: Configurations marked "reinforced" have a reinforced 3.0 mm outer sheath.

Dimensions & Weights: Aluminium conductor weight, copper screen weight and total cable weight are shown in kg/km. Values are approximate and subject to confirmation for the selected configuration.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

UNIMA CABLE

NA2XS(F)2Y Cable Calculator

Calculate cable weight, copper content and approximate cable length.

m
Cable Weight 0 kg
Cable Length 0 m
Copper Content 0 kg
Copper Share 0 %
Cable weight: 0 kg/km
Copper: 0 kg/km
Approximate values based on technical cable data. Actual values may vary due to manufacturing tolerances.