UNIMA CABLE | SIGNAL & CONTROL CABLES
LIYCY-TP
Flexible, screened signal and control cable with twisted pairs, designed for electronic control systems, signal transmission and sound-frequency communication. The cable features Class 5 stranded copper conductors, PVC insulation, a tinned copper braided screen and a grey PVC outer sheath.
LIYCY-TP
300/500 V
Class 5 Copper
Twisted Pairs
Tinned Copper Braid
PVC / PVC
VDE 0812
300/500 V
Operating Voltage
2000 V
Test Voltage
Class 5
Copper Conductor
7.5 × D
Bending Radius
-30°C / +70°C
Temperature Range
78 Ω
Impedance
Construction
- Conductor: Electrolytic stranded annealed copper, Class 5, EN 60228 / IEC 60228
- Insulation: PVC compound, EN 50290-2-21
- Core identification: DIN 47100
- Stranding: Twisted pairs arranged in layers
- Separator: PES tape
- Screen: Tinned copper wire braid
- Outer sheath: PVC compound, EN 50290-2-22
- Sheath colour: Grey, RAL 7032
Applications
- Electronic control system connections
- Signal and information transmission
- Sound-frequency transmission
- Industrial control installations
- Screened communication connections
- Electronic equipment interconnections
Technical Characteristics
Cable Designation
LIYCY-TP
Reference Standard
VDE 0812
Operating Voltage
300/500 V
Test Voltage
2000 V
Conductor Class
Class 5
Insulation Resistance
≥ 200 MΩ·km
Impedance
78 Ω
Inductance
0.67 mH/km
Temperature Range
-30°C to +70°C
Minimum Bending Radius
7.5 × D
Flame Retardance
IEC 60332-1-2
Outer Sheath Colour
RAL 7032 Grey
Electrical Data by Conductor Size
| Cross-section (mm²) |
Conductor Resistance (Ω/km) |
Mutual Capacitance (pF/m) |
Current Capacity (A) |
|---|---|---|---|
| 0.22 | 79 | 110 | 2.5 |
| 0.50 | 39 | 120 | 6 |
| 0.75 | 26 | 120 | 13 |
| 1.00 | 19.50 | 130 | 16 |
| 1.50 | 13.30 | 140 | 20 |
| 2.50 | 7.98 | 150 | 25 |
Technical Note:
Values are based on the technical reference
for the LIYCY-TP cable construction.
Current-carrying capacity depends on
installation and operating conditions.
CPR classification must be verified
against the manufacturer's applicable
Declaration of Performance (DoP).
06
Dimensions & Cable Weights
LIYCY-TP | 96 configurations | Manufacturer reference values
Showing all 96 configurations
| Configuration | Outer Diameter (mm) |
Copper Weight (kg/km) |
Cable Weight (kg/km) |
Weight for Length (kg) |
|---|
Enter a cable size in the search field to narrow the table.
Cable weight is calculated for the selected length.
Technical note:
Dimensions and weights are nominal manufacturer reference
values. Actual values may vary within manufacturing
tolerances. The calculated weight excludes drums,
pallets and packaging. CPR classification must be
confirmed against the applicable Declaration of
Performance (DoP).