N2XS2Y – Copper Medium Voltage Power Cable
Single-core medium voltage power cable with stranded copper conductor, XLPE insulation, copper wire screen and black polyethylene outer sheath. Designed for underground power distribution, industrial installations and medium voltage electrical infrastructure.
Product Overview
N2XS2Y is a single-core copper medium voltage power cable designed for electrical energy transmission and distribution in underground, outdoor and indoor installations.
The cable incorporates a round stranded bare copper conductor (RM), manufactured according to DIN EN 60228 Class 2.
The conductor is surrounded by an inner semiconducting layer, cross-linked polyethylene (XLPE) insulation and an outer semiconducting layer.
A metallic screen consisting of copper wires surrounds the insulated cable core. The screen forms part of the electrical protection and earthing arrangement of the medium voltage cable system.
The black polyethylene outer sheath provides external protection for the cable during installation and service.
N2XS2Y is suitable for direct burial, outdoor installations, indoor installations and installation in cable channels.
The reference product range includes rated voltages of 6/10 kV, 12/20 kV and 18/30 kV, with copper conductor cross-sections ranging from 35 to 500 mm² depending on the selected voltage rating.
Key Technical Features
Voltage Classes
N2XS2Y 6/10 kV
35–500 mm²
11 reference configurations.
Test voltage: 21 kV for 5 minutes.
N2XS2Y 12/20 kV
35–500 mm²
11 reference configurations.
Test voltage: 42 kV for 5 minutes.
N2XS2Y 18/30 kV
50–500 mm²
10 reference configurations.
Test voltage: 63 kV for 5 minutes.
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
XLPE Insulation & Copper Wire Screen
XLPE Insulation System
Cross-linked polyethylene insulation provides the dielectric insulation required for medium voltage power distribution.
The inner and outer semiconducting layers support controlled electrical field distribution around the conductor and insulation.
The reference documentation specifies a short-circuit temperature of +250°C for a maximum duration of 5 seconds.
Metallic Copper Wire Screen
The metallic copper wire screen is available in reference cross-sections of 16, 25 and 35 mm².
The screen cross-section depends on the selected conductor size and must be suitable for the earthing arrangement and anticipated earth-fault current.
Screen bonding and earthing must be designed according to the requirements of the complete medium voltage installation.
PE Outer Sheath & Underground Installation
The black polyethylene outer sheath provides external protection for underground and outdoor installations.
N2XS2Y is suitable for direct burial in the ground, installation in cable channels and installation in indoor and outdoor environments.
The reference construction does not specify additional longitudinal or transverse water-blocking layers.
Where longitudinal or radial watertightness is required, a separately specified water-blocked cable construction must be selected.
Typical Applications
Installation Conditions
N2XS2Y cables are intended for fixed medium voltage installations.
The reference documentation permits direct burial, outdoor installation, indoor installation and installation in cable channels.
The specified temperature range during bending and for fixed installation is -20°C to +90°C.
The minimum bending radius is 15 times the cable outer diameter.
The published current-carrying capacities are based on trefoil cable formation. Actual current ratings depend on installation conditions, ambient temperature, soil thermal resistivity, burial depth, cable spacing and screen bonding.
Installation design must be verified for the actual project conditions.
Applicable Standards
DIN VDE 0276-620 – Reference standard for medium voltage power cables with extruded insulation.
HD 620 S1:1996 – Reference harmonisation document for medium voltage distribution cables, as stated in the original technical documentation.
DIN EN 60228, Class 2 – Stranded copper conductor construction.
Related Medium Voltage Cable Constructions
Copper Conductor Versions
N2XS2Y – Copper conductor, XLPE insulation, copper wire screen and PE sheath.
N2XS(F)2Y – Related copper conductor construction with longitudinal water blocking.
N2XS(FL)2Y – Related copper conductor construction with longitudinal and transverse water blocking.
Aluminium Conductor Versions
NA2XS2Y – Related aluminium conductor construction with XLPE insulation and PE sheath.
NA2XS(F)2Y – Related aluminium conductor construction with longitudinal water blocking.
NA2XS(FL)2Y – Related aluminium conductor construction with longitudinal and transverse water blocking.
N2XS2Y – Cable Sizes & Technical Data
Complete reference range of single-core copper medium voltage power cables rated 6/10 kV, 12/20 kV and 18/30 kV, including conductor and screen cross-sections, copper content, cable dimensions, approximate weights and current-carrying capacities.
N2XS2Y 6/10 kV – Cable Sizes & Current Ratings
| Cable Size (mm²) | Copper Content (kg/km) | Approx. Outer Diameter (mm) | Max. Outer Diameter (mm) | Approx. Weight (kg/km) | Current in Ground (A)* | Current in Air (A)* |
|---|---|---|---|---|---|---|
| 1x35 RM/16 | 518.4 | 23 | 28 | 820 | 187 | 197 |
| 1x50 RM/16 | 662.4 | 24 | 29 | 960 | 220 | 236 |
| 1x70 RM/16 | 854.4 | 26 | 31 | 1150 | 269 | 292 |
| 1x95 RM/16 | 1094.4 | 27 | 32 | 1450 | 320 | 358 |
| 1x120 RM/16 | 1334.4 | 29 | 34 | 1700 | 363 | 413 |
| 1x150 RM/25 | 1723.2 | 30 | 35 | 2000 | 405 | 468 |
| 1x185 RM/25 | 2059.2 | 32 | 37 | 2350 | 456 | 535 |
| 1x240 RM/25 | 2587.2 | 34 | 39 | 2900 | 526 | 631 |
| 1x300 RM/25 | 3163.2 | 36 | 41 | 3550 | 591 | 722 |
| 1x400 RM/35 | 4233.6 | 40 | 45 | 4500 | 662 | 827 |
| 1x500 RM/35 | 5193.6 | 43 | 48 | 5550 | 744 | 949 |
N2XS2Y 12/20 kV – Cable Sizes & Current Ratings
| Cable Size (mm²) | Copper Content (kg/km) | Approx. Outer Diameter (mm) | Max. Outer Diameter (mm) | Approx. Weight (kg/km) | Current in Ground (A)* | Current in Air (A)* |
|---|---|---|---|---|---|---|
| 1x35 RM/16 | 518.4 | 27 | 32 | 1000 | 189 | 200 |
| 1x50 RM/16 | 662.4 | 28 | 33 | 1150 | 222 | 239 |
| 1x70 RM/16 | 854.4 | 30 | 35 | 1350 | 271 | 297 |
| 1x95 RM/16 | 1094.4 | 31 | 36 | 1600 | 323 | 361 |
| 1x120 RM/16 | 1334.4 | 33 | 38 | 1850 | 367 | 416 |
| 1x150 RM/25 | 1723.2 | 34 | 39 | 2250 | 409 | 470 |
| 1x185 RM/25 | 2059.2 | 36 | 41 | 2600 | 461 | 538 |
| 1x240 RM/25 | 2587.2 | 39 | 44 | 3150 | 532 | 634 |
| 1x300 RM/25 | 3163.2 | 41 | 46 | 3800 | 599 | 724 |
| 1x400 RM/35 | 4233.6 | 44 | 49 | 4750 | 671 | 829 |
| 1x500 RM/35 | 5193.6 | 47 | 52 | 5800 | 754 | 953 |
N2XS2Y 18/30 kV – Cable Sizes & Current Ratings
| Cable Size (mm²) | Copper Content (kg/km) | Approx. Outer Diameter (mm) | Max. Outer Diameter (mm) | Approx. Weight (kg/km) | Current in Ground (A)* | Current in Air (A)* |
|---|---|---|---|---|---|---|
| 1x50 RM/16 | 662.4 | 33 | 38 | 1350 | 225 | 241 |
| 1x70 RM/16 | 854.4 | 35 | 40 | 1600 | 274 | 299 |
| 1x95 RM/16 | 1094.4 | 36 | 41 | 1900 | 327 | 363 |
| 1x120 RM/16 | 1334.4 | 38 | 43 | 2200 | 371 | 418 |
| 1x150 RM/25 | 1723.2 | 39 | 44 | 2550 | 414 | 472 |
| 1x185 RM/25 | 2059.2 | 41 | 46 | 2950 | 466 | 539 |
| 1x240 RM/25 | 2587.2 | 43 | 48 | 3500 | 539 | 635 |
| 1x300 RM/25 | 3163.2 | 46 | 51 | 4150 | 606 | 725 |
| 1x400 RM/35 | 4233.6 | 49 | 54 | 5150 | 680 | 831 |
| 1x500 RM/35 | 5193.6 | 52 | 57 | 6200 | 765 | 953 |
* Current-carrying capacities: Reference values for cables installed in trefoil formation. The original documentation does not specify detailed calculation conditions such as ambient temperature, soil thermal resistivity, burial depth or screen bonding arrangement. Actual permissible current must be determined for the project-specific installation.
Copper content values are reproduced from the reference documentation and must not be interpreted as independently verified recoverable copper mass. Cable dimensions and weights are approximate.
Voltage Class Comparison
| Parameter | 6/10 kV | 12/20 kV | 18/30 kV |
|---|---|---|---|
| Rated Voltage U0/U | 6/10 kV | 12/20 kV | 18/30 kV |
| Conductor Range | 35–500 mm² | 35–500 mm² | 50–500 mm² |
| Screen Cross-Section | 16–35 mm² | 16–35 mm² | 16–35 mm² |
| Reference Configurations | 11 | 11 | 10 |
| Test Voltage | 21 kV | 42 kV | 63 kV |
| Test Duration | 5 min | 5 min | 5 min |
| Approx. Outer Diameter | 23–43 mm | 27–47 mm | 33–52 mm |
| Max. Outer Diameter | 28–48 mm | 32–52 mm | 38–57 mm |
| Approx. Cable Weight | 820–5550 kg/km | 1000–5800 kg/km | 1350–6200 kg/km |
| Current in Ground* | 187–744 A | 189–754 A | 225–765 A |
| Current in Air* | 197–949 A | 200–953 A | 241–953 A |
Conductor & Copper Screen Configuration
| Conductor Cross-Section (mm²) | Copper Screen (mm²) | Conductor Construction | Copper Content (kg/km) |
|---|---|---|---|
| 35 | 16 | RM, Class 2 | 518.4 |
| 50 | 16 | RM, Class 2 | 662.4 |
| 70 | 16 | RM, Class 2 | 854.4 |
| 95 | 16 | RM, Class 2 | 1094.4 |
| 120 | 16 | RM, Class 2 | 1334.4 |
| 150 | 25 | RM, Class 2 | 1723.2 |
| 185 | 25 | RM, Class 2 | 2059.2 |
| 240 | 25 | RM, Class 2 | 2587.2 |
| 300 | 25 | RM, Class 2 | 3163.2 |
| 400 | 35 | RM, Class 2 | 4233.6 |
| 500 | 35 | RM, Class 2 | 5193.6 |
Example: 1x240 RM/25 identifies a single-core cable with a 240 mm² round stranded copper conductor and a 25 mm² metallic copper screen.
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Rated Voltage U0/U | 6/10, 12/20 and 18/30 kV |
| Test Voltage 6/10 kV | 21 kV / 5 minutes |
| Test Voltage 12/20 kV | 42 kV / 5 minutes |
| Test Voltage 18/30 kV | 63 kV / 5 minutes |
| Conductor Material | Bare Copper |
| Conductor Construction | Round Stranded (RM) |
| Conductor Class | Class 2 |
| Conductor Standard | DIN EN 60228 |
| Insulation Material | XLPE |
| Metallic Screen | Copper Wires |
| Conductor DC Resistance | Not Specified |
| Inductance | Not Specified |
| Capacitance | Not Specified |
| Screen Short-Circuit Rating | Not Specified |
| Reference Current-Rating Formation | Trefoil |
Temperature Characteristics
| Installation / Operating Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| During Bending | -20°C | +90°C |
| Fixed Installation | -20°C | +90°C |
| Short-Circuit Condition | Not Specified | +250°C |
Maximum short-circuit duration: 5 seconds.
Minimum Cable Bending Radius
| Cable Size (mm²) | 6/10 kV (mm) | 12/20 kV (mm) | 18/30 kV (mm) |
|---|---|---|---|
| 1x35/16 | 345 | 405 | — |
| 1x50/16 | 360 | 420 | 495 |
| 1x70/16 | 390 | 450 | 525 |
| 1x95/16 | 405 | 465 | 540 |
| 1x120/16 | 435 | 495 | 570 |
| 1x150/25 | 450 | 510 | 585 |
| 1x185/25 | 480 | 540 | 615 |
| 1x240/25 | 510 | 585 | 645 |
| 1x300/25 | 540 | 615 | 690 |
| 1x400/35 | 600 | 660 | 735 |
| 1x500/35 | 645 | 705 | 780 |
The listed bending radii are indicative calculated values based on the approximate outer diameter multiplied by the specified bending factor of 15. For installation planning, the actual supplied cable diameter must be used. Where only the maximum reference diameter is available, a conservative planning radius may be calculated from that value.
Conservative Bending Radius Based on Maximum Diameter
| Cable Size (mm²) | 6/10 kV (mm) | 12/20 kV (mm) | 18/30 kV (mm) |
|---|---|---|---|
| 1x35/16 | 420 | 480 | — |
| 1x50/16 | 435 | 495 | 570 |
| 1x70/16 | 465 | 525 | 600 |
| 1x95/16 | 480 | 540 | 615 |
| 1x120/16 | 510 | 570 | 645 |
| 1x150/25 | 525 | 585 | 660 |
| 1x185/25 | 555 | 615 | 690 |
| 1x240/25 | 585 | 660 | 720 |
| 1x300/25 | 615 | 690 | 765 |
| 1x400/35 | 675 | 735 | 810 |
| 1x500/35 | 720 | 780 | 855 |
Calculated planning values based on 15 times the maximum reference outer diameter. These values are not separately declared manufacturer installation parameters.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Round Stranded Bare Copper, RM, Class 2 |
| 2 | Conductor Screen | Inner Semiconducting Layer |
| 3 | Core Insulation | Cross-Linked Polyethylene (XLPE) |
| 4 | Insulation Screen | Outer Semiconducting Layer |
| 5 | Metallic Screen | Copper Wires |
| 6 | Outer Sheath | Black Polyethylene (PE) |
Installation & Environmental Characteristics
| Parameter | Reference Value |
|---|---|
| Direct Burial | Suitable |
| Outdoor Installation | Suitable |
| Indoor Installation | Suitable |
| Cable Channels | Suitable |
| Fixed Installation | Suitable |
| Outer Sheath Material | Polyethylene (PE) |
| Outer Sheath Colour | Black |
| Minimum Bending Radius | 15 x Cable Diameter |
| Longitudinal Water Blocking | Not Specified |
| Transverse Water Blocking | Not Specified |
| Permanent Water Immersion | Not Specified |
| UV Resistance Test | Not Specified |
| Maximum Pulling Force | Not Specified |
| Flame Retardancy | Not Specified |
| CPR Classification | Not Specified |
Applicable Standards
| Standard | Reference Application |
|---|---|
| DIN VDE 0276-620 | Medium Voltage Power Cable Construction |
| HD 620 S1:1996 | Reference Harmonisation Document for Medium Voltage Distribution Cables |
| DIN EN 60228 | Stranded Copper Conductors, Class 2 |