N2XSEY 6/10 kV – Medium Voltage Copper Power Cable
Three-core medium voltage power cable with stranded copper conductors, XLPE DIX8 insulation, individual copper wire screens and a red PVC DMV6 outer sheath. Designed for power distribution networks, power stations and industrial installations.
Product Overview
N2XSEY 6/10 kV is a three-core medium voltage power cable designed for electrical energy distribution in power stations, industrial facilities and distribution networks.
The cable features stranded bare copper conductors with XLPE DIX8 insulation. Inner and outer semiconducting layers are applied using triple extrusion for electrical field control.
Each insulated core is individually screened with copper wires and a counter helix. The red PVC DMV6 outer sheath provides mechanical protection and flame-retardant properties according to IEC 60332-1-2.
The cable is suitable for indoor and outdoor installation, underground installation, installation in water and routing through cable ducts. Protection from sunlight is required.
Key Technical Features
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Typical Applications
Applicable Standards
IEC 60332-1-2 – Vertical flame propagation test for a single insulated cable.
VDE 0482-332-1-2 – Flame propagation testing.
VDE 0276-603 – Reference for sunlight protection requirements.
N2XSEY 6/10 kV – Cable Sizes & Technical Data
Complete dimensional, electrical and mechanical reference data for nine three-core medium voltage cable sizes, including copper weight and total cable weight per kilometre.
Available Cable Sizes & Weights
| Size (mm²) | Resistance (Ω/km) | Current Air 30°C (A) | Current Ground 20°C (A) | Outer Diameter (mm) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|
| N2XSEY 6/10 kV – Three-Core Cables | ||||||
| 3x35/16 RM | 0.524 | 178 | 187 | 49 | 1209 | 3300 |
| 3x50/16 RM | 0.387 | 213 | 213 | 52 | 1671 | 3900 |
| 3x70/16 RM | 0.268 | 265 | 261 | 55 | 2247 | 4700 |
| 3x95/16 RM | 0.193 | 322 | 312 | 60 | 2994 | 5850 |
| 3x120/16 RM | 0.153 | 370 | 355 | 64 | 3714 | 6800 |
| 3x150/25 RM | 0.124 | 420 | 399 | 67 | 4638 | 7950 |
| 3x185/25 RM | 0.0991 | 481 | 451 | 71 | 5646 | 9300 |
| 3x240/25 RM | 0.0754 | 566 | 523 | 77 | 7272 | 11550 |
| 3x300/25 RM | 0.0601 | 648 | 590 | 80 | 9160 | 12200 |
Mechanical & Short-Circuit Data
| Size (mm²) | Conductor Diameter (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Short-Circuit Current 1s (kA) | Bending Radius (mm) | Pulling Force (N) |
|---|---|---|---|---|---|---|
| N2XSEY 6/10 kV – Installation Parameters | ||||||
| 3x35/16 RM | 7.5 | 3.4 | 2.1 | 5 | 735 | 5250 |
| 3x50/16 RM | 8.6 | 3.4 | 2.1 | 7.15 | 780 | 7500 |
| 3x70/16 RM | 10.2 | 3.4 | 2.1 | 10 | 825 | 10500 |
| 3x95/16 RM | 12 | 3.4 | 2.1 | 13.6 | 900 | 14250 |
| 3x120/16 RM | 13.5 | 3.4 | 2.1 | 17.2 | 960 | 18000 |
| 3x150/25 RM | 15 | 3.4 | 2.1 | 21.4 | 1005 | 22500 |
| 3x185/25 RM | 16.8 | 3.4 | 2.1 | 26.5 | 1065 | 27750 |
| 3x240/25 RM | 19.2 | 3.4 | 2.1 | 34.3 | 1155 | 36000 |
| 3x300/25 RM | 21.6 | 3.4 | 2.1 | 42.9 | 1200 | 45000 |