E-YCY 0.6/1 kV
PVC insulated and PVC sheathed power cable with bare copper conductors and a concentric copper conductor consisting of copper wires and a counter helix. Designed for fixed installation indoors, outdoors, underground, in water and in concrete. Available in E-YCY-O, E-YCY-OZ and E-YCY-J configurations.
E-YCY
0.6/1 kV
Copper Conductor
Concentric Copper
PVC / PVC
Black Sheath
CPR Eca*
HD 603 Reference
0.6/1 kV
Radni napon
4 kV
Test Voltage
70°C
Maximum Conductor Temperature
12 × D
Minimum Fixed Bending Radius
-30°C / +70°C
Fixed Cable Temperature Range
Eca*
CPR Classification
Construction
- Conductor: Bare copper
- Conductor class: Class 1; Class 2 from 25 mm²
- Insulation: PVC DIV 4
- Concentric conductor: Copper wires with counter helix
- Outer sheath: PVC
- Sheath colour: Crna
- Core identification: Colour-coded or numbered, depending on configuration
- Meter marking: Yes
Primjene
- Fixed indoor electrical installations
- Outdoor power cable installations
- Direct burial in the ground
- Installation in water
- Installation in concrete
- Power distribution with a concentric copper conductor
Technical Characteristics
Cable Designation
E-YCY
Reference Standard
ÖVE/ÖNORM E 8200-603
(HD 603), with reference to
Rated Voltage U₀/U
0.6/1 kV
Maximum System Voltage
1.2 kV
Test Voltage
4 kV
Conductor Construction
Class 1 / Class 2
from 25 mm²
Conductor Temperature
Max. +70°C
Short-Circuit Temperature
Max. +160°C
Fixed Cable Temperature
-30°C to +70°C
Moved Cable Temperature
-5°C to +70°C
Fixed Bending Radius
12 × D
Moving Bending Radius
15 × D
Maximum Tensile Stress
50 N/mm²
Flame Retardance
IEC 60332-1-2
UV Resistance
Yes
Outer Sheath Colour
Crna
Available Configurations
| Variant | Core Identification | Listed Sizes |
|---|---|---|
| E-YCY-O | Without protective conductor | 9 |
| E-YCY-OZ | Numbered cores, without protective conductor | 15 |
| E-YCY-J | With green-yellow protective conductor | 3 |
Technical Note:
Technical values and listed configurations
are based on the supplied E-YCY reference
datasheet. Dimensions and weights are
approximate. The Eca classification shown
in the reference document must be confirmed
for the actual supplied product by its
applicable manufacturer Declaration of
Performance (DoP). Availability and
manufacturer-specific data are subject
to confirmation.
UNIMA CABLE | CABLE DIMENSIONS
E-YCY – Technical Size Table
27 listed cable configurations. Click any table row to calculate the total cable and copper weight.
Technical Size Table
| Cable Size | Outer Diameter (mm) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|
Cable Weight Calculator
Selected Cable:
–
–
Total Cable Weight (kg)
–
Copper Weight (kg)
–
Selected Length (m)
Technical Note:
Cable diameters and weights are approximate
reference values. Copper weight includes
the copper components of the cable.
Actual values may vary by manufacturer.
Select a cable size by clicking its row.