LIYCY-TP

Flexible, screened signal and control cable with twisted pairs, designed for electronic control systems, signal transmission and sound-frequency communication. The cable features Class 5 stranded copper conductors, PVC insulation, a tinned copper braided screen and a grey PVC outer sheath.

LIYCY-TP 300/500 V Class 5 Copper Twisted Pairs Tinned Copper Braid PVC / PVC VDE 0812
300/500 V Operating Voltage
2000 V Test Voltage
Class 5 Copper Conductor
7.5 × D Bending Radius
-30°C / +70°C Temperature Range
78 Ω Impedance

Construction

  • Conductor: Electrolytic stranded annealed copper, Class 5, EN 60228 / IEC 60228
  • Insulation: PVC compound, EN 50290-2-21
  • Core identification: DIN 47100
  • Stranding: Twisted pairs arranged in layers
  • Separator: PES tape
  • Screen: Tinned copper wire braid
  • Outer sheath: PVC compound, EN 50290-2-22
  • Sheath colour: Grey, RAL 7032

Primjene

  • Electronic control system connections
  • Signal and information transmission
  • Sound-frequency transmission
  • Industrial control installations
  • Screened communication connections
  • Electronic equipment interconnections

Technical Characteristics

Cable Designation LIYCY-TP
Reference Standard VDE 0812
Operating Voltage 300/500 V
Test Voltage 2000 V
Conductor Class Class 5
Insulation Resistance ≥ 200 MΩ·km
Impedance 78 Ω
Inductance 0.67 mH/km
Temperature Range -30°C to +70°C
Minimum Bending Radius 7.5 × D
Flame Retardance IEC 60332-1-2
Outer Sheath Colour RAL 7032 Grey

Electrical Data by Conductor Size

Poprečni presjek
(mm²)
Conductor Resistance
(Ω/km)
Mutual Capacitance
(pF/m)
Current Capacity
(A)
0.22791102.5
0.50391206
0.752612013
1.0019.5013016
1.5013.3014020
2.507.9815025
Technical Note: Values are based on the technical reference for the LIYCY-TP cable construction. Current-carrying capacity depends on installation and operating conditions. CPR classification must be verified against the manufacturer's applicable Declaration of Performance (DoP).
06

Dimensions & Cable Weights

LIYCY-TP | 96 configurations | Manufacturer reference values

Showing all 96 configurations
Configuration Outer Diameter
(mm)
Copper Weight
(kg/km)
Cable Weight
(kg/km)
Weight for Length
(kg)
Enter a cable size in the search field to narrow the table. Cable weight is calculated for the selected length.
Technical note: Dimensions and weights are nominal manufacturer reference values. Actual values may vary within manufacturing tolerances. The calculated weight excludes drums, pallets and packaging. CPR classification must be confirmed against the applicable Declaration of Performance (DoP).

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

UNIMA CABLE

LIYCY-TP Cable Calculator

Calculate cable weight, copper content and approximate cable length.

m
Cable Weight 0 kg
Cable Length 0 m
Copper Content 0 kg
Copper Share 0 %
Cable weight: 0 kg/km
Copper: 0 kg/km
Approximate values based on technical cable data. Actual values may vary due to manufacturing tolerances.

Send Us email - RFQ