NSGAFöu (GHöuf) – Special Rubber Single-Core Cable 1.8/3 kV
Flexible single-core rubber cable with fine-stranded tinned copper conductor, aluminium-polyester foil wrapping, EPR insulation and a robust black polychloroprene outer sheath. Designed for railway vehicles, buses, switchboards, electrical distribution equipment and short-circuit protection applications.
Product Overview
NSGAFöu (GHöuf) is a special flexible single-core rubber cable rated at 1.8/3 kV, manufactured with reference to DIN VDE 0250 Part 602.
The cable features a fine-stranded tinned copper conductor according to DIN EN 60228 Class 5, providing flexibility for installation and connection within electrical equipment.
The conductor is wrapped with aluminium-polyester foil and insulated with an ethylene propylene rubber (EPR) compound.
A black polychloroprene outer sheath provides resistance to abrasion and oil, together with specified single-cable flame-retardant performance.
NSGAFöu is intended for use in railway vehicles and buses, as well as installations in dry locations, switchboards and electrical distribution equipment up to 1,000 V, including short-circuit protection and earthing applications.
The reference product range includes 16 nominal conductor cross-sections from 1.5 mm² to 300 mm², covering compact electrical connections and high-current power distribution applications.
Key Technical Features
Cable Construction & Technical Properties
Cable Construction
Electrical & Mechanical Properties
Flexible Tinned Copper Conductor
Class 5 Conductor Construction
The conductor consists of multiple fine tinned copper wires arranged in a flexible stranded construction according to DIN EN 60228 Class 5.
The fine-stranded construction facilitates cable routing, installation and termination in switchboards, electrical distribution equipment and vehicle electrical systems.
The reference conductor range extends from 1.5 mm² to 300 mm².
Aluminium-Polyester Foil Wrapping
An aluminium-polyester foil wrapping is applied around the stranded conductor beneath the EPR insulation.
This wrapping forms part of the specified cable construction.
The foil wrapping must not be interpreted as a declared external electromagnetic screen or protective conductor.
EPR Insulation & Polychloroprene Sheath
Ethylene Propylene Rubber Insulation
The EPR insulation provides the dielectric insulation required for the specified rated voltage of 1.8/3 kV.
The reference cable has an AC test voltage of 6 kV and a maximum short-circuit conductor temperature of +200°C for a duration not exceeding five seconds.
The specified temperature range during bending is -25°C to +80°C.
Heavy-Duty Polychloroprene Outer Sheath
The black polychloroprene outer sheath provides mechanical protection and resistance to abrasion and oil.
Oil resistance is specified according to EN 60811-2-1.
Single-cable flame propagation performance is specified according to EN 60332-1-2.
The reference construction is not declared halogen-free.
Short-Circuit Protection Applications
NSGAFöu is designed for applications requiring a robust insulated single-core cable within electrical equipment, including short-circuit protection and earthing applications.
The combination of EPR insulation, flexible tinned copper and a protective rubber sheath makes the cable suitable for the documented applications in switchboards and electrical distribution equipment up to 1,000 V.
The specified maximum short-circuit temperature is +200°C, with a maximum short-circuit duration of five seconds.
Short-circuit withstand capability must be evaluated according to conductor cross-section, prospective fault current, protective device operating time and the applicable installation requirements.
Typical Applications
Installation Conditions
Installation Parameters
Additional Installation Considerations
Fire & Environmental Performance
Specified Properties
Additional Performance Requirements
Applicable Standards
DIN VDE 0250-602 – Reference product standard for the special rubber-insulated cable construction.
DIN EN 60228 Class 5 – Flexible stranded conductors of insulated cables.
EN 60811-2-1 – Reference test standard for oil resistance, as specified in the original technical documentation.
EN 60332-1-2 – Vertical flame propagation test for a single insulated wire or cable.
Voltage Variants
NSGAFöu 1.8/3 kV
Standard reference construction covered by the published technical dimensions and electrical characteristics.
Rated voltage: 1.8/3 kV.
Reference cross-section range: 1.5–300 mm².
AC test voltage: 6 kV.
NSGAFöu 3.6/6 kV
A higher-voltage NSGAFöu variant is referenced in the original technical documentation.
Rated voltage: 3.6/6 kV.
Technical dimensions, available cross-sections, prices and delivery times are subject to separate enquiry.
The technical values of the 1.8/3 kV version must not automatically be applied to this variant.
NSGAFöu (GHöuf) 1.8/3 kV – Cable Sizes & Technical Data
Complete reference range of flexible single-core rubber cables with tinned copper conductors, EPR insulation and polychloroprene outer sheath, including conductor construction, copper content, cable dimensions, current ratings and bending radii.
Complete Cable Size Range
| Cable Size (mm²) | Copper Content (kg/km) | Approx. Conductor Construction (n × mm) | Approx. Outer Diameter (mm) | Current Rating in Air (A) | Approx. Cable Weight (kg/km) |
|---|---|---|---|---|---|
| Small Cross-Section Single-Core Cables | |||||
| 1x1.5 | 14.4 | 30 × 0.26 | 6.5 | 30 | 60 |
| 1x2.5 | 24.0 | 50 × 0.26 | 7.0 | 41 | 70 |
| 1x4 | 38.4 | 56 × 0.31 | 7.5 | 55 | 90 |
| 1x6 | 57.6 | 84 × 0.31 | 8.5 | 70 | 120 |
| 1x10 | 96.0 | 80 × 0.41 | 10.0 | 98 | 180 |
| Medium Cross-Section Single-Core Cables | |||||
| 1x16 | 153.6 | 126 × 0.41 | 11.0 | 132 | 250 |
| 1x25 | 240.0 | 196 × 0.41 | 13.0 | 176 | 390 |
| 1x35 | 336.0 | 276 × 0.41 | 14.0 | 218 | 470 |
| 1x50 | 480.0 | 396 × 0.41 | 15.5 | 276 | 625 |
| 1x70 | 672.0 | 360 × 0.51 | 17.0 | 347 | 880 |
| 1x95 | 912.0 | 475 × 0.51 | 19.5 | 416 | 1190 |
| Large Cross-Section Single-Core Cables | |||||
| 1x120 | 1152.0 | 608 × 0.51 | 21.5 | 488 | 1430 |
| 1x150 | 1440.0 | 756 × 0.51 | 23.0 | 566 | 1750 |
| 1x185 | 1776.0 | 925 × 0.51 | 25.0 | 644 | 2160 |
| 1x240 | 2304.0 | 1221 × 0.51 | 28.0 | 775 | 2534 |
| 1x300 | 2880.0 | 1530 × 0.51 | 32.5 | 898 | 3178 |
All conductor construction values, copper content, cable dimensions, current ratings and cable weights are reproduced from the reference datasheet. Current ratings apply to the stated reference condition of installation in air. Ambient temperature, grouping and other rating conditions are not specified in the source documentation.
Minimum Bending Radius by Cable Size
| Cable Size (mm²) | Approx. Outer Diameter (mm) | Fixed / Single Bend 6 × D (mm) | During Bending 10 × D (mm) |
|---|---|---|---|
| 1x1.5 | 6.5 | 39 | 65 |
| 1x2.5 | 7.0 | 42 | 70 |
| 1x4 | 7.5 | 45 | 75 |
| 1x6 | 8.5 | 51 | 85 |
| 1x10 | 10.0 | 60 | 100 |
| 1x16 | 11.0 | 66 | 110 |
| 1x25 | 13.0 | 78 | 130 |
| 1x35 | 14.0 | 84 | 140 |
| 1x50 | 15.5 | 93 | 155 |
| 1x70 | 17.0 | 102 | 170 |
| 1x95 | 19.5 | 117 | 195 |
| 1x120 | 21.5 | 129 | 215 |
| 1x150 | 23.0 | 138 | 230 |
| 1x185 | 25.0 | 150 | 250 |
| 1x240 | 28.0 | 168 | 280 |
| 1x300 | 32.5 | 195 | 325 |
Minimum bending radii are calculated from the published approximate outer diameter using the specified factors of 6 × D for fixed or single-bend installation and 10 × D during bending. Actual cable diameter must be used for final installation calculations.
Electrical Characteristics
| Parameter | Reference Value |
|---|---|
| Rated Voltage U0 | 1,800 V |
| Rated Voltage U | 3,000 V |
| Rated Voltage U0/U | 1.8/3 kV |
| AC Test Voltage | 6,000 V AC |
| Conductor Material | Tinned Copper |
| Conductor Class | Class 5 Flexible |
| Conductor Standard | DIN EN 60228 |
| Nominal Cross-Section Range | 1.5–300 mm² |
| Current Rating in Air | 30–898 A, Depending on Cross-Section |
| Maximum Short-Circuit Temperature | +200°C |
| Maximum Short-Circuit Duration | 5 Seconds |
| DC Conductor Resistance at 20°C | Not Specified in Reference Datasheet |
| Insulation Resistance | Not Specified |
| Capacitance | Not Specified |
| Inductance | Not Specified |
| Test Voltage Duration | Not Specified |
Temperature Characteristics
| Operating Condition | Minimum Temperature | Maximum Temperature |
|---|---|---|
| Temperature During Bending | -25°C | +80°C |
| Fixed Installation Temperature | Not Specified | Not Specified |
| Continuous Conductor Operating Temperature | Not Specified | Not Specified |
| Short-Circuit Temperature | Not Applicable | +200°C |
| Short-Circuit Duration | Not Applicable | 5 Seconds |
The specified temperature range of -25°C to +80°C relates to bending conditions. It must not automatically be interpreted as a separately declared continuous conductor operating temperature range.
Cable Construction Layers
| Layer | Component | Material / Construction |
|---|---|---|
| 1 | Conductor | Fine-Stranded Tinned Copper, Class 5 |
| 2 | Conductor Wrapping | Aluminium-Polyester Foil (Alu-PT) |
| 3 | Insulation | Ethylene Propylene Rubber Compound (EPR) |
| 4 | Outer Sheath | Black Polychloroprene Rubber |
Conductor Stranding Overview
| Nominal Cross-Section Range | Approx. Individual Wire Diameter | Conductor Construction |
|---|---|---|
| 1.5–2.5 mm² | 0.26 mm | Class 5 Tinned Copper |
| 4–6 mm² | 0.31 mm | Class 5 Tinned Copper |
| 10–50 mm² | 0.41 mm | Class 5 Tinned Copper |
| 70–300 mm² | 0.51 mm | Class 5 Tinned Copper |
Mechanical & Environmental Properties
| Property | Standard / Reference Value | Status |
|---|---|---|
| Conductor Flexibility | DIN EN 60228 Class 5 | Specified |
| Oil Resistance | EN 60811-2-1 | Specified |
| Abrasion Resistance | Polychloroprene Sheath | Specified |
| Minimum Fixed Bending Radius | 6 × D | Specified |
| Minimum Radius During Bending | 10 × D | Specified |
| Temperature During Bending | -25°C to +80°C | Specified |
| UV Resistance | Not Specified | Requires Verification |
| Ozone Resistance | Not Specified | Requires Verification |
| Water Immersion Resistance | Not Specified | Requires Verification |
| Continuous Dynamic Flexing | Not Specified | Requires Verification |
| Maximum Installation Tensile Load | Not Specified | Requires Verification |
| Outer Sheath Colour | Black | Specified |
Fire Performance & Certification
| Property | Standard / Reference | Declared Performance |
|---|---|---|
| Single-Cable Flame Retardancy | EN 60332-1-2 | Specified |
| Bunched Cable Flame Retardancy | IEC 60332-3 Series | Not Declared |
| CPR Reaction to Fire | EN 50575 / EN 13501-6 | Not Specified |
| Low Smoke | EN IEC 61034-2 | Not Declared |
| Halogen-Free Performance | EN IEC 60754 Series | Not Declared |
| Fire-Resistant Circuit Integrity | IEC 60331 Series | Not Declared |
| Railway Fire Safety Classification | EN 45545-2 | Not Specified |
Installation & Application Conditions
| Application / Installation Method | Reference Status |
|---|---|
| Railway Vehicle Electrical Installations | Specified Application |
| Bus Electrical Installations | Specified Application |
| Dry Indoor Locations | Specified Application |
| Switchboards | Specified Application |
| Distribution Equipment up to 1,000 V | Specified Application |
| Short-Circuit Protection Applications | Specified Application |
| Earthing Applications | Specified Application |
| Outdoor Installation | Not Specified |
| Directly Buried Installation | Not Specified |
| Permanent Water Immersion | Not Specified |
| Battery Energy Storage Systems | Project-Specific Verification Required |
| Continuous Dynamic Flexing | Not Specified |
Applicable Standards
| Standard | Application |
|---|---|
| DIN VDE 0250-602 | Special Rubber Cable Construction |
| DIN EN 60228 | Conductors of Insulated Cables, Class 5 |
| EN 60811-2-1 | Oil Resistance Test, as Referenced in Original Datasheet |
| EN 60332-1-2 | Vertical Flame Propagation Test for a Single Insulated Wire or Cable |
Available Voltage Variants
| Cable Type | Rated Voltage | Cross-Section Range | Technical Data Status |
|---|---|---|---|
| NSGAFöu (GHöuf) | 1.8/3 kV | 1.5–300 mm² | Covered by Reference Datasheet |
| NSGAFöu | 3.6/6 kV | On Request | Separate Technical Confirmation Required |