Potraži kabel

Select a cable or enter another designation.


H07V2-K 450/750 V

Flexible Copper Conductor | Heat-Resistant PVC Insulation | 90°C

Product Description

H07V2-K is a single-core flexible low voltage cable with a Class 5 copper conductor and heat-resistant PVC insulation, designed for protected electrical installations and internal wiring of electrical equipment. The cable has a rated voltage of 450/750 V and a maximum conductor operating temperature of 90°C.

Primjene

  • Electrical installations in protective conduits.
  • Installation on and under plaster in dry rooms.
  • Installation in closed electrical installation ducts.
  • Internal wiring of switchgear and distribution boxes.
  • Protected wiring of lighting equipment.
  • Electrical installations requiring a conductor operating temperature of up to 90°C.

Direct installation in cable trays is not permitted. For protected lighting installations, the datasheet specifies nominal voltages up to 1000 V AC or 750 V DC against earth.

Cable Construction

Component Description
Conductor Flexible copper, Class 5 according to EN 60228
Insulation Heat-resistant PVC compound, type TI 3
Number of cores Single core
Cross-section range 1.5–240 mm²

Technical Characteristics

Parameter Value
Rated voltage U₀/U 450/750 V
Test voltage 2.5 kV
Bending radius 6 × cable outer diameter
Maximum conductor temperature +90°C
Maximum short-circuit temperature +160°C

Standardi

  • EN 50525-2-31 – Cable construction
  • IEC 60227 – PVC-insulated cables
  • EN 60228 – Conductors
  • EN 50525-1 – Core identification
  • DIN VDE 0298-4 – Current-carrying capacity

Available Insulation Colours

Crna Blue Brown Grey Orange Pink Red Turquoise Violet White Green/Yellow

Availability of individual cross-sections and colours is subject to confirmation.

H07V2-K – Technical Data & Dimensions

450/750 V | Flexible Class 5 Copper | Heat-Resistant PVC Insulation | 90°C

Electrical and Physical Characteristics

Nominal Cross-section
mm²
Max. DC Resistance at 20°C
Ω/km
Insulation Thickness
mm
Outer Diameter
mm
Metal Weight
kg/km
Cable Weight
kg/km
1 × 1.513.30.73.014.422
1 × 2.57.980.83.724.035
1 × 44.950.84.338.452
1 × 63.300.85.057.674
1 × 101.9101.06.596.0122
1 × 161.2101.07.8—186
1 × 250.7801.29.8240.0290
1 × 350.5541.210.9336.0392
1 × 500.3861.412.8480.0557
1 × 700.2721.414.5672.0760
1 × 950.2061.616.7912.01028
1 × 1200.1611.619.01152.01286
1 × 1500.1291.820.71440.01603
1 × 1850.1062.023.01776.01978
1 × 2400.08012.226.12304.02557

Outer diameters and cable weights are approximate. Metal weight for 1 × 16 mm² is subject to confirmation.

Current-Carrying Capacity at 30°C

Nominal Cross-section
mm²
Installation Conduit in Thermally Insulated Wall Installation Conduit in Wall Open Air
2 Loaded Cores
A
3 Loaded Cores
A
2 Loaded Cores
A
3 Loaded Cores
A
1 Loaded Core
A
1 × 1.51917232024
1 × 2.52623312832
1 × 43531423742
1 × 64540544854
1 × 106154756673
1 × 1681731008898
1 × 2510695133117129
1 × 35131117164144158
1 × 50158141198175198
1 × 70200179253222245
1 × 95241216306269292
1 × 120278249354312344
1 × 150318285393342391
1 × 185362324449384448
1 × 240424380528450528
1 × 300*486435603514608

Current-carrying capacities according to DIN VDE 0298-4. Maximum conductor operating temperature: 90°C. Ambient temperature: 30°C. Actual permissible current depends on installation conditions and applicable correction factors. Open-air reference values do not imply permission for direct installation in cable trays.

*Current-carrying capacity for 300 mm² is provided for reference only. Physical dimensions, cable weight and product availability are subject to confirmation.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


KOLEKCIJA KABELA UNIMA

Istražite našu ponudu kabela

Otkrijte vrste kabela, tehničke specifikacije i rješenja za svoje projekte.

80 Cable Types Available