H07Z1-K 450/750 V
Flexible Copper Conductor | Halogen-Free HFFR Insulation | B2ca-s1,d1,a1
Product Description
H07Z1-K is a single-core, flexible low voltage cable with a Class 5 copper conductor and halogen-free, flame-retardant thermoplastic insulation (HFFR). Designed for electrical installations requiring enhanced reaction-to-fire performance, the cable has a rated voltage of 450/750 V and a CPR classification of B2ca-s1,d1,a1.
Primjene
- Internal wiring of lighting equipment and electrical devices.
- Switchgear cabinets and distribution boxes.
- Installation in conduits and closed installation ducts.
- Installation on, in and under plaster.
- Buildings with a high density of occupants or valuable assets.
- Electrical installations in dry rooms.
Cable Construction
| Component | Description |
|---|---|
| Conductor | Flexible copper, Class 5 according to EN 60228 |
| Insulation | Halogen-free thermoplastic compound, type TI 7 according to EN 50363-7 |
| UV resistance | UV-resistant insulation |
| Number of cores | Single core |
| Cross-section range | 1.5–240 mm² |
Technical Characteristics
| Parameter | Value |
|---|---|
| Rated voltage U₀/U | 450/750 V |
| Test voltage | 2.5 kV |
| CPR classification | B2ca-s1,d1,a1 |
| Minimum bending radius | 5 × cable outer diameter |
| Minimum installation temperature | +5°C |
| Ambient temperature range | −35°C to +35°C |
| Maximum conductor temperature | +70°C |
| Maximum short-circuit temperature | +160°C |
Standardi
- EN 50525-3-31 – Cable construction
- EN 60228 – Conductors
- EN 50363-7 – Insulation compound TI 7
- EN 60754-1 and EN 60754-2 – Halogen-free characteristics
- EN 50575 – Construction Products Regulation
- EN 13501-6 – Reaction-to-fire classification
- EN 50525-1 – Core identification
- DIN VDE 0298-4 – Current-carrying capacity
Available Insulation Colours
Availability of individual cross-sections and colours is subject to confirmation.
H07Z1-K – Technical Data & Dimensions
450/750 V | Flexible Class 5 Copper | HFFR Insulation | B2ca-s1,d1,a1
Electrical and Physical Characteristics
| Nominal Cross-section mm² |
Max. DC Resistance at 20°C Ω/km |
Insulation Thickness mm |
Min. Outer Diameter mm |
Max. Outer Diameter mm |
Metal Weight kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|---|
| 1 × 1.5 | 13.3 | 0.7 | 2.8 | 3.4 | 14.4 | 22 |
| 1 × 2.5 | 7.98 | 0.8 | 3.4 | 4.1 | 24.0 | 34 |
| 1 × 4 | 4.95 | 0.8 | 3.9 | 4.8 | 38.4 | 51 |
| 1 × 6 | 3.30 | 0.8 | 4.4 | 5.3 | 57.6 | 72 |
| 1 × 10 | 1.910 | 1.0 | 5.7 | 6.8 | 96.0 | 119 |
| 1 × 16 | 1.210 | 1.0 | 6.7 | 8.1 | 153.6 | 181 |
| 1 × 25 | 0.780 | 1.2 | 8.4 | 10.2 | 240.0 | 280 |
| 1 × 35 | 0.554 | 1.2 | 9.7 | 11.7 | 336.0 | 383 |
| 1 × 50 | 0.386 | 1.4 | 11.5 | 13.9 | 480.0 | 545 |
| 1 × 70 | 0.272 | 1.4 | 13.2 | 16.0 | 672.0 | 747 |
| 1 × 95 | 0.206 | 1.6 | 15.1 | 18.2 | 912.0 | 1012 |
| 1 × 120 | 0.161 | 1.6 | 16.7 | 20.2 | 1152.0 | 1263 |
| 1 × 150 | 0.129 | 1.8 | 18.6 | 22.5 | 1440.0 | 1579 |
| 1 × 185 | 0.106 | 2.0 | 20.6 | 24.9 | 1776.0 | 1948 |
| 1 × 240 | 0.0801 | 2.2 | 23.5 | 28.4 | 2304.0 | 2519 |
Outer diameters and cable weights are approximate. Metal weights are stated as specified in the technical datasheet.
Current-Carrying Capacity at 30°C
| Nominal Cross-section mm² |
Thermally Insulated Wall | Electrical Installation Conduit | On the Wall | |||
|---|---|---|---|---|---|---|
| 2 Cores A |
3 Cores A |
2 Cores A |
3 Cores A |
2 Cores A |
3 Cores A |
|
| 1 × 1.5 | 19 | 17 | 23 | 20 | 24 | 22 |
| 1 × 2.5 | 26 | 23 | 31 | 28 | 33 | 30 |
| 1 × 4 | 35 | 31 | 42 | 37 | 45 | 40 |
| 1 × 6 | 45 | 40 | 54 | 48 | 58 | 52 |
| 1 × 10 | 61 | 54 | 75 | 66 | 80 | 71 |
| 1 × 16 | 81 | 73 | 100 | 88 | 107 | 96 |
| 1 × 25 | 106 | 95 | 133 | 117 | 138 | 119 |
| 1 × 35 | 131 | 117 | 164 | 144 | 171 | 147 |
| 1 × 50 | 158 | 141 | 198 | 175 | 209 | 179 |
| 1 × 70 | 200 | 179 | 235 | 222 | 269 | 229 |
| 1 × 95 | 241 | 216 | 306 | 269 | 328 | 278 |
| 1 × 120 | 278 | 249 | 354 | 312 | 382 | 322 |
| 1 × 150 | 318 | 285 | 393 | 342 | 441 | 371 |
| 1 × 185 | 362 | 324 | 449 | 384 | 506 | 424 |
| 1 × 240 | 424 | 380 | 528 | 450 | 599 | 500 |
Current-carrying capacities according to DIN VDE 0298-4, at an ambient temperature of 30°C. The 2-core and 3-core columns refer to the installation arrangement of single-core conductors, not multicore cable construction. Actual permissible current depends on installation conditions and applicable correction factors.