UNIMA CABLE | MEDIUM VOLTAGE POWER CABLES

EAXeCWB / EAXeCeWB – Aluminium Medium Voltage Power Cable

Single-core aluminium power distribution cables with XLPE insulation, copper wire screen, water-blocking layers and a polyethylene outer sheath. Designed for medium voltage distribution networks and industrial installations.

15–36 kV Aluminium Class 2 XLPE Insulation Copper Screen PE Sheath Water Blocking NBN HD 620

Product Overview

EAXeCWB and EAXeCeWB are single-core aluminium power distribution cables with extruded XLPE insulation and a screened construction.

The EAXeCWB design provides longitudinal water blocking at the metallic screen level through swelling tapes.

The EAXeCeWB design additionally incorporates an aluminium moisture barrier bonded to the polyethylene outer sheath, providing transverse water blocking.

Both cable types feature a round stranded aluminium conductor, copper wire screen with counter-helix copper tape, and a polyethylene outer sheath with good weather and mechanical impact resistance.

Key Technical Features

15–36 kVVoltage Range
50–1000 mm²Conductor Range
Class 2Aluminium Conductor
+90°COperating Temperature

Cable Variants

EAXeCWB

Longitudinal Water Blocking

Water-blocking tapes at screen level with polyethylene outer sheath.

EAXeCeWB

Longitudinal and Transverse Water Blocking

Additional aluminium tape bonded to the PE outer sheath for radial moisture protection.

Construction & Technical Properties

Cable Construction

ConductorAluminium
Conductor ClassClass 2, Stranded
Conductor ShapeRound
Number of Cores1
Conductor ScreenExtruded Semiconducting XLPE
InsulationExtruded XLPE
Insulation ScreenExtruded Semiconducting Layer
Water BlockingSwelling Tapes
Metallic ScreenCopper Wires and Counter-Helix Copper Tape
Moisture BarrierBonded Aluminium Tape (EAXeCeWB)
Outer SheathPE
Sheath ColourRed or Black, Depending on Variant

Electrical & Mechanical Data

Voltage Range15–36 kV
Conductor Range50–1000 mm²
Screen Cross-Section16–35 mm²
Insulation Thickness3.6–8.8 mm
Max. Conductor Temp.+90°C
Short-Circuit Temp.+250°C
Longitudinal WatertightnessYes
Transverse WatertightnessEAXeCeWB
Weather ResistanceGood
Mechanical Impact ResistanceGood
Outdoor InstallationYes

Typical Applications

Medium Voltage Distribution Networks
Industrial Power Distribution
Cable Channels
Cable Ducts and Tubes
Outdoor Installations
Installations With or Without Protection

Applicable Standards

NBN HD 620 / 10B-A – Reference cable construction standard.
13782-99HH – Product specification.
NBN HD 620 / 10B-B, 10B-C and 10B-D – Reduced insulation constructions, depending on selected variant.

Special Versions

Halogen-free versions EAXeCGB and EAXeCeGB may be available on request. Reduced insulation thickness constructions can also be requested for specific projects.
Technical Note: Cable construction, voltage rating, sheath colour and insulation thickness depend on the selected variant. Technical parameters and applicable standards must be confirmed for the supplied product. CPR classification is not specified in the reference documentation.
UNIMA CABLE | TECHNICAL DIMENSIONS

EAXeCWB / EAXeCeWB – Cable Sizes & Technical Data

52 reference configurations with aluminium conductors, copper screens, insulation thickness, sheath thickness, maximum outer diameter and approximate cable weight per kilometre.

52Reference Configurations
50–1000 mm²Conductor Range
15–36 kVVoltage Range
Al Class 2Aluminium Conductor

Available Cable Sizes

Tip kabela Voltage Size (mm²) Insulation (mm) Screen (mm²) Sheath (mm) Max. Diameter (mm) Cable Weight (kg/km)
15 kV – Insulation 3.6 mm
EAXeCWB15 kV1x50/163.6161.8–700
EAXeCWB15 kV1x95/253.6252.632950
EAXeCWB RGE HD620S2-10B-B15 kV1x150/253.6252.9351180
EAXeCWB ROUGE HD620S2-10B-B15 kV1x150/253.6252.9351200
EAXeCeWB15 kV1x150/253.6252.9361250
EAXeCWB15 kV1x240/253.6253.1401600
EAXeCeWB15 kV1x240/253.6253.1401675
EAXeCWB ELECT15 kV1x400/253.6253.3452200
EAXeCeWB15 kV1x400/253.6253.3462300
EAXeCWB15 kV1x630/353.6353.5553200
EAXeCeWB15 kV1x630/353.6353.5563300
8.7/15 kV and 15 kV – Insulation 4.5 mm
EAXeCWB np8.7/15 kV1x50/164.5162.633940
EAXeCWB np8.7/15 kV1x95/254.5252.6361290
EAXeCeWB np8.7/15 kV1x95/254.5252.6361290
EAXeCWB Black15 kV1x150/254.5252.9401350
EAXeCWB Black15 kV1x240/254.5253.1441750
EAXeCeWB np8.7/15 kV1x240/254.5253.1442010
EAXeCWB Black15 kV1x400/354.5353.3502450
EAXeCeWB np15 kV1x400/354.5353.3502500
EAXeCWB np8.7/15 kV1x400/354.5353.3502760
EAXeCWB np8.7/15 kV1x630/354.5353.5563710
EAXeCWB np8.7/15 kV1x1000/354.5353.7685370
12/20 kV and 20 kV – Insulation 5.5 mm
EAXeCWB np12/20 kV1x50/165.5162.6351030
EAXeCWB np12/20 kV1x95/255.5252.7391410
EAXeCWB np12/20 kV1x150/255.5253.0421710
EAXeCWB np12/20 kV1x240/255.5253.1462140
EAXeCWB np ELIA20 kV1x400/355.5353.3522600
EAXeCWB np12/20 kV1x400/355.5353.3522900
EAXeCWB np12/20 kV1x630/355.5353.5583880
EAXeCWB np12/20 kV1x1000/355.5353.8715600
36 kV – Insulation 6.0 mm
EAXeCWB ELIA36 kV1x400/256.0252.4502400
EAXeCWB ELIA36 kV1x630/256.0252.6583400
EAXeCWB ELIA36 kV1x1000/256.0253.0694800
EAXeCWB 10B-D36 kV1x400/256.0253.6522580
EAXeCeWB 10B-D36 kV1x400/256.0253.6522680
EAXeCeWB 10B-D36 kV1x630/256.0253.860To be confirmed*
EAXeCWB 10B-D36 kV1x630/256.0253.8603550
18/30 kV and 30 kV – Insulation 8.0 mm
EAXeCWB np18/30 kV1x50/168.0162.8411330
EAXeCWB np18/30 kV1x95/258.0252.9441730
EAXeCWB np18/30 kV1x150/258.0253.2472080
EAXeCWB 10B-A30 kV1x240/258.0253.3512180
EAXeCWB np18/30 kV1x240/258.0253.3512540
EAXeCWB np18/30 kV1x400/358.0353.5573350
EAXeCWB np18/30 kV1x630/358.0353.7634380
EAXeCWB np18/30 kV1x1000/358.0354.0766190
20.8/36 kV and 36 kV – Insulation 8.8 mm
EAXeCWB np20.8/36 kV1x50/168.8162.8–1410
EAXeCeWB np20.8/36 kV1x95/258.8252.9–1830
EAXeCWB 10B-A36 kV1x150/258.8253.2491880
EAXeCWB np20.8/36 kV1x150/258.8253.2492190
EAXeCeWB np20.8/36 kV1x240/258.8253.4532680
EAXeCWB Black20.8/36 kV1x400/358.8353.6–3510
EAXeCWB np20.8/36 kV1x630/358.8353.8654550
EAXeCWB np20.8/36 kV1x1000/358.8354.0786360
Technical Note: All dimensions and cable weights are indicative. Cable weights are expressed in kg/km and exclude drums and packaging. Separate aluminium and copper weights are not specified in the reference documentation. Missing or zero diameter values are displayed as a dash.
Data Verification: *The cable weight for EAXeCeWB 36 kV 1x630/25, insulation 6.0 mm, requires confirmation. Maximum operating voltage values must be confirmed for each selected configuration. All cable specifications are subject to confirmation for the supplied product.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


KOLEKCIJA KABELA UNIMA

Istražite našu ponudu kabela

Otkrijte vrste kabela, tehničke specifikacije i rješenja za svoje projekte.

80 Cable Types Available