1-CYKY – PVC Insulated Copper Power Cable
Low voltage power cable with copper conductors, PVC insulation and a black PVC outer sheath, designed for fixed electrical installations, underground distribution and industrial power supply.
Product Overview
1-CYKY is a low voltage power cable manufactured with solid or stranded copper conductors, PVC DIV 1 insulation and a PVC DMV 1 outer sheath.
The cable is designed for fixed installation in electrical distribution networks, industrial plants, power stations and other electrical installations.
Suitable for installation underground, in cable ducts, on support brackets and in dry or wet conditions where mechanical damage and tensile strain are not expected.
The reference product range includes four-core cables and configurations with reduced cross-section conductors, available in various round and sector-shaped conductor constructions.
Key Technical Features
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Core Identification
Typical Applications
Applicable Standards
HD 603 S1 – Distribution cables of rated voltage 0.6/1 kV.
EN 60228 – Conductors of insulated cables.
HD 308 S2 – Identification of cable cores.
1-CYKY – Cable Sizes & Technical Data
22 reference cable configurations with conductor construction, electrical resistance, current capacity, outer diameter, copper weight and total cable weight.
Available Cable Sizes
| Size (mm²) | Conductor Construction | Resistance 20°C (Ω/km) | Current Air (A) | Current Ground (A) | Outer Diameter (mm) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|---|
| 4x10 | RE | 1.830 | 59 | 78 | 19.1 | 384 | 690 |
| 4x16 | RM/RE | 1.150 | 78 | 107 | 22.0 | 614 | 1050 |
| 4x25 | RM/RE | 0.727 | 105 | 132 | 27.8 | 960 | 1550 |
| 4x35 | RM/RE | 0.524 | 129 | 159 | 30.5 | 1344 | 1962 |
| 4x50 | RE/SE | 0.387 | 157 | 188 | 29.9 | 1920 | 2180 |
| 4x70 | RE/SE | 0.268 | 199 | 232 | 33.2 | 2688 | 2990 |
| 3x95+50 | SM/RM(SM) | 0.193/0.387 | 246 | 280 | 38.5 | 3216 | 3900 |
| 3x95+70 | SM/RE | 0.193/0.268 | 246 | 280 | 38.5 | 3408 | 4400 |
| 4x95 | SM | 0.193 | 246 | 280 | 40.0 | 3648 | 4600 |
| 3x120+50 | SM/RM(SM) | 0.153/0.387 | 285 | 318 | 41.0 | 3936 | 4900 |
| 3x120+70 | SM/RE(RM) | 0.153/0.268 | 285 | 318 | 43.0 | 4128 | 5150 |
| 3x120+70 | SM/SM | 0.153/0.268 | 285 | 318 | 40.0 | 4128 | 5100 |
| 4x120 | SM | 0.153 | 285 | 318 | 43.0 | 4608 | 5060 |
| 3x150+70 | SM/RE(RM) | 0.124/0.268 | 326 | 359 | 46.0 | 4992 | 6150 |
| 3x150+70 | SM/SM | 0.124/0.268 | 326 | 359 | 45.5 | 4992 | 6100 |
| 4x150 | SM | 0.124 | 326 | 359 | 48.0 | 5760 | 6800 |
| 3x185+95 | SM/RM | 0.0991/0.193 | 374 | 406 | 50.5 | 6240 | 7600 |
| 3x185+95 | SM/SM | 0.0991/0.193 | 374 | 406 | 49.5 | 6240 | 7600 |
| 4x185 | SM | 0.0991 | 374 | 406 | 52.5 | 7104 | 8400 |
| 3x240+120 | SM/RM | 0.0991/0.153* | 445 | 473 | 58.0 | 8064 | 9800 |
| 3x240+120 | SM/SM | 0.0991/0.153* | 445 | 473 | 57.0 | 8064 | 9800 |
| 4x240 | SM | 0.0754 | 445 | 473 | 60.0 | 9216 | 11000 |
Conductor Construction Codes
RM: Round stranded conductor.
SE: Sector-shaped solid conductor.
SM: Sector-shaped stranded conductor.
*Values requiring confirmation: The reference resistance of 0.0991 Ω/km for the main conductor in both 3x240+120 configurations requires technical confirmation before use in engineering calculations.