NFA2X – Aerial Bundled Aluminium Cable (ABC)
Low voltage aerial bundled power cable with stranded aluminium conductors and PE TIX 2 insulation, designed for overhead electricity distribution and above-ground service connections.
Product Overview
NFA2X is a low voltage aerial bundled cable designed for overhead electrical distribution networks in urban, suburban and rural areas.
Both phase and neutral conductors are manufactured from Class 2 stranded aluminium according to EN 60228 and individually insulated with PE TIX 2 compound.
The cable is suitable for supplying remote facilities, villages and temporary or permanent installations, including above-ground connections to residential buildings.
The product range includes two-core, three-core, four-core and five-core configurations, as well as variants with additional conductors.
Key Technical Features
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Typical Applications
Applicable Standards
HD 626 S1 – Overhead distribution cables of rated voltage 0.6/1 kV.
EN 60228 – Conductors of insulated cables.
HD 626-1, Method A – Core identification by ridges.
NFA2X – Cable Sizes & Technical Data
46 reference cable configurations with conductor resistance, current capacity in air, aluminium weight, total cable weight and standard packing information.
Available Cable Sizes
| Size (mm²) | Resistance 20°C (Ω/km) | Current Air (A) | Aluminium Weight (kg/km) | Cable Weight (kg/km) | Drum Type | Drum Length (m) |
|---|---|---|---|---|---|---|
| 2-Core Cables | ||||||
| 2x16 | 1.91 | 83 | 92.8 | 131 | N9 | 1000 |
| 2x25 | 1.20 | 107 | 145 | 192 | N12 | 1000 |
| 2x35 | 0.868 | 132 | 203 | 261 | N12 | 1000 |
| 2x50 | 0.641 | 165 | 290 | 346 | N13 | 1000 |
| 2x70 | 0.443 | 213 | 406 | 530 | N15 | 1000 |
| 2x95 | 0.320 | 258 | 551 | 691 | N16 | 1000 |
| 2x120 | 0.253 | 300 | 696 | 847 | N16 | 1000 |
| 2x150 | 0.206 | 344 | 870 | 1030 | N15 | 500 |
| 3-Core Cables | ||||||
| 3x16 | 1.91 | 83 | 139.2 | 196 | N11 | 1000 |
| 3x25 | 1.20 | 107 | 217.5 | 288 | N12 | 1000 |
| 4-Core Cables and Additional Conductor Configurations | ||||||
| 4x16 | 1.91 | 83 | 185.6 | 261 | N11 | 1000 |
| 4x25 | 1.200 | 107 | 290 | 384 | N13 | 1000 |
| 4x25+16 | 1.200/1.910 | 107 | 336.4 | 449 | N13 | 1000 |
| 4x25+2x16 | 1.200/1.910 | 107 | 382.8 | 514 | N13 | 1000 |
| 4x35 | 0.868 | 132 | 406 | 523 | N12 | 500 |
| 4x35+16 | 0.868/1.910 | 132 | 452.4 | 589 | N12 | 500 |
| 4x35+2x16 | 0.868/1.910 | 132 | 498.8 | 654 | N12 | 500 |
| 4x35+25 | 0.868/1.200 | 132 | 478.5 | 595 | N12 | 500 |
| 4x50 | 0.641 | 165 | 580 | 692 | N13 | 500 |
| 4x50+25 | 0.641/1.200 | 165 | 652.5 | 788 | N13 | 500 |
| 4x50+35 | 0.641/0.868 | 165 | 681.5 | 823 | N13 | 500 |
| 4x50+2x16 | 0.614/1.910* | 165 | 672.8 | 860 | N14 | 500 |
| 4x50+2x25 | 0.641/1.200 | 165 | 725 | 884 | N14 | 500 |
| 4x50+2x35 | 0.641/0.868 | 165 | 783 | 954 | N14 | 500 |
| 4x70 | 0.443 | 205 | 812 | 935 | N14 | 500 |
| 4x70+16 | 0.443/1.910 | 205 | 858.4 | 1000 | N14 | 500 |
| 4x70+2x16 | 0.443/1.910 | 205 | 904.8 | 1066 | N14 | 500 |
| 4x70+25 | 0.443/1.200 | 205 | 884.5 | 1031 | N13 | 500 |
| 4x70+2x25 | 0.443/1.200 | 205 | 957 | 1066 | N14 | 500 |
| 4x70+35 | 0.443/0.868 | 205 | 913.5 | 1127 | N15 | 500 |
| 4x70+2x35 | 0.443/0.868 | 205 | 1015 | 1197 | N15 | 500 |
| 4x95 | 0.320 | 258 | 1102 | 1296 | N15 | 500 |
| 4x95+25 | 0.320/1.200 | 258 | 1174.5 | 1392 | N15 | 500 |
| 4x95+35 | 0.320/0.868 | 258 | 1203.5 | 1427 | N15 | 500 |
| 4x95+2x16 | 0.320/1.910 | 258 | 1194.8 | 1455 | N15 | 500 |
| 4x95+2x25 | 0.320/1.200 | 258 | 1247 | 1488 | N15 | 500 |
| 4x95+2x35 | 0.320/0.868 | 258 | 1305 | 1558 | N15 | 500 |
| 4x120 | 0.253 | 300 | 1392 | 1635 | N16 | 500 |
| 4x120+25 | 0.253/1.200 | 300 | 1464.5 | 1731 | N16 | 500 |
| 4x120+35 | 0.253/0.868 | 300 | 1493.5 | 1766 | N16 | 500 |
| 4x120+2x25 | 0.253/1.200 | 300 | 1537 | 1827 | N16 | 500 |
| 4x120+2x35 | 0.253/0.868 | 300 | 1595 | 1896 | N16 | 500 |
| 4x150 | 0.206 | 344 | 1740 | 1867 | N18 | 500 |
| 4x185 | 0.164 | 395 | 2146 | 2362 | N20 | 500 |
| 5-Core Cables | ||||||
| 5x16 | 1.910 | 83 | 232 | 311 | N12 | 1000 |
| 5x25 | 1.200 | 107 | 362.5 | 362.5* | N12 | 1000 |
*Values requiring confirmation: The reference resistance for 4x50+2x16 and the total cable weight for 5x25 require technical confirmation before use in engineering or logistics calculations.