NA2XS(F)2Y – Medium Voltage Aluminium Power Cable
Single-core medium voltage power cable with compact stranded aluminium conductor, XLPE insulation, copper wire screen, longitudinal water blocking and a mechanically resistant black polyethylene outer sheath.
Product Overview
NA2XS(F)2Y is a single-core medium voltage power cable designed for fixed installation in electrical distribution networks, substations, power stations and industrial facilities.
The cable features a compact stranded aluminium conductor with XLPE DIX8 insulation and extruded inner and outer semiconducting layers for electrical field control.
A concentric copper wire screen with a counter-wound copper tape provides electrical screening. Semiconductive water-swellable tape prevents longitudinal water propagation within the cable.
The black PE DMP2 outer sheath provides enhanced mechanical protection during and after installation. The cable is suitable for underground installations, cable ducts, indoor and outdoor environments, and installation in water.
Key Technical Features
Construction & Technical Properties
Cable Construction
Electrical & Mechanical Data
Voltage Ratings & Test Voltages
| Rated Voltage U0/U | Maximum System Voltage | AC Test Voltage (5 min) |
|---|---|---|
| 6/10 kV | 12 kV | 21 kV |
| 12/20 kV | 24 kV | 42 kV |
| 18/30 kV | 36 kV | 63 kV |
| 20.8/36 kV | 42 kV | 73.5 kV |
Typical Applications
Applicable Standards
DIN VDE 0276-620 – Medium voltage power cable specification.
IEC 60502-2 – Power cables with extruded insulation.
IEC 60228 – Conductors of insulated cables.
DIN VDE 0295 / HD 383 – Conductor classification.
NA2XS(F)2Y – Cable Sizes & Technical Data
48 cable configurations across four voltage ratings, with electrical characteristics, dimensional data, aluminium weight, copper weight and total cable weight per kilometre.
NA2XS(F)2Y 6/10 kV
Um: 12 kV | AC Test Voltage: 21 kV | Nominal XLPE Insulation: 3.4 mm | Nominal PE Sheath: 2.5 mm
| Size (mm²) | Outer Diameter (mm) | Resistance 20°C (Ω/km) | Current Air (A) | Current Ground (A) | Inductance (mH/km) | Aluminium Weight (kg/km) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 1x50/16 RM | 24–29 | 0.641 | 183 | 171 | 0.434 | 145 | 182 | 653 |
| 1x70/16 RM | 26–31 | 0.443 | 228 | 208 | 0.409 | 203 | 182 | 740 |
| 1x95/16 RM | 27–32 | 0.320 | 278 | 248 | 0.391 | 276 | 182 | 856 |
| 1x120/16 RM | 29–34 | 0.253 | 321 | 283 | 0.377 | 348 | 182 | 954 |
| 1x150/16 RM | 30–35 | 0.206 | 364 | 315 | 0.364 | 435 | 182 | 1100 |
| 1x150/25 RM | 30–35 | 0.206 | 364 | 315 | 0.364 | 435 | 283 | 1132 |
| 1x185/16 RM | 32–37 | 0.164 | 418 | 357 | 0.353 | 537 | 182 | 1250 |
| 1x185/25 RM | 32–37 | 0.164 | 418 | 357 | 0.353 | 537 | 283 | 1273 |
| 1x240/16 RM | 34–39 | 0.125 | 494 | 413 | 0.338 | 696 | 182 | 1400 |
| 1x240/25 RM | 34–39 | 0.125 | 494 | 413 | 0.338 | 696 | 283 | 1478 |
| 1x300/25 RM | 36–41 | 0.100 | 568 | 466 | 0.329 | 870 | 283 | 1684 |
| 1x400/35 RM | 40–45 | 0.0778 | 660 | 529 | 0.315 | 1160 | 394 | 2082 |
| 1x500/35 RM | 43–48 | 0.0605 | 767 | 602 | 0.306 | 1450 | 394 | 2445 |
NA2XS(F)2Y 12/20 kV
Um: 24 kV | AC Test Voltage: 42 kV | Nominal XLPE Insulation: 5.5 mm | Nominal PE Sheath: 2.5 mm
| Size (mm²) | Outer Diameter (mm) | Resistance 20°C (Ω/km) | Current Air (A) | Current Ground (A) | Inductance (mH/km) | Aluminium Weight (kg/km) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 1x50/16 RM | 28–33 | 0.641 | 185 | 172 | 0.465 | 145 | 182 | 810 |
| 1x70/16 RM | 30–35 | 0.443 | 231 | 210 | 0.438 | 203 | 182 | 907 |
| 1x95/16 RM | 31–36 | 0.320 | 280 | 251 | 0.419 | 276 | 182 | 1034 |
| 1x120/16 RM | 33–38 | 0.253 | 323 | 286 | 0.403 | 348 | 182 | 1139 |
| 1x150/16 RM | 34–39 | 0.206 | 366 | 319 | 0.389 | 435 | 182 | 1251 |
| 1x150/25 RM | 34–39 | 0.206 | 366 | 319 | 0.389 | 435 | 283 | 1324 |
| 1x185/16 RM | 36–41 | 0.164 | 420 | 361 | 0.377 | 537 | 182 | 1450 |
| 1x185/25 RM | 36–41 | 0.164 | 420 | 361 | 0.377 | 537 | 283 | 1479 |
| 1x240/16 RM | 39–44 | 0.125 | 496 | 417 | 0.361 | 696 | 182 | 1693 |
| 1x240/25 RM | 39–44 | 0.125 | 496 | 417 | 0.361 | 696 | 283 | 1698 |
| 1x300/25 RM | 41–46 | 0.100 | 569 | 471 | 0.350 | 870 | 283 | 1917 |
| 1x400/35 RM | 44–49 | 0.0778 | 660 | 535 | 0.335 | 1160 | 394 | 2336 |
| 1x500/35 RM | 47–52 | 0.0605 | 766 | 609 | 0.326 | 1450 | 394 | 2698 |
| 1x630/35 RM | 51–55 | 0.0469 | 890 | 675 | 0.301 | 1827 | 394 | 3166 |
NA2XS(F)2Y 18/30 kV
Um: 36 kV | AC Test Voltage: 63 kV | Nominal XLPE Insulation: 8.0 mm | Nominal PE Sheath: 2.5 mm
| Size (mm²) | Outer Diameter (mm) | Resistance 20°C (Ω/km) | Current Air (A) | Current Ground (A) | Inductance (mH/km) | Aluminium Weight (kg/km) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 1x50/16 RM | 33–38 | 0.641 | 187 | 174 | 0.496 | 145 | 182 | 1040 |
| 1x70/16 RM | 35–40 | 0.443 | 232 | 213 | 0.468 | 203 | 182 | 1151 |
| 1x95/16 RM | 36–41 | 0.320 | 282 | 254 | 0.447 | 276 | 182 | 1290 |
| 1x120/16 RM | 38–43 | 0.253 | 325 | 289 | 0.430 | 348 | 182 | 1409 |
| 1x150/25 RM | 39–44 | 0.206 | 367 | 322 | 0.415 | 435 | 283 | 1603 |
| 1x185/25 RM | 41–46 | 0.164 | 421 | 364 | 0.402 | 537 | 283 | 1771 |
| 1x240/25 RM | 43–48 | 0.125 | 496 | 422 | 0.384 | 696 | 283 | 2009 |
| 1x300/25 RM | 46–51 | 0.100 | 568 | 476 | 0.373 | 870 | 283 | 2704 |
| 1x400/35 RM | 49–54 | 0.0778 | 650 | 541 | 0.357 | 1160 | 394 | 2682 |
| 1x500/35 RM | 52–57 | 0.0605 | 764 | 616 | 0.346 | 1450 | 394 | 3069 |
| 1x630/35 RM | 56–62 | 0.0469 | 890 | 675 | 0.301 | 1827 | 394 | 3569 |
NA2XS(F)2Y 20.8/36 kV
Um: 42 kV | AC Test Voltage: 73.5 kV | Nominal XLPE Insulation: 8.8 mm | Nominal PE Sheath: 2.5 mm
| Size (mm²) | Outer Diameter (mm) | Resistance 20°C (Ω/km) | Current Air (A) | Current Ground (A) | Inductance (mH/km) | Aluminium Weight (kg/km) | Copper Weight (kg/km) | Cable Weight (kg/km) |
|---|---|---|---|---|---|---|---|---|
| 1x50/16 RM | 37–38.5 | 0.641 | 187 | 175 | – | 145 | 182 | 1100 |
| 1x70/16 RM | 37.6–40.5 | 0.443 | 232 | 214 | – | 203 | 182 | 1250 |
| 1x95/16 RM | 39.2–42 | 0.320 | 281 | 256 | – | 276 | 182 | 1400 |
| 1x120/16 RM | 40.7–44 | 0.253 | 323 | 290 | – | 348 | 182 | 1500 |
| 1x150/25 RM | 42–45.5 | 0.206 | 365 | 324 | – | 435 | 283 | 1750 |
| 1x185/25 RM | 43.6–47.5 | 0.164 | 418 | 366 | – | 537 | 283 | 1950 |
| 1x240/25 RM | 46–50 | 0.125 | 494 | 426 | – | 696 | 283 | 2200 |
| 1x300/25 RM | 48.5–52.5 | 0.100 | 564 | 479 | – | 870 | 283 | 2450 |
| 1x400/35 RM | 51.4–55.5 | 0.0778 | 654 | 545 | – | 1160 | 394 | 2950 |
| 1x500/35 RM | 54.7–59 | 0.0605 | 747 | 614 | – | 1450 | 394 | 3400 |
Conductor Dimensions
| Conductor Cross-Section (mm²) | Maximum Conductor Diameter (mm) | Maximum Resistance at 20°C (Ω/km) |
|---|---|---|
| 50 | 8.6 | 0.641 |
| 70 | 10.2 | 0.443 |
| 95 | 12.0 | 0.320 |
| 120 | 13.5 | 0.253 |
| 150 | 15.0 | 0.206 |
| 185 | 16.8 | 0.164 |
| 240 | 19.2 | 0.125 |
| 300 | 21.6 | 0.100 |
| 400 | 24.6 | 0.0778 |
| 500 | 27.6 | 0.0605 |
| 630 | 29.3 | 0.0469 |