H07BQ-F / X07BQ-F 450/750 V

Flexible PUR Rubber Cable | Class 5 Copper | EPR Insulation | Oil, Abrasion & Impact Resistant

Product Description

H07BQ-F and X07BQ-F are flexible power and connection cables designed for electrical equipment operating in demanding industrial and construction environments under medium mechanical stress.

The cable construction combines fine-stranded Class 5 bare copper conductors, ethylene propylene rubber (EPR) insulation and a durable polyurethane (PUR) outer sheath.

The PUR outer sheath provides high resistance to oil, abrasion and mechanical impact, making these cables suitable for connecting electrical tools and portable industrial equipment.

The cables are intended for dry and wet environments, cold environments and temporary outdoor use within the specified operating conditions.

Key Features

  • Flexible Class 5 copper conductors.
  • Durable polyurethane (PUR) outer sheath.
  • EPR rubber insulation, type EI6.
  • High resistance to oil and abrasion.
  • High resistance to mechanical impact.
  • Suitable for dry and wet environments.
  • Suitable for temporary outdoor use.
  • Suitable for medium mechanical stress.
  • Available with and without filler.

Applications

  • Electrical tools on construction sites.
  • Portable electrical equipment.
  • Industrial machinery and equipment.
  • Manufacturing and production facilities.
  • Industrial maintenance operations.
  • Electrical equipment in cold environments.
  • Temporary outdoor electrical connections.
  • Industrial environments requiring resistance to oil, abrasion and mechanical impact.

Cable Versions

Designation Construction
H07BQ-F With filler
H07BQ-F Without filler
X07BQ-F With filler
X07BQ-F Without filler

Cable Construction

Component Description
Conductor Bare copper
Conductor Class Class 5, fine-stranded according to DIN EN IEC 60228 (VDE 0295)
Core Insulation Ethylene propylene rubber (EPR), EI6
Filler Depending on cable version
Outer Sheath Polyurethane (PUR)
Sheath Colour Orange; black for selected sizes
Core Identification According to VDE 0293 / HD 308, depending on cable version
Protective Conductor Depending on cable configuration

Technical Characteristics

Parameter Value
Rated Voltage Uo/U 450/750 V
Maximum Conductor Temperature +90°C
Permitted Outer Cable Temperature – Fixed -40°C to +50°C
Minimum Bending Radius – Fixed 4 × outer cable diameter
Bending Radius – Moving 12.5 × outer cable diameter
Mechanical Stress Medium
Oil Resistance IEC 60811-404
Abrasion Resistance High
Impact Resistance High
Flame Retardancy Not flame-retardant
Outdoor Installation Temporary outdoor use
Installation Environment Dry and wet environments

Standards

  • DIN EN 50525-2-21 (VDE 0285-525-2-21).
  • DIN EN IEC 60228 / VDE 0295 – Class 5 flexible copper conductors.
  • DIN EN 60811-404 / VDE 0473-811-404 / IEC 60811-404 – Oil resistance.
  • VDE 0293 / HD 308 – Core identification.

Available Cross-Sections

  • H07BQ-F: 1 mm² to 16 mm².
  • X07BQ-F: 1.5 mm² to 300 mm².
  • Single-core and multicore configurations.
  • Available configurations depend on the cable designation and construction.

Installation Conditions

When installed in pipes or similar enclosed systems, the reference technical documentation permits use at voltages up to 1000 V AC or 750 V DC against earth, subject to the applicable installation requirements.

Installation Notice: The rated cable voltage is 450/750 V. Temporary outdoor use is permitted. Permanent outdoor exposure, continuous flexing and drag-chain applications are not confirmed by the reference documentation. The cable is not specified as flame-retardant. Technical suitability and certification must be confirmed for the selected construction.

H07BQ-F / X07BQ-F – Technical Data & Dimensions

450/750 V | Class 5 Copper | EPR EI6 Insulation | PUR Outer Sheath

H07BQ-F – With Filler

Nominal Size
mm²
Sheath Colour Conductor Resistance
Ω/km
Ampacity in Air at 30°C
A
Outer Diameter
mm
Copper Weight (GER)
kg/km
Cable Weight
kg/km
4G6Orange3.33716.2230391
5G6Orange3.33817.9288472
4G10Orange1.915221.6384722
5G10Orange1.915423.2480840
4G16Orange1.216924.2614.4980
5G16Orange1.217126.97681192

H07BQ-F – Without Filler

Nominal Size
mm²
Sheath Colour Conductor Resistance
Ω/km
Ampacity in Air at 30°C
A
Outer Diameter
mm
Copper Weight (GER)
kg/km
Cable Weight
kg/km
1 mm²
2×1Black19.5157.419.266
1.5 mm²
2×1.5Orange13.318.58.428.886
3G1.5Orange13.319.58.943.2100
4G1.5Orange13.3169.957.6136
5G1.5Orange13.316.510.872164
2.5 mm²
2×2.5Orange7.982510.048125
3G2.5Orange7.982610.672155
4G2.5Orange7.982211.896201
5G2.5Orange7.982313.1120244
4 mm²
3G4Orange4.953512.9115.2211
4G4Orange4.953014.5154254
5G4Orange4.953016.0192336
6 mm²
4G6Orange3.33716.2230.4436
5G6Orange3.33817.9288518
10 mm²
4G10Orange1.915221.6384722
5G10Orange1.915423.2480864
16 mm²
4G16Orange1.216924.2614.41103
5G16Orange1.217126.97681382

X07BQ-F – With Filler

Nominal Size
mm²
Sheath Colour Conductor Resistance
Ω/km
Ampacity in Air at 30°C
A
Outer Diameter
mm
Copper Weight (GER)
kg/km
Cable Weight
kg/km
Single-Core Cables
1×25Orange0.789413.8240375
1×35Orange0.55411715.4336492
1×50Orange0.38614817.7480675
1×70Orange0.27218520.0672908
1×95Orange0.20622222.29121171
1×120Orange0.16126024.611521445
1×150Orange0.12930026.914401783
1×185Orange0.10634128.917762125
1×240Orange0.080140732.723042733
1×300Orange0.064146836.528803350
Four-Core Cables
4G25Orange0.789229.29601609
4G35Orange0.55411432.413441893
4G50Orange0.38614337.619202642
4G70Orange0.27217842.426883597
4G95Orange0.20621049.236485121
4G120Orange0.16124656.046086550
Five-Core Cables
5G25Orange0.789435.012001744
5G35Orange0.55411739.016802340
5G50Orange0.38614846.524003290
5G70Orange0.27218553.033604522
5G95Orange0.20622260.045605800
Multicore Cables
7G1.5Orange13.315.513.2101267
7G2.5Orange7.982115.2168352
12G2.5Orange7.982120.8288520

X07BQ-F – Without Filler

Nominal Size
mm²
Sheath Colour Conductor Resistance
Ω/km
Ampacity in Air at 30°C
A
Outer Diameter
mm
Copper Weight (GER)
kg/km
Cable Weight
kg/km
Four-Core Cables
4G25Orange0.789226.89601348
4G35Orange0.55411430.213441810
4G50Orange0.38614335.219202516
4G70Orange0.27217840.026883413
4G95Orange0.20621046.836484535
Multicore Cables
12G1.5Orange13.315.516.0172.8340
12G2.5Orange7.982120.8288520

G = with green-yellow protective conductor. × = without green-yellow protective conductor.

Core identification is according to VDE 0293 / HD 308 as specified for each construction. For X07BQ-F without filler and more than five cores, the reference documentation specifies numbered cores with a green-yellow protective conductor.

Outer diameters and cable weights are approximate. Copper weights are stated according to the GER copper weight convention and do not represent measured recoverable copper content.

Current ratings refer to ampacity in air at 30°C. Actual permissible current depends on installation conditions, ambient temperature, cable grouping and the number of loaded conductors.

Technical parameters, available constructions, delivery lengths, certification and availability are subject to final order confirmation.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


UNIMA CABLE COLLECTION

Explore Our Cable Range

Discover cable types, technical specifications and solutions for your projects.

80 Cable Types Available