H07V2-K 450/750 V
Flexible Copper Conductor | Heat-Resistant PVC Insulation | 90°C
Product Description
H07V2-K is a single-core flexible low voltage cable with a Class 5 copper conductor and heat-resistant PVC insulation, designed for protected electrical installations and internal wiring of electrical equipment. The cable has a rated voltage of 450/750 V and a maximum conductor operating temperature of 90°C.
Applications
- Electrical installations in protective conduits.
- Installation on and under plaster in dry rooms.
- Installation in closed electrical installation ducts.
- Internal wiring of switchgear and distribution boxes.
- Protected wiring of lighting equipment.
- Electrical installations requiring a conductor operating temperature of up to 90°C.
Direct installation in cable trays is not permitted. For protected lighting installations, the datasheet specifies nominal voltages up to 1000 V AC or 750 V DC against earth.
Cable Construction
| Component | Description |
|---|---|
| Conductor | Flexible copper, Class 5 according to EN 60228 |
| Insulation | Heat-resistant PVC compound, type TI 3 |
| Number of cores | Single core |
| Cross-section range | 1.5–240 mm² |
Technical Characteristics
| Parameter | Value |
|---|---|
| Rated voltage U₀/U | 450/750 V |
| Test voltage | 2.5 kV |
| Bending radius | 6 × cable outer diameter |
| Maximum conductor temperature | +90°C |
| Maximum short-circuit temperature | +160°C |
Standards
- EN 50525-2-31 – Cable construction
- IEC 60227 – PVC-insulated cables
- EN 60228 – Conductors
- EN 50525-1 – Core identification
- DIN VDE 0298-4 – Current-carrying capacity
Available Insulation Colours
Availability of individual cross-sections and colours is subject to confirmation.
H07V2-K – Technical Data & Dimensions
450/750 V | Flexible Class 5 Copper | Heat-Resistant PVC Insulation | 90°C
Electrical and Physical Characteristics
| Nominal Cross-section mm² |
Max. DC Resistance at 20°C Ω/km |
Insulation Thickness mm |
Outer Diameter mm |
Metal Weight kg/km |
Cable Weight kg/km |
|---|---|---|---|---|---|
| 1 × 1.5 | 13.3 | 0.7 | 3.0 | 14.4 | 22 |
| 1 × 2.5 | 7.98 | 0.8 | 3.7 | 24.0 | 35 |
| 1 × 4 | 4.95 | 0.8 | 4.3 | 38.4 | 52 |
| 1 × 6 | 3.30 | 0.8 | 5.0 | 57.6 | 74 |
| 1 × 10 | 1.910 | 1.0 | 6.5 | 96.0 | 122 |
| 1 × 16 | 1.210 | 1.0 | 7.8 | — | 186 |
| 1 × 25 | 0.780 | 1.2 | 9.8 | 240.0 | 290 |
| 1 × 35 | 0.554 | 1.2 | 10.9 | 336.0 | 392 |
| 1 × 50 | 0.386 | 1.4 | 12.8 | 480.0 | 557 |
| 1 × 70 | 0.272 | 1.4 | 14.5 | 672.0 | 760 |
| 1 × 95 | 0.206 | 1.6 | 16.7 | 912.0 | 1028 |
| 1 × 120 | 0.161 | 1.6 | 19.0 | 1152.0 | 1286 |
| 1 × 150 | 0.129 | 1.8 | 20.7 | 1440.0 | 1603 |
| 1 × 185 | 0.106 | 2.0 | 23.0 | 1776.0 | 1978 |
| 1 × 240 | 0.0801 | 2.2 | 26.1 | 2304.0 | 2557 |
Outer diameters and cable weights are approximate. Metal weight for 1 × 16 mm² is subject to confirmation.
Current-Carrying Capacity at 30°C
| Nominal Cross-section mm² |
Installation Conduit in Thermally Insulated Wall | Installation Conduit in Wall | Open Air | ||
|---|---|---|---|---|---|
| 2 Loaded Cores A |
3 Loaded Cores A |
2 Loaded Cores A |
3 Loaded Cores A |
1 Loaded Core A |
|
| 1 × 1.5 | 19 | 17 | 23 | 20 | 24 |
| 1 × 2.5 | 26 | 23 | 31 | 28 | 32 |
| 1 × 4 | 35 | 31 | 42 | 37 | 42 |
| 1 × 6 | 45 | 40 | 54 | 48 | 54 |
| 1 × 10 | 61 | 54 | 75 | 66 | 73 |
| 1 × 16 | 81 | 73 | 100 | 88 | 98 |
| 1 × 25 | 106 | 95 | 133 | 117 | 129 |
| 1 × 35 | 131 | 117 | 164 | 144 | 158 |
| 1 × 50 | 158 | 141 | 198 | 175 | 198 |
| 1 × 70 | 200 | 179 | 253 | 222 | 245 |
| 1 × 95 | 241 | 216 | 306 | 269 | 292 |
| 1 × 120 | 278 | 249 | 354 | 312 | 344 |
| 1 × 150 | 318 | 285 | 393 | 342 | 391 |
| 1 × 185 | 362 | 324 | 449 | 384 | 448 |
| 1 × 240 | 424 | 380 | 528 | 450 | 528 |
| 1 × 300* | 486 | 435 | 603 | 514 | 608 |
Current-carrying capacities according to DIN VDE 0298-4. Maximum conductor operating temperature: 90°C. Ambient temperature: 30°C. Actual permissible current depends on installation conditions and applicable correction factors. Open-air reference values do not imply permission for direct installation in cable trays.
*Current-carrying capacity for 300 mm² is provided for reference only. Physical dimensions, cable weight and product availability are subject to confirmation.