H07Z1-K 450/750 V

Flexible Copper Conductor | Halogen-Free HFFR Insulation | B2ca-s1,d1,a1

Product Description

H07Z1-K is a single-core, flexible low voltage cable with a Class 5 copper conductor and halogen-free, flame-retardant thermoplastic insulation (HFFR). Designed for electrical installations requiring enhanced reaction-to-fire performance, the cable has a rated voltage of 450/750 V and a CPR classification of B2ca-s1,d1,a1.

Applications

  • Internal wiring of lighting equipment and electrical devices.
  • Switchgear cabinets and distribution boxes.
  • Installation in conduits and closed installation ducts.
  • Installation on, in and under plaster.
  • Buildings with a high density of occupants or valuable assets.
  • Electrical installations in dry rooms.

Cable Construction

Component Description
Conductor Flexible copper, Class 5 according to EN 60228
Insulation Halogen-free thermoplastic compound, type TI 7 according to EN 50363-7
UV resistance UV-resistant insulation
Number of cores Single core
Cross-section range 1.5–240 mm²

Technical Characteristics

Parameter Value
Rated voltage U₀/U 450/750 V
Test voltage 2.5 kV
CPR classification B2ca-s1,d1,a1
Minimum bending radius 5 × cable outer diameter
Minimum installation temperature +5°C
Ambient temperature range −35°C to +35°C
Maximum conductor temperature +70°C
Maximum short-circuit temperature +160°C

Standards

  • EN 50525-3-31 – Cable construction
  • EN 60228 – Conductors
  • EN 50363-7 – Insulation compound TI 7
  • EN 60754-1 and EN 60754-2 – Halogen-free characteristics
  • EN 50575 – Construction Products Regulation
  • EN 13501-6 – Reaction-to-fire classification
  • EN 50525-1 – Core identification
  • DIN VDE 0298-4 – Current-carrying capacity

Available Insulation Colours

Black Blue Brown Grey Orange Pink Red Turquoise Violet White Green/Yellow

Availability of individual cross-sections and colours is subject to confirmation.

H07Z1-K – Technical Data & Dimensions

450/750 V | Flexible Class 5 Copper | HFFR Insulation | B2ca-s1,d1,a1

Electrical and Physical Characteristics

Nominal Cross-section
mm²
Max. DC Resistance at 20°C
Ω/km
Insulation Thickness
mm
Min. Outer Diameter
mm
Max. Outer Diameter
mm
Metal Weight
kg/km
Cable Weight
kg/km
1 × 1.513.30.72.83.414.422
1 × 2.57.980.83.44.124.034
1 × 44.950.83.94.838.451
1 × 63.300.84.45.357.672
1 × 101.9101.05.76.896.0119
1 × 161.2101.06.78.1153.6181
1 × 250.7801.28.410.2240.0280
1 × 350.5541.29.711.7336.0383
1 × 500.3861.411.513.9480.0545
1 × 700.2721.413.216.0672.0747
1 × 950.2061.615.118.2912.01012
1 × 1200.1611.616.720.21152.01263
1 × 1500.1291.818.622.51440.01579
1 × 1850.1062.020.624.91776.01948
1 × 2400.08012.223.528.42304.02519

Outer diameters and cable weights are approximate. Metal weights are stated as specified in the technical datasheet.

Current-Carrying Capacity at 30°C

Nominal Cross-section
mm²
Thermally Insulated Wall Electrical Installation Conduit On the Wall
2 Cores
A
3 Cores
A
2 Cores
A
3 Cores
A
2 Cores
A
3 Cores
A
1 × 1.5191723202422
1 × 2.5262331283330
1 × 4353142374540
1 × 6454054485852
1 × 10615475668071
1 × 1681731008810796
1 × 2510695133117138119
1 × 35131117164144171147
1 × 50158141198175209179
1 × 70200179235222269229
1 × 95241216306269328278
1 × 120278249354312382322
1 × 150318285393342441371
1 × 185362324449384506424
1 × 240424380528450599500

Current-carrying capacities according to DIN VDE 0298-4, at an ambient temperature of 30°C. The 2-core and 3-core columns refer to the installation arrangement of single-core conductors, not multicore cable construction. Actual permissible current depends on installation conditions and applicable correction factors.