Single-core copper conductor high-voltage power cable with XLPE insulation, metallic screening and protective outer sheath for high-voltage power transmission and distribution networks.

64/110 (123) kV Copper Conductor XLPE Insulation 95 mm² Metallic Screen 16 Reference Sizes IEC 60840

Product Overview

XRUHKXS / 2XS(FL)2Y / N2XS(FL)2Y is a single-core high-voltage power cable with a copper conductor, rated 64/110 (123) kV.

The reference construction incorporates a copper conductor, semiconductive conductor screen, XLPE insulation, semiconductive insulation screen, metallic screen and protective outer sheath.

The reference range covers 16 conductor sizes from 150 to 3000 mm², including RM and RMS conductor configurations. Insulation thickness, outer diameter, cable weight and mechanical characteristics depend on the selected conductor size.

Key Technical Features

64/110 (123)Rated Voltage (kV)
150–3000Conductor Size (mm²)
16Reference Sizes
95 mm²Metallic Screen

Construction & Technical Properties

Cable Construction

Number of Cores1
Conductor MaterialCopper
Conductor DesignationRM / RMS
Conductor ScreenSemiconductive Layer
InsulationXLPE
Nominal Insulation Thickness14.0–18.5 mm
Insulation ScreenSemiconductive Layer
Metallic Screen95 mm²
Outer SheathProtective PE Sheath

Reference Technical Data

Rated Voltage64/110 (123) kV
Conductor Size Range150–3000 mm²
Outer Diameter Range67–121 mm
Cable Weight Range6280–35960 kg/km
Maximum Pulling Force4.5–90 kN
Minimum Bending Radius1.7–3.0 m
Conductor ResistanceAt 90°C
Electrical PropertiesSize Dependent

Typical Applications

High-Voltage Transmission Networks
Utility Power Infrastructure
High-Voltage Substation Connections
Industrial High-Voltage Power Systems

Referenced Standards

IEC 60840 – Referenced for XRUHKXS and 2XS(FL)2Y.
DIN VDE 0276-632 – Referenced for N2XS(FL)2Y.
Technical Note: Values are based on the supplied reference catalogue. Cable construction, dimensions, insulation thickness, electrical characteristics and installation requirements vary by conductor size. Final product specifications and compliance must be confirmed with the supplying manufacturer. CPR classification is not specified in the supplied excerpt.
UNIMA CABLE | TECHNICAL DIMENSIONS

XRUHKXS / 2XS(FL)2Y / N2XS(FL)2Y – Cable Sizes

64/110 (123) kV copper conductor high-voltage power cable. Reference dimensions, insulation thickness, metallic screen and cable weight per kilometre.

16Reference Sizes
150–3000Conductor Size (mm²)
67–121Outer Diameter (mm)
6280–35960Cable Weight (kg/km)

Available Cable Sizes

Conductor (mm²) Conductor Diameter (mm) Insulation Thickness (mm) Metallic Screen (mm²) Outer Diameter (mm) Cable Weight (kg/km) Max. Pulling Force (kN) Min. Bending Radius (m)
150 RM14.418.0956762804.51.7
185 RM15.817.0956854505.551.7
240 RM18.516.5956760007.21.7
300 RM20.515.5956765009.01.7
400 RM23.814.59569730012.01.7
500 RM26.414.09571835015.01.8
630 RM30.314.09575992018.91.9
800 RM34.714.095801174024.02.0
1000 RM38.314.095841388030.02.1
1200 RMS41.814.095891600036.02.2
1400 RMS45.814.095941804042.02.3
1600 RMS49.814.095982029048.02.4
1800 RMS53.214.0951022270054.02.5
2000 RMS54.814.0951032427060.02.6
2500 RMS60.014.5951122983075.02.8
3000 RMS68.414.5951213596090.03.0
Technical Note: Reference data from the supplied catalogue. Cable weights are expressed in kg/km and exclude drums and packaging. The metallic screen is 95 mm² for all listed configurations. Separate copper weight is not specified. Final technical specifications must be confirmed with the supplying manufacturer.

Technical Documentation

Technical Data Sheet

EU declaration of conformity

Core Identification

Send Us email - RFQ


UNIMA CABLE COLLECTION

Explore Our Cable Range

Discover cable types, technical specifications and solutions for your projects.

80 Cable Types Available