(N)A2XS(F)2Y 20.3/35 kV


Tehnički podaci

  • (N)A2XS(F)2Y
  • Tip kabela
  • Medium Voltage Power Distribution
  • Područje primjene
  • TSEK 204 / TS IEC 60502-2 / IEC 60502-2
  • Standard

Detaljnije

  • Izolacijski materijal XLPE
  • Pakiranje Wooden Drums
  • Dostupnost On Request
  • Cable Configuration Single Core
  • Conductor Type Class 2 Compacted Aluminium
  • Screen Copper Wire & Tape Screen
  • Outer Sheath Black PE (ST7)
  • Max. Operating Temperature 90°C
  • Max. Short-Circuit Temperature 250°C (max. 5 sec.)
  • Minimum Bending Radius 15 × D
  • Water Blocking Longitudinal – Semiconductive & Swellable Tapes
  • Insulation XLPE
  • Materijal vodiča Aluminium
  • Grupa kabela Energetski kablovi 1 - 30 kV
  • Izolacijski materijal XLPE
  • Radni napon 20.3/35 (42) kV
  • Standard TSEK 204 / TS IEC 60502-2 / IEC 60502-2
(N)A2XS(F)2Y · MEDIUM VOLTAGE POWER CABLE

(N)A2XS(F)2Y Aluminium XLPE Medium Voltage Cable

(N)A2XS(F)2Y is a single-core medium-voltage power cable with a Class 2 circular compacted aluminium conductor, XLPE insulation, a copper wire and tape screen, longitudinal water-blocking layers and a black polyethylene (PE) outer sheath.

Designed for fixed medium-voltage power distribution in underground networks, cable ducts, substations, power infrastructure and industrial installations. The swellable water-blocking tapes help limit longitudinal water propagation within the cable.

20.3/35 kV Radni napon
Aluminium Conductor
XLPE Insulation
Cu Screen Wires & Tape
Water-Blocking Longitudinal Protection
01

Construction

AL / XLPE / CWS + CWT / WATER-BLOCKING / PE

1
Conductor

Circular compacted aluminium conductor, Class 2 according to IEC 60228

2
Inner Semiconductive Layer

Extruded semiconductive conductor screen

3
Insulation

Cross-linked polyethylene (XLPE)

4
Outer Semiconductive Layer

Extruded semiconductive insulation screen, bonded construction

5
Semiconductive Water-Blocking Tape

Semiconductive swellable tape providing longitudinal water-blocking protection

6
Metallic Screen

Copper wires and copper tape. Screen cross-section depends on cable size.

7
Separator / Water-Blocking Layer

Non-conductive swellable tape beneath the outer sheath

8
Outer Sheath

Black polyethylene (PE), ST7 according to IEC 60502-2

02

Technical Data

Electrical and thermal characteristics

Rated Voltage U₀/U (Um) 20.3/35 (42) kV
Materijal vodiča Aluminium
Conductor Class Class 2, compacted
Insulation XLPE
Metallic Screen Copper Wires & Tape
Longitudinal Water Blocking Semiconductive and non-conductive swellable tapes
Outer Sheath PE, ST7, Black
Maximum Conductor Temperature 90°C
Maximum Short-Circuit Temperature 250°C
Minimum Bending Radius 15 × D
Cable Configuration Single Core
03

1×185/25 mm² – Technical Reference

Confirmed 20.3/35 (42) kV construction

Conductor Cross-Section 185 mm² Aluminium, RM
Copper Screen Cross-Section 25 mm²
Insulation Thickness (Nominal) 9.0 mm
Overall Diameter (Approx.) 46 mm
DC Resistance at 20°C (Max.) 0.164 Ω/km
Current Rating – Underground, 20°C (Flat) 400 A
Current Rating – Air, 30°C (Flat) 485 A
Current Rating – Ducts, 40°C (Flat) 323 A
Capacitance 0.18 µF/km
Inductance 0.63 mH/km
Aluminium Conductor Weight (Approx.) 478 kg/km
Copper Screen Weight (Approx.) 220 kg/km
Total Cable Weight (Approx.) 1,845 kg/km
High Voltage Test (5 min.) 71 kV
Minimum Bending Radius 690 mm
04

Standardi

Referenced technical specifications

IEC 60502-2 Medium-voltage power cable standard
TS IEC 60502-2 / TSEK 204 Referenced cable specifications
05

Primjene

Medium-voltage energy distribution

Energy Networks Fixed medium-voltage power distribution in electrical networks.
Underground Installation Underground cable installations with longitudinal water-blocking protection.
Cable Ducts Suitable for installation in cable ducts under appropriate conditions.
Industrial Installations Medium-voltage electrical installations in industrial facilities.
Substations Electrical substations and medium-voltage switching installations.
Power Infrastructure Single-core cable solution for medium-voltage power infrastructure.
(N)A2XS(F)2Y · AL / XLPE / Cu SCREEN / WATER-BLOCKING / PE Available in multiple conductor and copper screen cross-sections. The specific numerical values shown for 1×185/25 mm² refer to a confirmed 20.3/35 (42) kV technical specification. Dimensions, weights and electrical characteristics of other cross-sections depend on the selected cable configuration and manufacturing specification.
NA2XS2Y · 20.3/35 kV (20.8/36 kV)

Dimensions & Technical Data

Standard single-core cable configurations with nominal dimensions, weights, conductor resistance and current carrying capacity.

01

Single Core

NA2XS2Y · Aluminium conductor · Copper wire screen

Cross Section
mm²
Overall Ø
mm
Net Weight
kg/km
Dostava
m
Resistance 20°C
Ω/km
Resistance 90°C
Ω/km
Inductance
mH/km
Capacitance
µF/km
Ground Flat
A
Ground Trefoil
A
Air Flat
A
Air Trefoil
A
1×35/16 37.5 1000 1000 0.868 1.1110 0.690 0.115 – – – –
1×50/16 38.5 1100 1000 0.641 0.8205 0.664 0.125 196 175 217 187
1×70/16 40.5 1250 1000 0.443 0.5670 0.633 0.140 238 214 270 232
1×95/16 42.0 1400 1000 0.320 0.4096 0.609 0.153 284 256 328 281
1×120/16 44.0 1500 1000 0.253 0.3238 0.590 0.165 322 290 378 323
1×150/25 45.5 1750 1000 0.206 0.2637 0.572 0.178 355 324 425 365
1×185/25 47.5 1950 1000 0.164 0.2099 0.556 0.191 400 366 485 418
1×240/25 50.0 2200 1000 0.125 0.1600 0.535 0.209 461 426 572 494
1×300/25 52.5 2450 1000 0.100 0.1280 0.519 0.226 516 479 649 564
1×400/35 55.5 2950 1000 0.0778 0.1009 0.497 0.252 572 545 737 654
1×500/35 59.0 3400 1000 0.0605 0.0774 0.481 0.274 638 614 835 747
1×630/35 62.5 3900 1000 0.0469 0.0600 0.464 0.300 728 690 950 851
Need another configuration? Additional conductor and copper screen configurations may be available on request. Contact UNIMA CABLE with your project specification.
Technical note Current carrying capacities in ground are based on 20°C soil temperature, 70 cm laying depth, soil thermal resistivity of 1 K·m/W and load factor 0.7. Current carrying capacities in air are based on 30°C ambient temperature and load factor 1.0. Flat formation uses cable spacing of 1 × cable outer diameter in air and 7 cm in ground. Dimensions and weights are approximate.
(N)A2XS(F)2Y · 20.3/35 (42) kV

Available Cable Dimensions

Aluminium conductor · XLPE insulation · Copper wire and tape screen · Longitudinal water blocking · PE sheath

Cable Size Conductor Resistance
20°C
Ω/km
Outer
Diameter
mm
Aluminium
kg/km
Cable Weight
kg/km
1×185/25 RM, Class 2 0.164 46.0 478 1845
Verified 1×185/25 mm² – Additional Data
Insulation Thickness 9.0 mm nominal
Copper Screen 25 mm² / 220 kg/km
Underground, 20°C 400 A
In Air, 30°C 485 A
In Ducts, 40°C 323 A
Minimum Bending Radius 690 mm

Technical values for 1×185/25 mm² are based on the confirmed 20.3/35 (42) kV specification. Other dimensions and values are subject to confirmation for the selected manufacturing variant.