NYCY is a 0.6/1 kV copper power cable with PVC insulation and a concentric copper conductor, designed for fixed installations in industrial plants, commercial buildings, utility networks, and infrastructure projects.The concentric conductor provides an integrated protective earth (PE) and neutral function, making NYCY ideal where enhanced electrical safety and fault current protection are required.
Suitable for installation indoors, outdoors, in cable ducts, underground (with additional protection), and in concrete.
NYCY Copper Power Cable with Concentric Conductor
NYCY is a 0.6/1 kV power cable with copper conductors, PVC insulation, a concentric copper conductor and PVC outer sheath.
Designed for fixed power distribution installations where the concentric copper conductor can be used as a protective, neutral or combined protective and neutral conductor, depending on the installation design and applicable requirements.
Construction
CU / PVC / CONCENTRIC CU / PVC
Copper conductor, Class 1 or Class 2 depending on cross-section
PVC insulation compound
Insulated conductors laid up to form the cable core
Concentric copper wires arranged around the cable core
PVC outer sheath
0.6/1 kV
Technical Data
Electrical and installation characteristics
Standards
Applicable cable standards
Applications
Fixed low-voltage power distribution
Dimensions & Technical Data
2 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 2 × 1.5 / 1.5 | 12.1 | 0.8 | 19 | 27 | 13.0 | 52 | 200 |
| 2 × 2.5 / 2.5 | 7.41 | 0.8 | 26 | 36 | 13.6 | 80 | 260 |
| 2 × 4 / 4 | 4.61 | 1.0 | 34 | 47 | 15.4 | 123 | 350 |
| 2 × 6 / 6 | 3.08 | 1.0 | 44 | 59 | 16.9 | 182 | 430 |
| 2 × 10 / 10 | 1.83 | 1.0 | 60 | 79 | 18.5 | 312 | 520 |
| 2 × 16 / 16 | 1.15 | 1.0 | 80 | 102 | 20.5 | 489 | 720 |
3 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 3 × 1.5 / 1.5 | 12.1 | 0.8 | 19 | 27 | 13.2 | 66 | 220 |
| 3 × 2.5 / 2.5 | 7.41 | 0.8 | 26 | 36 | 14.2 | 104 | 280 |
| 3 × 2.5 / 10 | 7.41 | 0.8 | 26 | 36 | 14.4 | 192 | 359 |
| 3 × 4 / 4 | 4.61 | 1.0 | 34 | 47 | 16.3 | 161 | 390 |
| 3 × 6 / 6 | 3.08 | 1.0 | 44 | 59 | 17.3 | 240 | 500 |
| 3 × 10 / 10 | 1.83 | 1.0 | 60 | 79 | 20.0 | 408 | 680 |
| 3 × 16 / 16 | 1.15 | 1.0 | 80 | 102 | 23.0 | 643 | 1010 |
4 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 4 × 1.5 / 1.5 | 12.1 | 0.8 | 19 | 27 | 14.2 | 81 | 250 |
| 4 × 2.5 / 2.5 | 7.41 | 0.8 | 26 | 36 | 15.3 | 128 | 340 |
| 4 × 4 / 4 | 4.61 | 1.0 | 34 | 47 | 17.3 | 200 | 460 |
| 4 × 6 / 6 | 3.08 | 1.0 | 44 | 59 | 18.4 | 297 | 580 |
| 4 × 10 / 10 | 1.83 | 1.0 | 60 | 79 | 21.0 | 504 | 765 |
| 4 × 16 / 16 | 1.15 | 1.0 | 80 | 102 | 23.0 | 796 | 1060 |
5 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 5 × 1.5 / 1.5 | 12.1 | 0.8 | 19 | 27 | 15.0 | 95 | 330 |
| 5 × 2.5 / 2.5 | 7.41 | 0.8 | 26 | 36 | 16.0 | 152 | 400 |
| 5 × 4 / 4 | 4.61 | 1.0 | 34 | 47 | 19.0 | 238 | 550 |
| 5 × 6 / 6 | 3.08 | 1.0 | 44 | 59 | 21.0 | 355 | 700 |
7 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 7 × 1.5 / 2.5 | 12.1 | 0.8 | 19 | 27 | 15.3 | 133 | 350 |
| 7 × 2.5 / 2.5 | 7.41 | 0.8 | 25 | 36 | 17.4 | 200 | 450 |
| 7 × 4 / 4 | 4.61 | 1.0 | 34 | 47 | 20.0 | 315 | 600 |
| 7 × 6 / 6 | 3.08 | 1.0 | 43 | 59 | 22.5 | 470 | 790 |
| 7 × 10 / 10 | 1.83 | 1.0 | 60 | 79 | 25.0 | 792 | 1320 |
10–16 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 10 × 1.5 / 2.5 | 12.1 | 0.8 | 19 | 27 | 18.4 | 176 | 410 |
| 10 × 2.5 / 4 | 7.41 | 1.0 | 25 | 36 | 20.4 | 286 | 600 |
| 10 × 4 / 6 | 4.61 | 0.8 | 34 | 47 | 23.5 | 451 | 900 |
| 12 × 1.5 / 2.5 | 12.1 | 0.8 | 19 | 27 | 19.4 | 205 | 470 |
| 12 × 2.5 / 4 | 7.41 | 0.8 | 25 | 36 | 20.5 | 334 | 660 |
| 12 × 4 / 6 | 4.61 | 1.0 | 34 | 47 | 24.5 | 528 | 1060 |
| 14 × 1.5 / 2.5 | 12.1 | 0.8 | 19 | 27 | 20.4 | 234 | 520 |
| 14 × 2.5 / 6 | 7.41 | 0.8 | 25 | 36 | 21.5 | 403 | 750 |
| 16 × 1.5 / 4 | 12.1 | 0.8 | 19 | 27 | 20.0 | 276 | 620 |
| 16 × 2.5 / 6 | 7.41 | 0.8 | 25 | 36 | 22.5 | 451 | 800 |
19–61 Core
| Configuration mm² |
Resistance Ω/km @ 20°C |
Insulation mm |
Ampacity Air 30°C · A |
Ampacity Ground 20°C · A |
Overall Ø approx. mm |
Copper Weight kg/km |
Net Weight kg/km |
|---|---|---|---|---|---|---|---|
| 19 × 1.5 / 4 | 12.1 | 0.8 | 19 | 27 | 22.5 | 320 | 660 |
| 19 × 2.5 / 6 | 7.41 | 0.8 | 25 | 36 | 23.5 | 523 | 940 |
| 19 × 4 / 10 | 4.61 | 1.0 | 34 | 47 | 27.1 | 850 | 1376 |
| 21 × 1.5 / 6 | 12.1 | 0.8 | 19 | 27 | 23.0 | 369 | 790 |
| 24 × 1.5 / 6 | 12.1 | 0.8 | 19 | 27 | 25.5 | 413 | 850 |
| 24 × 2.5 / 10 | 7.41 | 0.8 | 25 | 36 | 27.6 | 696 | 1150 |
| 24 × 4 / 10 | 4.61 | 1.0 | 34 | 47 | 32.3 | 1042 | 1813 |
| 30 × 1.5 / 6 | 12.1 | 0.8 | 19 | 27 | 26.5 | 499 | 1020 |
| 30 × 2.5 / 10 | 7.41 | 0.8 | 25 | 36 | 29.5 | 840 | 1600 |
| 40 × 1.5 / 10 | 12.1 | 0.8 | 19 | 27 | 30.0 | 696 | 1280 |
| 40 × 2.5 / 10 | 7.41 | 0.8 | 25 | 36 | 33.0 | 1080 | 1660 |
| 52 × 1.5 / 10 | 12.1 | 0.8 | 19 | 27 | 32.0 | 869 | 1600 |
| 52 × 2.5 / 10 | 7.41 | 0.8 | 25 | 36 | 35.0 | 1368 | 2000 |
| 61 × 1.5 / 10 | 12.1 | 0.8 | 19 | 27 | 33.0 | 998 | 2000 |
| 61 × 2.5 / 10 | 7.41 | 0.8 | 25 | 36 | 36.0 | 1584 | 2280 |
Additional NYCY conductor configurations and cross-sections are available on request. Contact UNIMA CABLE with the required size, quantity and delivery location.
The value after “/” indicates the cross-section of the concentric copper conductor. Outer diameters and weights are approximate. Current ratings depend on installation conditions and applicable correction factors. Technical values should be confirmed for the selected cable configuration before final project design.