UNIMA CABLE | BUILDING & FLEXIBLE WIRES
H07V-K – Flexible PVC Insulated Wire
Fine-stranded copper single-core wire for electrical installations, distribution boards, switchgear and internal machinery wiring.
450/750 VClass 5 CopperPVC TI1CPR Eca1.5–240 mm²EN 50525-2-31
Product Overview
H07V-K is a flexible, PVC-insulated single-core installation wire with fine-stranded Class 5 bare copper conductors and a nominal voltage of 450/750 V.
It is designed for laying in conduits installed on or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and electrical distribution systems.
The wire is flame-retardant according to IEC 60332-1-2 and classified Eca under EN 50575.
Key Technical Features
450/750 VRated Voltage
+70°CMax. Conductor Temp.
EcaCPR Classification
15Cross-Sections
Construction & Technical Properties
Cable Construction
ConductorBare Copper
ConstructionClass 5, Fine Stranded
InsulationPVC TI1
Core ArrangementSingle Core
Cross-Sections1.5–240 mm²
CPR ClassificationEca
Electrical & Mechanical Data
Rated Voltage450/750 V
Test Voltage2.5 kV
Max. Conductor Temp.+70°C
Fixed Temperature-5°C to +70°C
Moving Temperature+5°C to +70°C
Minimum Bending Radius4 × Outer Diameter
Max. Operating Capacitance100 nF/km
Flame RetardanceIEC 60332-1-2
Typical Applications
Electrical Conduits
Building Installation Wiring
Switchgear & Control Panels
Distribution Boards
Internal Machinery Wiring
Closed Installation Ducts
Applicable Standards
DIN EN 50525-2-31 – PVC insulated single-core wires.
DIN EN IEC 60228 – Class 5 copper conductors.
EN 50575 – CPR classification Eca.
IEC 60332-1-2 – Flame propagation test.
VDE 0298-4 – Current-carrying capacity reference.
DIN EN IEC 60228 – Class 5 copper conductors.
EN 50575 – CPR classification Eca.
IEC 60332-1-2 – Flame propagation test.
VDE 0298-4 – Current-carrying capacity reference.
Installation note: H07V-K must be installed in suitable conduits or closed installation ducts. It is not suitable for direct installation under plaster without a protective conduit. Current-carrying capacities depend on installation conditions and must be verified according to VDE 0298-4.
Technical Data & Cable Dimensions
H07V-K | Flexible Copper Class 5 | 450/750 V | PVC TI1 | CPR Eca
15Cross-Sections
450/750 VRated Voltage
70°CMax. Conductor Temp.
EcaCPR Class
| Cross-Section mm² |
Conductor Ø mm |
Resistance Ω/km |
Insulation mm |
Current in Air A |
Fixed Bend mm |
Outer Ø mm |
Copper kg/km |
Cable kg/km |
|---|---|---|---|---|---|---|---|---|
| 1x1.5 | 1.8 | 13.3 | 0.7 | 24 | 11.2 | 2.8 | 14.4 | 20 |
| 1x2.5 | 2.6 | 7.98 | 0.8 | 32 | 13.6 | 3.4 | 24 | 32 |
| 1x4 | 3.2 | 4.95 | 0.8 | 42 | 15.6 | 3.9 | 38 | 46 |
| 1x6 | 3.9 | 3.3 | 0.8 | 54 | 18 | 4.5 | 58 | 65 |
| 1x10 | 5.1 | 1.91 | 1.0 | 73 | 23.2 | 5.8 | 96 | 115 |
| 1x16 | 6.3 | 1.21 | 1.0 | 98 | 28 | 7.0 | 154 | 170 |
| 1x25 | 7.8 | 0.78 | 1.2 | 129 | 34 | 8.5 | 240 | 260 |
| 1x35 | 9.2 | 0.554 | 1.2 | 158 | 39.2 | 9.8 | 336 | 360 |
| 1x50 | 11.0 | 0.386 | 1.4 | 198 | 46.4 | 11.6 | 480 | 515 |
| 1x70 | 13.1 | 0.272 | 1.4 | 245 | 53.2 | 13.3 | 672 | 710 |
| 1x95 | 15.0 | 0.206 | 1.6 | 292 | 61.2 | 15.3 | 912 | 940 |
| 1x120 | 16.7 | 0.161 | 1.6 | 344 | 67.6 | 16.9 | 1152 | 1180 |
| 1x150 | 18.6 | 0.129 | 1.8 | 391 | 75.2 | 18.8 | 1440 | 1600 |
| 1x185 | 20.6 | 0.106 | 2.0 | 448 | 84 | 21.0 | 1776 | 2100 |
| 1x240 | 23.5 | 0.0801 | 2.2 | 528 | 96 | 24.0 | 2304 | 3015 |
Showing 15 of 15 cross-sections
Technical notes: Current-carrying capacities refer to the manufacturer's values in air at 30°C and must be verified for the actual installation method. Outer diameters are approximate. Copper and cable weights are expressed per kilometre. Special colour variants may have different outer diameters.