UNIMA CABLE | Low Voltage Power Cables
NYCY
TECHNICAL DATA SHEET
NYCY | 0.6/1 kV Copper Power Cable | Concentric Copper Conductor | PVC

0.6/1 kV Rated Voltage
Copper Concentric Conductor
PVC Insulation & Sheath
UV Resistant
PRODUCT DESCRIPTION
NYCY is a 0.6/1 kV PVC-insulated power cable with copper conductors, a concentric copper conductor and a black PVC outer sheath.
Designed for fixed installation indoors, outdoors, underground, in water and in concrete. UV-resistant and flame-retardant according to IEC 60332-1-2.
CABLE CONSTRUCTION
| Conductor | Bare Copper, Class 1; Class 2 from 25 mm² |
|---|---|
| Core Insulation | PVC DIV 4 |
| Core Identification | HD 308; Numbered Above 5 Cores |
| Concentric Conductor | Copper (Cu) |
| Outer Sheath | PVC DMV5 |
| Sheath Colour | Black |
TECHNICAL DATA
| Rated Voltage | 0.6/1 kV |
|---|---|
| Maximum Operating Voltage | 1.2 kV |
| DC Voltage (Core-Earth / Core-Core) | 1.8/1.8 kV |
| Test Voltage | 4 kV |
| Maximum Conductor Temperature | +70°C |
| Operating Temperature (Moved) | -5°C to +70°C |
| Minimum Bending Radius | 12 × D |
| UV Resistance | Yes |
| Flame Retardance | IEC 60332-1-2 |
| CPR Classification | Eca |
STANDARDS
- VDE 0276-603 – Power Cable Standard
- VDE 0276-627 – Cables with ≥5 Cores
- HD 308 – Core Identification
- IEC 60332-1-2 – Flame Retardance
- EN 50575 – CPR Classification
APPLICATIONS
- Indoor Fixed Installation
- Outdoor Fixed Installation
- Underground Installation
- Installation in Water
- Installation in Concrete
CPR CLASS: Eca – EN 50575