NHXMH-J / NHXMH-O | Halogen-Free XLPE Insulated Installation Cable | 300/500 V

PRODUCT DESCRIPTION
NHXMH-J and NHXMH-O are halogen-free installation cables rated 300/500 V, with copper conductors, XLPE insulation and a low-smoke, flame-retardant outer sheath. Designed for fixed electrical installations in residential, commercial and public buildings where reduced smoke and corrosive gas emissions are required.
CABLE CONSTRUCTION
| Conductor | Bare copper, Class 1 (RE) or Class 2 (RM) |
|---|---|
| Insulation | Cross-linked polyethylene (XLPE), type 2XI1 |
| Core Identification | According to VDE 0293 / HD 308 |
| Protective Conductor | NHXMH-J with PE / NHXMH-O without PE |
| Outer Sheath | Halogen-free FRNC compound, type HM2 |
| Sheath Colour | Grey |
TECHNICAL DATA
| Rated Voltage | 300/500 V |
|---|---|
| Maximum System Voltage | Not specified |
| Test Voltage | 2 kV AC |
| Conductor Material | Copper |
| Conductor Class | Class 1 / Class 2 |
| Insulation | XLPE (2XI1) |
| Outer Sheath | Halogen-free compound (HM2) |
| Sheath Colour | Grey |
| Maximum Conductor Temperature | +70°C |
| Fixed Installation Temperature | -40°C to +70°C |
| Minimum Installation Temperature | +5°C |
| Core Identification | HD 308 / VDE 0293 |
| Flame Propagation | IEC 60332-3-24 |
| Smoke Emission | IEC 61034 |
| Halogen Content | IEC 60754 |
| CPR Classification | According to variant-specific DoP |
| Product Standard | VDE 0250-214 |
STANDARDS
- VDE 0250-214 – Cable construction
- EN 60228 – Conductors
- EN 50575 – Construction Products Regulation (CPR)
- IEC 60332-3-24 – Flame propagation, Category C
- IEC 61034 – Smoke density
- IEC 60754 – Halogen and acidic gas emissions
- HD 308 / VDE 0293 – Core identification
APPLICATIONS
- Residential buildings and apartments
- Commercial and office buildings
- Schools, hospitals and public buildings
- Fixed electrical installations on and under plaster
- Installation in dry and wet indoor areas
- Installation in concrete, excluding shaken or tamped concrete
- Electrical distribution where halogen-free cables are required
- Not intended for direct burial in soil or installation in water