UNIMA CABLE
UNIMA CABLE | TECHNICAL DOCUMENTATION

(N)HXH-J / (N)HXH-O FE180/E90

TECHNICAL DATA SHEET

(N)HXH-J / (N)HXH-O | Halogen-Free Fire Resistant Power Cable | FE180/E90 | 0.6/1 kV

(N)HXH-J / (N)HXH-O FE180/E90
PRODUCT DESCRIPTION

(N)HXH-J and (N)HXH-O FE180/E90 are halogen-free, fire-resistant power cables rated 0.6/1 kV, manufactured with bare copper conductors, FRNC HI1 insulation and an orange FRNC HM1 outer sheath.

Designed for fixed electrical installations in dry and wet rooms, these cables provide FE180 fire resistance and E90 circuit integrity when installed with appropriately tested support systems in accordance with DIN 4102-12.

Suitable for public buildings and installations with high fire safety requirements. Not intended for direct burial in soil or installation in water.

CABLE CONSTRUCTION
ConductorBare copper, Class 1 (RE); from 25 mm² Class 2 (RM)
InsulationFire-resistant FRNC compound, type HI1
Core IdentificationAccording to HD 308 / VDE 0293
Protective Conductor(N)HXH-J with PE / (N)HXH-O without PE
Outer SheathHalogen-free FRNC compound, type HM1
Sheath ColourOrange
TECHNICAL DATA
Rated Voltage0.6/1 kV
Maximum System Voltage1.2 kV
Test Voltage4 kV AC
Conductor MaterialBare Copper
Conductor ClassClass 1 (RE) / Class 2 (RM)
InsulationFRNC HI1
Outer SheathFRNC HM1
Sheath ColourOrange
Maximum Conductor Temperature+90°C
Fixed Installation Temperature-30°C to +90°C
Minimum Movement Temperature-5°C
Minimum Bending Radius Multicore12 x Outer Diameter
Minimum Bending Radius Single-Core15 x Outer Diameter
Fire ResistanceFE180
Circuit IntegrityE90 (tested installation system)
Flame PropagationIEC 60332-3-24 (Cat. C)
Smoke EmissionIEC 61034
Halogen-FreeIEC 60754
CPR ClassificationAccording to applicable DoP
Product StandardVDE 0266
STANDARDS
  • VDE 0266 – Cable construction
  • VDE 0472-814 / IEC 60331-11 – FE180 fire resistance
  • DIN 4102-12 – E90 circuit integrity
  • IEC 60332-3-24 – Flame propagation, Category C
  • IEC 61034 – Smoke density
  • IEC 60754 – Halogen and acidic gas emissions
  • HD 308 / VDE 0293 – Core identification
APPLICATIONS
  • Public buildings with high fire safety requirements
  • Hospitals and healthcare facilities
  • Commercial and office buildings
  • Schools and educational facilities
  • Emergency power supply installations
  • Fire safety electrical circuits
  • Fixed installations in dry and wet rooms
  • Direct installation in concrete
  • Installations requiring E90 circuit integrity
  • Not suitable for direct burial in soil or installation in water