UNIMA CABLE | TECHNICAL DOCUMENTATION
NFA2X
TECHNICAL DATA SHEET
PE Insulated Aerial Bundled Aluminium Power Cable (ABC) | 0.6/1 kV
Overhead Power Cables
PRODUCT DESCRIPTION
Phase Conductors|Aluminium, Class 2
Neutral Conductors|Aluminium, Class 2
Insulation|PE Compound TIX 2
Insulation Colour|Black
Core Identification|By Ridges
Identification Method|HD 626-1, Method A
Configuration|Aerial Bundled Conductors
CABLE CONSTRUCTION
| Phase Conductors | Aluminium, Class 2 |
|---|---|
| Neutral Conductors | Aluminium, Class 2 |
| Insulation | PE Compound TIX 2 |
| Insulation Colour | Black |
| Core Identification | By Ridges |
| Identification Method | HD 626-1, Method A |
| Configuration | Aerial Bundled Conductors |
TECHNICAL DATA
| Rated Voltage | 0.6/1 kV |
|---|---|
| Test Voltage | 4 kV |
| Max. Conductor Temp. | +80°C |
| Short-Circuit Temp. | +130°C |
| Operating Temperature | -40°C to +50°C |
| Min. Laying Temperature | -10°C |
| Min. Bending Radius | 18 × D |
| CPR Class | Fca |
STANDARDS
- VDE 0276-626
- HD 626 S1
- EN 60228
- HD 626-1, Method A
APPLICATIONS
- Low voltage overhead distribution networks
- Urban and suburban electricity networks
- Rural electrification
- Remote facility power supply
- Above-ground residential connections
- Temporary and permanent overhead installations