UNIMA CABLE | Low Voltage Power Cables
NAYCWY
TECHNICAL DATA SHEET
NAYCWY | PVC Insulated Aluminium Power Cable with Concentric Copper Conductor | 0.6/1 kV

PRODUCT DESCRIPTION
NAYCWY is a 0.6/1 kV low-voltage power cable with aluminium conductors, PVC insulation, a concentric copper conductor and a black PVC outer sheath. It is designed for fixed installation indoors, outdoors, in the ground, in water and in concrete.
The cable is flame-retardant and UV-resistant. It is manufactured according to VDE 0276-603 and is suitable for power distribution applications requiring a concentric copper conductor.
CABLE CONSTRUCTION
| Main Conductor | Aluminium |
|---|---|
| Conductor Configuration | RE, RM, RMv, SE or SMv depending on cable size |
| Insulation | PVC DIV 4 |
| Concentric Conductor | Copper (Cu) |
| Outer Sheath | PVC DMV5 |
| Sheath Colour | Black |
| Core Identification | Colours according to HD 308; numbered cores for more than 5 cores |
| Meter Marking | Yes |
TECHNICAL DATA
| Rated Voltage | 0.6/1 kV |
|---|---|
| Maximum Operating Voltage (Three-Phase) | 1.2 kV |
| Nominal DC Voltage (Core-Earth/Core-Core) | 1.8/1.8 kV |
| Test Voltage | 4 kV |
| Maximum Conductor Temperature | +70°C |
| Maximum Outer Cable Temperature (Fixed) | +70°C |
| Permitted Cable Temperature (Moved) | -5°C to +70°C |
| Minimum Bending Radius (Multicore, Fixed) | 12 × D |
| Minimum Bending Radius (Single-Core, Fixed) | 15 × D |
| Flame Retardance | IEC 60332-1-2 |
| UV Resistance | Yes |
| Outdoor Use | Yes |
| Meter Marking | Yes |
STANDARDS
- Cable Standard — VDE 0276-603
- CPR Classification — Eca according to EN 50575
- Flame Retardance — VDE 0482-332-1-2 / IEC 60332-1-2
- Core Identification — HD 308
- Concentric Conductor Resistance — DIN EN 60228 / VDE 0295
APPLICATIONS
- NAYCWY is designed for fixed installation indoors, outdoors, directly in the ground, in water and in concrete.
- Suitable for low-voltage power distribution systems requiring aluminium main conductors and a concentric copper conductor.
TECHNICAL NOTES
NAYCWY cables are manufactured with aluminium main conductors and a concentric copper conductor. According to VDE 0276-603, the concentric conductor must be copper; a concentric aluminium conductor is not permitted.