UNIMA CABLE | Signal and Control Cables
LiHCH
TECHNICAL DATA SHEET
LIHCH | Halogen-Free Screened Electronic Cable | 300/500 V | Class 5 Copper

Halogen-Free HFFR
300/500 V
Class 5 Copper
AL-PES Screen
PRODUCT DESCRIPTION
LIHCH is a halogen-free, flame-retardant, low-smoke screened cable for electronic signal transmission, control and communication systems.
It features Class 5 stranded copper conductors, HFFR insulation, DIN 47100 core identification and layered core stranding.
An AL-PES tape screen with tinned copper drain wire provides electromagnetic screening. The outer sheath is grey HFFR (RAL 7001).
Rated voltage: 300/500 V. Test voltage: 2000 V. Operating temperature: -30°C to +70°C.
CABLE CONSTRUCTION
| Conductor | Class 5 Annealed Copper |
|---|---|
| Insulation | HFFR, EN 50290-2-26 |
| Core Identification | DIN 47100 |
| Core Arrangement | Twisted in Layers |
| Separator | PES Tape |
| Screen | AL-PES + Tinned Copper Drain Wire |
| Outer Sheath | HFFR, EN 50290-2-27 |
| Sheath Colour | Grey, RAL 7001 |
TECHNICAL DATA
| Rated Voltage | 300/500 V |
|---|---|
| Test Voltage | 2000 V |
| Conductor Class | Class 5, EN 60228 |
| Conductor Resistance | 7.98–79 Ω/km |
| Insulation Resistance | ≥ 200 MΩ·km |
| Mutual Capacitance | 110–150 pF/m |
| Impedance | 78 Ω |
| Inductance | 0.67 mH/km |
| Operating Temperature | -30°C to +70°C |
| Minimum Bending Radius | 10 × D |
| Available Cross-Sections | 0.22–2.50 mm² |
| Available Configurations | 96 |
STANDARDS
- VDE 0812 – Signal and Control Cable
- EN 60228 / IEC 60228 – Class 5 Copper Conductors
- VDE 0295 – Conductor Construction
- DIN 47100 – Core Colour Identification
- EN 50290-2-26 – HFFR Core Insulation
- EN 50290-2-27 – HFFR Outer Sheath
- IEC 60332-1-2 – Flame Retardance
- IEC 60332-3-24 – Flame Propagation
- IEC 61034-2 – Smoke Density
- IEC 60754-1 – Halogen-Free Test
APPLICATIONS
- Electronic Control Systems
- Signal and Information Transmission
- Audio-Frequency Signal Transmission
- Electronic Equipment Interconnections
- Communication and Control Circuits
CPR CLASS: To be confirmed according to the applicable Declaration of Performance (DoP)