UNIMA CABLE | Low Voltage Power Cables
E-YCY 0.6/1 kV
TECHNICAL DATA SHEET
E-YCY is a 0.6/1 kV power cable with bare copper conductors, PVC insulation, a concentric copper conductor and a black PVC outer sheath.

0.6/1 kV Rated Voltage
Concentric Copper Conductor
PVC Insulation and Sheath
Suitable for Underground Installation
PRODUCT DESCRIPTION
Conductor|Bare copper, Class 1; Class 2 from 25 mm²
Insulation|PVC DIV 4
Concentric Conductor|Copper wires with counter helix
Outer Sheath|PVC
Sheath Colour|Black
Core Identification|Colour-coded or numbered according to configuration
Meter Marking|Yes
CABLE CONSTRUCTION
| Conductor | Bare copper, Class 1; Class 2 from 25 mm² |
|---|---|
| Insulation | PVC DIV 4 |
| Concentric Conductor | Copper wires with counter helix |
| Outer Sheath | PVC |
| Sheath Colour | Black |
| Core Identification | Colour-coded or numbered according to configuration |
| Meter Marking | Yes |
TECHNICAL DATA
| Rated Voltage | 0.6/1 kV |
|---|---|
| Maximum System Voltage | 1.2 kV |
| Test Voltage | 4 kV |
| Maximum Conductor Temperature | +70°C |
| Short-Circuit Temperature | +160°C |
| Fixed Cable Temperature | -30°C to +70°C |
| Moved Cable Temperature | -5°C to +70°C |
| Fixed Bending Radius | 12 × D |
| Moving Bending Radius | 15 × D |
| Maximum Tensile Stress | 50 N/mm² |
| UV Resistance | Yes |
STANDARDS
- ÖVE/ÖNORM E 8200-603 (HD 603), with reference to
- IEC 60332-1-2 – Flame Retardance
- EN 50575 – CPR (classification subject to manufacturer DoP)
APPLICATIONS
- Fixed indoor installations
- Fixed outdoor installations
- Underground installation
- Installation in water
- Installation in concrete
- Power distribution systems
TECHNICAL NOTES
Technical values are based on the E-YCY reference datasheet. Cable diameters and weights are approximate. Actual specifications may vary by manufacturer. The applicable Declaration of Performance (DoP) must be verified for the supplied cable.