UNIMA CABLE
UNIMA CABLE | TECHNICAL DOCUMENTATION

NHXMH-J / NHXMH-O

TECHNICAL DATA SHEET

NHXMH-J / NHXMH-O | Halogen-Free XLPE Insulated Installation Cable | 300/500 V

NHXMH-J / NHXMH-O
PRODUCT DESCRIPTION

NHXMH-J and NHXMH-O are halogen-free installation cables rated 300/500 V, with copper conductors, XLPE insulation and a low-smoke, flame-retardant outer sheath. Designed for fixed electrical installations in residential, commercial and public buildings where reduced smoke and corrosive gas emissions are required.

CABLE CONSTRUCTION
ConductorBare copper, Class 1 (RE) or Class 2 (RM)
InsulationCross-linked polyethylene (XLPE), type 2XI1
Core IdentificationAccording to VDE 0293 / HD 308
Protective ConductorNHXMH-J with PE / NHXMH-O without PE
Outer SheathHalogen-free FRNC compound, type HM2
Sheath ColourGrey
TECHNICAL DATA
Radni napon300/500 V
Maximum System VoltageNot specified
Test Voltage2 kV AC
Materijal vodičaCopper
Conductor ClassClass 1 / Class 2
InsulationXLPE (2XI1)
Outer SheathHalogen-free compound (HM2)
Sheath ColourGrey
Maximum Conductor Temperature+70°C
Fixed Installation Temperature-40°C to +70°C
Minimum Installation Temperature+5°C
Core IdentificationHD 308 / VDE 0293
Flame PropagationIEC 60332-3-24
Smoke EmissionIEC 61034
Halogen ContentIEC 60754
CPR ClassificationAccording to variant-specific DoP
Product StandardVDE 0250-214
STANDARDS
  • VDE 0250-214 – Cable construction
  • EN 60228 – Conductors
  • EN 50575 – Construction Products Regulation (CPR)
  • IEC 60332-3-24 – Flame propagation, Category C
  • IEC 61034 – Smoke density
  • IEC 60754 – Halogen and acidic gas emissions
  • HD 308 / VDE 0293 – Core identification
APPLICATIONS
  • Residential buildings and apartments
  • Commercial and office buildings
  • Schools, hospitals and public buildings
  • Fixed electrical installations on and under plaster
  • Installation in dry and wet indoor areas
  • Installation in concrete, excluding shaken or tamped concrete
  • Electrical distribution where halogen-free cables are required
  • Not intended for direct burial in soil or installation in water