UNIMA CABLE | TECHNICAL DOCUMENTATION
(N)HXH-J / (N)HXH-O FE180/E90
TECHNICAL DATA SHEET
(N)HXH-J / (N)HXH-O | Halogen-Free Fire Resistant Power Cable | FE180/E90 | 0.6/1 kV

PRODUCT DESCRIPTION
(N)HXH-J and (N)HXH-O FE180/E90 are halogen-free, fire-resistant power cables rated 0.6/1 kV, manufactured with bare copper conductors, FRNC HI1 insulation and an orange FRNC HM1 outer sheath.
Designed for fixed electrical installations in dry and wet rooms, these cables provide FE180 fire resistance and E90 circuit integrity when installed with appropriately tested support systems in accordance with DIN 4102-12.
Suitable for public buildings and installations with high fire safety requirements. Not intended for direct burial in soil or installation in water.
CABLE CONSTRUCTION
| Conductor | Bare copper, Class 1 (RE); from 25 mm² Class 2 (RM) |
|---|---|
| Insulation | Fire-resistant FRNC compound, type HI1 |
| Core Identification | According to HD 308 / VDE 0293 |
| Protective Conductor | (N)HXH-J with PE / (N)HXH-O without PE |
| Outer Sheath | Halogen-free FRNC compound, type HM1 |
| Sheath Colour | Orange |
TECHNICAL DATA
| Radni napon | 0.6/1 kV |
|---|---|
| Maximum System Voltage | 1.2 kV |
| Test Voltage | 4 kV AC |
| Materijal vodiča | Bare Copper |
| Conductor Class | Class 1 (RE) / Class 2 (RM) |
| Insulation | FRNC HI1 |
| Outer Sheath | FRNC HM1 |
| Sheath Colour | Orange |
| Maximum Conductor Temperature | +90°C |
| Fixed Installation Temperature | -30°C to +90°C |
| Minimum Movement Temperature | -5°C |
| Minimum Bending Radius Multicore | 12 x Outer Diameter |
| Minimum Bending Radius Single-Core | 15 x Outer Diameter |
| Fire Resistance | FE180 |
| Circuit Integrity | E90 (tested installation system) |
| Flame Propagation | IEC 60332-3-24 (Cat. C) |
| Smoke Emission | IEC 61034 |
| Halogen-Free | IEC 60754 |
| CPR Classification | According to applicable DoP |
| Product Standard | VDE 0266 |
STANDARDS
- VDE 0266 – Cable construction
- VDE 0472-814 / IEC 60331-11 – FE180 fire resistance
- DIN 4102-12 – E90 circuit integrity
- IEC 60332-3-24 – Flame propagation, Category C
- IEC 61034 – Smoke density
- IEC 60754 – Halogen and acidic gas emissions
- HD 308 / VDE 0293 – Core identification
APPLICATIONS
- Public buildings with high fire safety requirements
- Hospitals and healthcare facilities
- Commercial and office buildings
- Schools and educational facilities
- Emergency power supply installations
- Fire safety electrical circuits
- Fixed installations in dry and wet rooms
- Direct installation in concrete
- Installations requiring E90 circuit integrity
- Not suitable for direct burial in soil or installation in water