UNIMA CABLE | Low Voltage Power Cables
NAY2Y
TECHNICAL DATA SHEET
PVC Insulated Aluminium Power Cable with Polyethylene Sheath | 0.6/1 kV

PRODUCT DESCRIPTION
NAY2Y is a 0.6/1 kV low-voltage power cable with aluminium conductors, PVC insulation and a black polyethylene DMP2 outer sheath.
Designed for fixed installation indoors, outdoors, directly in the ground, in water and in concrete.
The cable is available in NAY2Y-J configurations with a protective conductor and NAY2Y-O configurations without a protective conductor.
The maximum permissible conductor temperature is +70°C. The outer sheath is UV-resistant and suitable for outdoor use.
The cable is not classified as flame-retardant in the reference technical documentation. CPR classification must be confirmed for the actual product supplied.
CABLE CONSTRUCTION
| Conductor | Aluminium (Al) |
|---|---|
| Conductor Shape | RE, SE, RMv, SMv |
| Insulation | PVC |
| Outer Sheath | Polyethylene DMP2 |
| Sheath Colour | Crna |
| Configuration | NAY2Y-J / NAY2Y-O |
| Core Identification | VDE 0293 / HD 308 |
| Meter Marking | Yes |
TECHNICAL DATA
| Radni napon | 0.6/1 kV |
|---|---|
| Max. System Voltage | 1.2 kV |
| Test Voltage | 4 kV |
| Max. Conductor Temp. | +70°C |
| Moved Temp. Range | -20°C to +70°C |
| Bending Radius (Multicore) | 12 × D |
| Bending Radius (Single-Core) | 15 × D |
| Materijal vodiča | Aluminium |
| Insulation | PVC |
| Outer Sheath | PE DMP2 |
| UV Resistance | Yes |
| Flame Retardance | No |
STANDARDS
- Cable Standard|VDE 0276-603
- Core Identification|VDE 0293 / HD 308
- Flame Retardance|Not flame-retardant
- CPR Classification|Not specified
APPLICATIONS
- Fixed low-voltage power distribution installations indoors and outdoors.
- Suitable for direct installation in the ground, in water and in concrete.
- Designed for permanent electrical installations requiring aluminium conductors, PVC insulation and a polyethylene outer sheath.